PAU - DX Type (ACMV-2) T&C
PAU - DX Type (ACMV-2) T&C
PAU - DX Type (ACMV-2) T&C
EXPECTED RESULT
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
3.
Monitor the Mode to “Local” PAU-XX-XX_Mode = “LOCAL”
4.
Switch the Mode to “BMS” PAU-XX-XX_Mode = “BMS”
EXPECTED RESULT
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
PAU-XX-XX_Trip = “Alarm”
10. Simulate the Trip condition is
“Alarm”
PAU-XX-XX_Sts = “OFF”
11.
Send Command to "OPEN" PAU-XX-XX_ChwVlvCmd = “OPEN”
13.
Send Command to "CLOSE" PAU-XX-XX_DmprCmd = “CLOSE”
EXPECTED RESULT
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
PAU-XX-XX_VSDTrip = “Alarm”
19. Simulate the VSD Trip condition
is “Alarm”
PAU-XX-XX_VSDSts = “OFF”
PAU-XX-XX_SmkAlm = “ALARM”
20. Simulate the Smoke alarm
condition is “Alarm”
PAU-XX-XX_Sts = “OFF”
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
PAU-XX-XX_PreFilAlm = “NORMAL”
PAU-XX-XX_PreFilAlm = “ALARM”
Simulate the Pre-filter and
26.
Second filter alarm condition to PAU-XX-XX_SecFilAlm = “ALARM”
“Alarm”
PAU-XX-XX_TertiaFilAlm = “ALARM”
5.
Monitor the Status is “ON” HRU-W-XX-XX_Sts = “ON
6.
Send command to “Stop” HRU-W-XX-XX_SS = “STOP”
7.
Monitor the Status is “OFF” HRU-W-XX-XX_Sts = “OFF”
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
HRU-W-XX-XX_Trip = “Alarm”
9. Simulate the Trip condition is
“Alarm”
HRU-W-XX-XX_Sts = “OFF”
5.
Monitor the Status is “ON” HRU-A-XX-XX_Sts = “ON
6.
Send command to “Stop” HRU-A-XX-XX_SS = “STOP”
7.
Monitor the Status is “OFF” HRU-A-XX-XX_Sts = “OFF”
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
HRU-A-XX-XX_Trip = “Alarm”
9. Simulate the Trip condition is
“Alarm”
HRU-A-XX-XX_Sts = “OFF”
1. Check the Chilled Water Supply Chilled Water Supply Temp Sensor
Temp Sensor. readings: ______ ºC
2. Check the Chilled Water Return Chilled Water Return Temp Sensor
Temp Sensor. readings ______ ºC
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
2.
Adjust the static pressure set VSD Command to modulate to ramp
point value above the static up the speed:
EXPECTED RESULT
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
TEST –
Monitoring Power meter LCMP-PAU
10
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
kWh
kW
Volt
Amp
TEST –
Monitoring Power meter LMCP-Hot Water
11
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
kW
Volt
Amp
TEST –
Monitoring Power meter LMCP-AIR
12
kW
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
Volt
Amp
NAME: NAME:
DATE: DATE:
NAME: NAME:
DATE: DATE: