DX-Air Handling Unit T&C
DX-Air Handling Unit T&C
EXPECTED RESULT
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
3.
Monitor the Mode to “Local” AHU-XX-XX_Mode = “LOCAL”
4.
Switch the Mode to “BMS” AHU-XX-XX_Mode = “BMS”
EXPECTED RESULT
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
6.
Monitor the Status is “ON” AHU-XX-XX_Sts = “ON
8.
Monitor the Status is “OFF” AHU-XX-XX_Sts = “OFF”
AHU-XX-XX_Trip = “Alarm”
10. Simulate the Trip condition is
“Alarm”
AHU-XX-XX_Sts = “OFF”
AHU-XX-XX_SmkAlm = “ALARM”
12. Simulate the Smoke alarm
condition is “Alarm”
AHU-XX-XX_Sts = “OFF”
AHU-XX-XX_PreFilAlm = “NORMAL”
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
AHU-XX-XX_PreFilAlm = “ALARM”
Simulate the Pre-filter and
14.
Second filter alarm condition to AHU-XX-XX_SecFilAlm = “ALARM”
“Alarm”
AHU-XX-XX_TertiaFilAlm = “ALARM”
3.
Monitor the Mode to “Local” UV-XX-XX_Mode = “LOCAL”
4.
Switch the Mode to “BMS” UV-XX-XX_Mode = “BMS”
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
1. Check the Chilled Water Supply Chilled Water Supply Temp Sensor
Temp Sensor. readings: ______ ºC
2. Check the Chilled Water Return Chilled Water Return Temp Sensor
Temp Sensor. readings ______ ºC
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY
Reading
kW
Volt
Amp
PwFtr
NAME: NAME:
DATE: DATE:
DATE: DATE: