PAU – DX TYPE Test Form

SOFTWARE FUNCTIONAL TEST FORM

Form No: ECC-NSCKWE-BMS-


Project: PROJECT THE ECC & NDCS @ SGH TESTFROM-0001

Equipment ID: PAU-XX-XX Date: Revision: 0

Process Description: Testing and Commissioning of PAU-XX-XX

Area/Location: Panel ID: DDC-XX-XX

EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

TEST – 1 PAU Status Monitoring Points PAU

1. Monitor the Incoming Power


PAU-XX-XX_IncPwrSts= “NORMAL”
Status is “Normal”

2. Switch off the Incoming Power


PAU-XX-XX_IncPwrSts= “ALARM”
Status is “Alarm”

3.
Monitor the Mode to “Local” PAU-XX-XX_Mode = “LOCAL”

4.
Switch the Mode to “BMS” PAU-XX-XX_Mode = “BMS”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Send command to “Start”.


5.
PAU-XX-XX_Start = “START”
When Time Program to
“Occupied.”

Monitor the Status is “ON”


PAU-XX-XX_Sts = “ON

6. Monitor the VSD Status is “ON”


PAU-XX-XX_VSDSts = “ON

Monitor the Airflow Status


PAU-XX-XX-FlowSts=” Flow”
“Flow”

Send command to “Stop”.


7.
PAU-XX-XX_SS = “STOP”
When Time Program to
“Unoccupied”

Monitor the Status is “OFF”


PAU-XX-XX_Sts = “OFF”
Monitor the VSD Status is
8.
“OFF” PAU-XX-XX_VSDSts = “OFF”

Monitor the Airflow Status “No PAU-XX-XX-FlowSts=” No Flow”


Flow”

9. Chec k the Trip condition is


PAU-XX-XX_Trip = “NORMAL”
“Normal”

PAU-XX-XX_Trip = “Alarm”
10. Simulate the Trip condition is
“Alarm”
PAU-XX-XX_Sts = “OFF”

11.
Send Command to "OPEN" PAU-XX-XX_ChwVlvCmd = “OPEN”

12. Monitor the Damper Status to


PAU-XX-XX_DmprSts = “OPEN”
“OPEN”

13.
Send Command to "CLOSE" PAU-XX-XX_DmprCmd = “CLOSE”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

14. Monitor the Damper Status to


PAU-XX-XX_DmprSts = “CLOSE”
“CLOSE”

15. Check the Smoke alarm


PAU-XX-XX_SmkAlm = “NORMAL”
condition is “Normal”

16. Check VSD common group PAU-XX-XX_VSDCmnAlm =


alarm condition is “Normal” “NORMAL”

17. Simulate the VSD common PAU-XX-XX_VSDCmnAlm =


group alarm condition is “Alarm” “ALARM”

18. Check the VSD Trip condition is


PAU-XX-XX_VSDTrip = “NORMAL”
“Normal”

PAU-XX-XX_VSDTrip = “Alarm”
19. Simulate the VSD Trip condition
is “Alarm”
PAU-XX-XX_VSDSts = “OFF”

PAU-XX-XX_SmkAlm = “ALARM”
20. Simulate the Smoke alarm
condition is “Alarm”
PAU-XX-XX_Sts = “OFF”

21. Monitor the Electrical Duct


PAU-XX-XX_DuctHtrSts = “ON”
Heater Status is “ON”

22. Monitor the Electrical Duct


PAU-XX-XX_DuctHtrSts = “OFF”
Heater Status is “OFF”

23. Monitor the UV Lights Status is


PAU-XX-XX_LightSts = “ON”
“ON”

24. Monitor the UV Lights Status is


PAU-XX-XX_LightSts = “OFF”
“OFF”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

PAU-XX-XX_PreFilAlm = “NORMAL”

Check the Pre-filter, second


25. PAU-XX-XX_SecFilAlm = “NORMAL”
filter and Tertiary filter alarm
condition is “Normal”
PAU-XX-XX_TertiaFilAlm =
“NORMAL”

PAU-XX-XX_PreFilAlm = “ALARM”
Simulate the Pre-filter and
26.
Second filter alarm condition to PAU-XX-XX_SecFilAlm = “ALARM”
“Alarm”
PAU-XX-XX_TertiaFilAlm = “ALARM”

DX-HRU (Hot Water)


TEST – 2 DX-HRU (Hot Water)
Monitoring Points

1. Monitor the Incoming Power HRU-W-XX-XX_IncPwrSts=


(LMCP) Status is “Normal” “NORMAL”

2. Switch off the Incoming Power HRU-W-XX-XX_IncPwrSts=


(LMCP) Status is “Alarm” “ALARM”

3. Monitor the (LMCP) Mode to


HRU-W-XX-XX_Mode = “LOCAL”
“Local”

4. Switch the Mode (LMCP) to


HRU-W-XX-XX_Mode = “BMS”
“BMS”

5.
Monitor the Status is “ON” HRU-W-XX-XX_Sts = “ON

6.
Send command to “Stop” HRU-W-XX-XX_SS = “STOP”

7.
Monitor the Status is “OFF” HRU-W-XX-XX_Sts = “OFF”

8. Check the Trip condition is


HRU-W-XX-XX_Trip = “NORMAL”
“Normal”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

HRU-W-XX-XX_Trip = “Alarm”
9. Simulate the Trip condition is
“Alarm”
HRU-W-XX-XX_Sts = “OFF”

10. Check common group alarm HRU-W-XX-XX_CmnAlm =


condition is “Normal” “NORMAL”

11. Simulate the common group


HRU-W-XX-XX_CmnAlm = “ALARM”
alarm condition is “Alarm”

DX-HRU (Air Side) Monitoring


TEST-3 DX-HRU (Air Side)
Points

1. Monitor the Incoming Power HRU-A-XX-XX_IncPwrSts=


(LMCP) Status is “Normal” “NORMAL”

2. Switch off the Incoming Power


HRU-A-XX-XX_IncPwrSts= “ALARM”
(LMCP) Status is “Alarm”

3. Monitor the (LMCP) Mode to


HRU-A-XX-XX_Mode = “LOCAL”
“Local”

4. Switch the Mode (LMCP) to


HRU-A-XX-XX_Mode = “BMS”
“BMS”

5.
Monitor the Status is “ON” HRU-A-XX-XX_Sts = “ON

6.
Send command to “Stop” HRU-A-XX-XX_SS = “STOP”

7.
Monitor the Status is “OFF” HRU-A-XX-XX_Sts = “OFF”

8. Check the Trip condition is


HRU-A-XX-XX_Trip = “NORMAL”
“Normal”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

HRU-A-XX-XX_Trip = “Alarm”
9. Simulate the Trip condition is
“Alarm”
HRU-A-XX-XX_Sts = “OFF”

10. Check common group alarm HRU-A-XX-XX_CmnAlm =


condition is “Normal” “NORMAL”

11. Simulate the common group


HRU-A-XX-XX_CmnAlm = “ALARM”
alarm condition is “Alarm”

TEST –4 Analog input Monitoring Points

1. Check the Chilled Water Supply Chilled Water Supply Temp Sensor
Temp Sensor. readings: ______ ºC

2. Check the Chilled Water Return Chilled Water Return Temp Sensor
Temp Sensor. readings ______ ºC

Chilled Water Flow Rate Sensor


readings
3. Check the Chilled Water Flow
Rate Sensor.
PAU-XX-XX _ChwFlw = ________
L/s

Supply air temp sensor readings


4. Check the Supply air
temperature sensor. PAU-XX-XX _SaT = ____________
ºC

Fresh air temp sensor readings


5. Check the Fresh air
temperature sensor. PAU-XX-XX _FaT = ____________
ºC

Air flow switch sensor readings


6. Check the Air flow switch
sensor. PAU-XX-XX _Airflw = _________
cmh
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Duct Air Humidity readings


7. Check the Duct Air Humidity
sensor. PAU-XX-XX _Humidity = ________
%

Scr Heater Output/Kw Measurement /


Check the Scr Heater Feedback reading.
8.
Output/Kw Measurement /
Feedback.
PAU-XX-XX _HtrFbk = ________ %

Duct Static Pressure Sensor


Readings.

9. Check the Duct Static Pressure HRU-W-XX-XX _StaPrs1 =______


sensor. Pa

HRU-W-XX-XX _StaPrs2 =______


Pa

Chilled Water Valve Position


Feedback Readings

10. Check the Chilled Water Valve HRU-W-XX-XX _CVlvFdb1 =______


Position Feedback. %

HRU-W-XX-XX _CVlvFdb2 =______


%

Verification of Valve control


TEST – 5 selection under Off coil PAU-XX-XX _Offcoil =______ ºC
Temperature mode.

Simulate Chilled Water Valve


1. Control selection software PAU-XX-XX_Tem pCtrl =
switch in to “Off coil OFFTempMode
Temperature Control” position

Valve Command to modulate to open


position:
Adjust temperature set point
2.
value below the Off coil
PAU-XX-XX _CVlvCtrl =______%
Temperature reading.

PAU-XX-XX _CVlvFdb =______%


EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Valve Command to modulate to close


position:
Adjust temperature set point
3.
value above the Off coil
PAU-XX-XX _CVlvCtrl =______%
Temperature reading.

PAU-XX-XX _CVlvFdb =______%

Verification of Valve control


PAU-XX-XX _SupAirTemp =______
TEST – 6 selection under Supply Air
ºC
Temperature mode.

Simulate Chilled Water Valve


1. Control selection software PAU-XX-XX_TempCtrl =
switch in to “Supply Air SuppAirTempMode
Temperature Control” position

Valve Command to modulate to open


position:
Adjust temperature set point
2.
value below the Supply Air
PAU-XX-XX _CVlvCtrl =______%
Temperature reading.

PAU-XX-XX _CVlvFdb =______%

Valve Command to modulate to close


position:
Adjust temperature set point
3.
value above the Supply Air
PAU-XX-XX _CVlvCtrl =______%
Temperature reading.

PAU-XX-XX _CVlvFdb =______%

Verification of Static pressure


TEST-7 PAU-XX-XX _StaPrs =______ Pa
VSD control

VSD Command to modulate to ramp


down the speed:
Adjust the static pressure set
1. point value below the static
PAU-XX-XX _VSDCtrl =______%
pressure reading

PAU-XX-XX _VSDFdb =______%

2.
Adjust the static pressure set VSD Command to modulate to ramp
point value above the static up the speed:
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

PAU-XX-XX _VSDCtrl =______%


pressure reading
PAU-XX-XX _VSDFdb =______%

Verification of Fresh Air Damper


TEST-8 PAU-XX-XX _CO2 =______ ppm
control

Fresh air damper control modulates


to open position.
Adjust CO2 set point value
1.
below the Return air CO2
PAU-XX-XX _FaDmpCtrl =______%
reading.

PAU-XX-XX _FaDmpFdb =______%

Fresh air damper control modulates


to close position.
Adjust CO2 set point value
2.
above the Return Air CO2
PAU-XX-XX _FaDmpCtrl =______%
reading.

PAU-XX-XX _FaDmpFdb =______%

TEST –9 Monitoring BTU meter

BMS Reading Site Reading


Ensure the BTU consumption
1. reading from site tally with BMS
reading.
kWh

BMS Reading Site Reading


Ensure the BTU reading from
2.
site tally with BMS reading.
kWh

TEST –
Monitoring Power meter LCMP-PAU
10

1 Ensure the power consumption BMS Site Reading


reading from site tally with BMS Reading
reading.
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

kWh

BMS Site Reading


Reading
Ensure the power reading from
2
site tally with BMS reading.

kW

BMS Site Reading


Reading
Ensure the power reading from
3
site tally with BMS reading.

Volt

BMS Site Reading


Reading
Ensure the power reading from
4
site tally with BMS reading.

Amp

BMS Site Reading


Ensure the power factor rating Reading
5 reading from site tally with BMS
reading.
PwFtr

TEST –
Monitoring Power meter LMCP-Hot Water
11

BMS Site Reading


Ensure the power consumption Reading
1 reading from site tally with BMS
reading.
kWh

BMS Site Reading


Ensure the power reading from Reading
2
site tally with BMS reading.
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

kW

BMS Site Reading


Reading
Ensure the power reading from
3
site tally with BMS reading.

Volt

BMS Site Reading


Reading
Ensure the power reading from
4
site tally with BMS reading.

Amp

BMS Site Reading


Ensure the power factor rating Reading
5 reading from site tally with BMS
reading.
PwFtr

TEST –
Monitoring Power meter LMCP-AIR
12

BMS Site Reading


Ensure the power consumption Reading
1 reading from site tally with BMS
reading.
kWh

BMS Site Reading


Reading
Ensure the power reading from
2
site tally with BMS reading.

kW

BMS Site Reading


Ensure the power reading from Reading
3
site tally with BMS reading.
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Volt

BMS Site Reading


Reading
Ensure the power reading from
4
site tally with BMS reading.

Amp

BMS Site Reading


Ensure the power factor rating Reading
5 reading from site tally with BMS
reading.
PwFtr

Tested By: Acknowledged


Honeywell Pte Ltd
By: Kilowatts

NAME: NAME:

DATE: DATE:

Submitted and Penta-Ocean Construction Witnessed and


RE/RTO
Checked By: Co,Lto. Checked BY:

NAME: NAME:

DATE: DATE: