HOT WATER SYSTEM Test Form

SOFTWARE FUNCTIONAL TEST FORM -1

Form No: ECC-NSCKWE-BMS-


Project: PROJECT THE ECC & NDCS @ SGH TESTFROM-0001

Equipment ID: HWS-XX-XX Date: Revision: 0

Process Description: Testing and Commissioning of HWS-XX-XX

Area/Location: Panel ID: DDC-XX-XX

EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

CALORIFIER C/W STANDBY


TEST – 1 ELECTRIC HEATER Status
Monitoring Points

Monitor the Incoming Power HWS-W-XX-XX_IncPwrSts=


(LMCP) Status is “Normal” “NORMAL”
1
Switch off the Incoming Power HWS-W-XX-XX_IncPwrSts=
(LMCP) Status is “Alarm” “ALARM”

Monitor the Status is “ON” HWS-XX-XX_Sts = “ON”


2
Monitor the Status is “OFF” HWS-XX-XX_Sts = “OFF”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Check the Trip condition is


“Normal” HWS-XX-XX_Trip = “NORMAL”
3
Simulate the Trip condition is HWS-XX-XX_Trip = “Alarm”
“Alarm”

Check the Common Alarm


condition is “Normal” HWS-XX-XX_Trip = “NORMAL”
4
Simulate the condition is HWS-XX-XX_Trip = “ALARM”
“Alarm”

Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”


5
Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”

Monitor the Valve Status is


“OPEN” HWS-XX-XX_Sts = “OPEN”
6
Monitor the Value Status is HWS-XX-XX_Sts = “CLOSE”
“CLOSE”

Monitor the Heater Status is


“ON” HWS-XX-XX_Sts = “ON”
7
Monitor the Heater Status is HWS-XX-XX_Sts = “OFF”
“OFF”

Send Command to "OPEN" HWS-XX-XX_DampCmd = “OPEN”


8
Send Command to "CLOSE" HWS-XX-XX_DampCmd = “CLOSE”

Monitor the Hot Water Valve


Status is “ON” HWS-XX-XX_Sts = “ON”
9
Monitor the Hot Water Valve HWS-XX-XX_Sts = “OFF”
Status is “OFF”

TEST –2 Analog input Monitoring Points


EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Hotwater storage temp1 sensor


readings
Check the Hot water Storage
1
temperature sensor.
HWS-XX-XX _RmT = ____________
ºC

Hotwater storage temp2 sensor


readings
Check the Hot water Storage
2
temperature sensor.
HWS-XX-XX _RmT = ____________
ºC

TEST – 3 Monitoring Power meter

BMS Site Reading


Ensure the power consumption Reading
1 reading from site tally with BMS
reading.
kWh

BMS Site Reading


Reading
Ensure the power reading from
2
site tally with BMS reading.

kW

CALORIFIER C/W STANDBY


TEST – 4 ELECTRIC HEATER High
Level Integration.

Test the CALORIFIER C/W All the parameters are displayed in


1 STANDBY ELECTRIC BMS as per BMS interface
HEATER for HLI. document.

HOT WATER CIRCULATION


TEST – 5 PUMPS Status Monitoring
Points

1 Monitor the Status is “ON” HWS-XX-XX_Sts = “ON”


EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Monitor the Status is “OFF” HWS-XX-XX_Sts = “OFF”

Check the Trip condition is


“Normal” HWS-XX-XX_Trip = “NORMAL”
2
Simulate the Trip condition is HWS-XX-XX_Trip = “Alarm”
“Alarm”

Check the Common Alarm


condition is “Normal” HWS-XX-XX_Trip = “NORMAL”
3
Simulate the condition is HWS-XX-XX_Trip = “ALARM”
“Alarm”

Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”


4
Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”

Monitor the Valve Status is


“OPEN” HWS-XX-XX_Sts = “OPEN”
5
Monitor the Value Status is HWS-XX-XX_Sts = “CLOSE”
“CLOSE”

Send Command to "OPEN" HWS-XX-XX_DampCmd = “OPEN”


6
Send Command to "CLOSE" HWS-XX-XX_DampCmd = “CLOSE”

Monitor the Hot Water Valve


Status is “ON” HWS-XX-XX_Sts = “ON”
7
Monitor the Hot Water Valve HWS-XX-XX_Sts = “OFF”
Status is “OFF”

Verification of Hot water


TEST-6 HWS-XX-XX _RmTemp =______ ºC
Temperature VSD control

Adjust the Hot water VSD Command to modulate to ramp


Temperature re set point value down the speed:
1
below the Room Temperature
reading HWS-XX-XX _VSDCtrl =______%
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

HWS-XX-XX _VSDFdb =______%

VSD Command to modulate to ramp


Adjust the Hot water up the speed:
Temperature set point value
2
above the Room Temperature HWS-XX-XX _VSDCtrl =______%
reading
HWS-XX-XX _VSDFdb =______%

HOT WATER CIRCULATION


TEST – 7
PUMPS High Level Integration.

All the parameters are displayed in


Test the HOT WATER
1 BMS as per BMS interface
CIRCULATION PUMPS for HLI.
document.

HOT WATER RETURN


TEST – 8 PUMPS Status Monitoring
Points

Monitor the Status is “ON” HWS-XX-XX_Sts = “ON”


1
Monitor the Status is “OFF” HWS-XX-XX_Sts = “OFF”

Check the Trip condition is


“Normal” HWS-XX-XX_Trip = “NORMAL”
2
Simulate the Trip condition is HWS-XX-XX_Trip = “Alarm”
“Alarm”

Check the Common Alarm


condition is “Normal” HWS-XX-XX_Trip = “NORMAL”
3
Simulate the condition is HWS-XX-XX_Trip = “ALARM”
“Alarm”

Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”


4
Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Monitor the Valve Status is


“OPEN” HWS-XX-XX_Sts = “OPEN”
5
Monitor the Value Status is HWS-XX-XX_Sts = “CLOSE”
“CLOSE”

Send Command to "OPEN" HWS-XX-XX_DampCmd = “OPEN”


6
Send Command to "CLOSE" HWS-XX-XX_DampCmd = “CLOSE”

Monitor the Hot Water Valve


Status is “ON” HWS-XX-XX_Sts = “ON”
7
Monitor the Hot Water Valve HWS-XX-XX_Sts = “OFF”
Status is “OFF”

Verification of Hot water


TEST-9 HWS-XX-XX _RmTemp =______ ºC
Temperature VSD control

VSD Command to modulate to ramp


Adjust the Hot water down the speed:
Temperature re set point value
1
below the Room Temperature HWS-XX-XX _VSDCtrl =______%
reading
HWS-XX-XX _VSDFdb =______%

VSD Command to modulate to ramp


Adjust the Hot water up the speed:
Temperature set point value
2
above the Room Temperature HWS-XX-XX _VSDCtrl =______%
reading
HWS-XX-XX _VSDFdb =______%

TEST – HOT WATER RETURN


10 PUMPS High Level Integration.

All the parameters are displayed in


Test the HOT WATER
1 BMS as per BMS interface
RETURN PUMPS for HLI.
document.
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

COLD WATER MAKEUP


TEST –
SUPPLY Status Monitoring
11
Points

Cold water pressure sensor readings


Check the cold water supply
1
temperature sensor. HWS-XX-XX _RmT = ____________
pa

Cold water pressuresensor readings


Check the Hot water Storage
2
Pressure sensor. HWS-XX-XX _RmT = ____________
pa

Clod water flow ensor readings


Check the Clod water flow
3
sensor. HWS-XX-XX _RmT
=___________m3/h

TEST – COLD WATER MAKEUP


12 SUPPLY High Level Integration.

All the parameters are displayed in


Test the COLD WATER
1 BMS as per BMS interface
MAKEUP SUPPLY for HLI.
document.

TEST – HOT WATER SYSTEM Status


13 Monitoring Points

Hot water Temperature sensor


readings
Check the Hot water supply
1
temperature sensor.
HWS-XX-XX _RmT = ___________
ºC

Hot water Temperature sensor


readings
Check the Hot water return
2
temperature sensor.
HWS-XX-XX _RmT = ____________
ºC
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Hot water supply flow rate readings


Check the Hot water supply
3
flow rate sensor. HWS-XX-XX _RmT =
__________m3/h

Hot water return flow rate readings


Check the Hot water return flow
4
rate sensor. HWS-XX-XX _RmT =
__________m3/h

Hot water supply pressure sensor


readings
Check the Hot water supply
5
pressure sensor.
HWS-XX-XX _RmT = ___________
ºC

Hot water return pressure sensor


readings
Check the Hot water return
6
pressure sensor.
HWS-XX-XX _RmT = ____________
ºC

TEST – HOT WATER SYSTEM


14 High Level Integration.

All the parameters are displayed in


Test the HOT WATER
1 BMS as per BMS interface
SYSTEM for HLI.
document.

LMCP FOR CALORIFIER C/W


TEST – STANDBY ELECTRIC
15 HEATER Status Monitoring
Points

Monitor the Incoming Power HWS-W-XX-XX_IncPwrSts=


(LMCP) Status is “Normal” “NORMAL”
1
Switch off the Incoming Power HWS-W-XX-XX_IncPwrSts=
(LMCP) Status is “Alarm” “ALARM”

2
Monitor the Status is “ON” HWS-XX-XX_Sts = “ON”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Monitor the Status is “OFF” HWS-XX-XX_Sts = “OFF”

Check the Trip condition is


“Normal” HWS-XX-XX_Trip = “NORMAL”
3
Simulate the Trip condition is HWS-XX-XX_Trip = “Alarm”
“Alarm”

Check the Common Alarm


condition is “Normal” HWS-XX-XX_Trip = “NORMAL”
4
Simulate the condition is HWS-XX-XX_Trip = “ALARM”
“Alarm”

Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”


5
Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”

Monitor the Heater Status is


“ON” HWS-XX-XX_Sts = “ON”
6
Monitor the Heater Status is HWS-XX-XX_Sts = “OFF”
“OFF”

Monitor the Hot Water Valve


Status is “ON” HWS-XX-XX_Sts = “ON”
7
Monitor the Hot Water Valve HWS-XX-XX_Sts = “OFF”
Status is “OFF”

TEST –
Monitoring Power meter
16

BMS Site Reading


Ensure the power consumption Reading
1 reading from site tally with BMS
reading.
kWh

2
Ensure the power reading from BMS Site Reading
site tally with BMS reading. Reading
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

kW

BMS Site Reading


Reading
Ensure the power reading from
3
site tally with BMS reading.

Volt

BMS Site Reading


Reading
Ensure the power reading from
4
site tally with BMS reading.

Amp

BMS Site Reading


Ensure the power factor rating Reading
5 reading from site tally with BMS
reading.
PwFtr

LMCP FOR CALORIFIER C/W


TEST – STANDBY ELECTRIC
17 HEATER High Level
Integration.

Test the LMCP FOR All the parameters are displayed in


1 CALORIFIER C/W STANDBY BMS as per BMS interface
ELECTRIC HEATER for HLI. document.

LMCP FOR CIRCULATION


TEST –
PUMPS Status Monitoring
18
Points

Monitor the Incoming Power HWS-W-XX-XX_IncPwrSts=


(LMCP) Status is “Normal” “NORMAL”
1
Switch off the Incoming Power HWS-W-XX-XX_IncPwrSts=
(LMCP) Status is “Alarm” “ALARM”

2 Monitor the Status is “ON” HWS-XX-XX_Sts = “ON”


EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Monitor the Status is “OFF” HWS-XX-XX_Sts = “OFF”

Check the Trip condition is


“Normal” HWS-XX-XX_Trip = “NORMAL”
3
Simulate the Trip condition is HWS-XX-XX_Trip = “Alarm”
“Alarm”

Check the Common Alarm


condition is “Normal” HWS-XX-XX_Trip = “NORMAL”
4
Simulate the condition is HWS-XX-XX_Trip = “ALARM”
“Alarm”

Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”


5
Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”

Monitor the Heater Status is


“ON” HWS-XX-XX_Sts = “ON”
6
Monitor the Heater Status is HWS-XX-XX_Sts = “OFF”
“OFF”

Monitor the Hot Water Valve


Status is “ON” HWS-XX-XX_Sts = “ON”
7
Monitor the Hot Water Valve HWS-XX-XX_Sts = “OFF”
Status is “OFF”

TEST –
Analog Input points
19

Hot water Temperature sensor


readings
Check the Hot water supply
1
temperature sensor.
HWS-XX-XX _RmT = ___________
ºC

2
Check the Hot water return Hot water Temperature sensor
temperature sensor. readings
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

HWS-XX-XX _RmT = ____________


ºC

TEST –
Monitoring Power meter
20

BMS Site Reading


Ensure the power consumption Reading
1 reading from site tally with BMS
reading.
kWh

BMS Site Reading


Reading
Ensure the power reading from
2
site tally with BMS reading.

kW

BMS Site Reading


Reading
Ensure the power reading from
3
site tally with BMS reading.

Volt

BMS Site Reading


Reading
Ensure the power reading from
4
site tally with BMS reading.

Amp

BMS Site Reading


Ensure the power factor rating Reading
5 reading from site tally with BMS
reading.
PwFtr

TEST – LMCP FOR CIRCULATION


21 PUMPS High Level Integration.
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

All the parameters are displayed in


Test the LMCP FOR
1 BMS as per BMS interface
CIRCULATION PUMPS for HLI.
document.

LMCP FOR HOT WATER


TEST –
RETURN PUMPS Status
22
Monitoring Points

Monitor the Incoming Power HWS-W-XX-XX_IncPwrSts=


(LMCP) Status is “Normal” “NORMAL”
1
Switch off the Incoming Power HWS-W-XX-XX_IncPwrSts=
(LMCP) Status is “Alarm” “ALARM”

Monitor the Status is “ON” HWS-XX-XX_Sts = “ON”


2
Monitor the Status is “OFF” HWS-XX-XX_Sts = “OFF”

Check the Trip condition is


“Normal” HWS-XX-XX_Trip = “NORMAL”
3
Simulate the Trip condition is HWS-XX-XX_Trip = “Alarm”
“Alarm”

Check the Common Alarm


condition is “Normal” HWS-XX-XX_Trip = “NORMAL”
4
Simulate the condition is HWS-XX-XX_Trip = “ALARM”
“Alarm”

Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”


5
Monitor the Mode to “Local” HWS-XX-XX_Mode = “LOCAL”

Monitor the Heater Status is


“ON” HWS-XX-XX_Sts = “ON”
6
Monitor the Heater Status is HWS-XX-XX_Sts = “OFF”
“OFF”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Monitor the Hot Water Valve


Status is “ON” HWS-XX-XX_Sts = “ON”
7
Monitor the Hot Water Valve HWS-XX-XX_Sts = “OFF”
Status is “OFF”

TEST –
Analog Input points
23

Hot water Temperature sensor


readings
Check the Hot water supply
1
temperature sensor.
HWS-XX-XX _RmT = ___________
ºC

Hot water Temperature sensor


readings
Check the Hot water return
2
temperature sensor.
HWS-XX-XX _RmT = ____________
ºC

TEST –
Monitoring Power meter
24

BMS Site Reading


Ensure the power consumption Reading
1 reading from site tally with BMS
reading.
kWh

BMS Site Reading


Reading
Ensure the power reading from
2
site tally with BMS reading.

kW

BMS Site Reading


Reading
Ensure the power reading from
3
site tally with BMS reading.

Volt
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

BMS Site Reading


Reading
Ensure the power reading from
4
site tally with BMS reading.

Amp

BMS Site Reading


Ensure the power factor rating Reading
5 reading from site tally with BMS
reading.
PwFtr

LMCP FOR HOT WATER


TEST –
RETURN PUMPS High Level
25
Integration.

Test the LMCP FOR HOT All the parameters are displayed in
1 WATER RETURN PUMPS for BMS as per BMS interface
HLI. document.

Tested By: Acknowledged


Honeywell Pte Ltd
By: Kilowatts

NAME: NAME:

DATE: DATE:

Submitted and Penta-Ocean Construction Co, Witnessed and


RE/RTO
Checked By: Ltd. Checked BY:

NAME: NAME:
DATE: DATE: