DX-AHU Test Form

SOFTWARE FUNCTIONAL TEST FORM

Form No: ECC-NSCKWE-BMS-


Project: PROJECT THE ECC & NDCS @ SGH TESTFROM-0001

Equipment ID: AHU-XX-XX Date: Revision: 0

Process Description: Testing and Commissioning of AHU-XX-XX

Area/Location: Panel ID: DDC-XX-XX

EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

TEST – 1 AHU Status Monitoring Points AHU

1. Monitor the Incoming Power


AHU-XX-XX_IncPwrSts= “NORMAL”
Status is “Normal”

2. Switch off the Incoming Power


AHU-XX-XX_IncPwrSts= “ALARM”
Status is “Alarm”

3.
Monitor the Mode to “Local” AHU-XX-XX_Mode = “LOCAL”

4.
Switch the Mode to “BMS” AHU-XX-XX_Mode = “BMS”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Send command to “Start”


5.
AHU-XX-XX_Start = “START”
When Time Program to
“Occupied.”

6.
Monitor the Status is “ON” AHU-XX-XX_Sts = “ON

Send command to “Stop”


7.
AHU-XX-XX_SS = “STOP”
When Time Program to
“Unoccupied”

8.
Monitor the Status is “OFF” AHU-XX-XX_Sts = “OFF”

9. Check the Trip condition is


AHU-XX-XX_Trip = “NORMAL”
“Normal”

AHU-XX-XX_Trip = “Alarm”
10. Simulate the Trip condition is
“Alarm”
AHU-XX-XX_Sts = “OFF”

11. Check the Smoke alarm


AHU-XX-XX_SmkAlm = “NORMAL”
condition is “Normal”

AHU-XX-XX_SmkAlm = “ALARM”
12. Simulate the Smoke alarm
condition is “Alarm”
AHU-XX-XX_Sts = “OFF”

AHU-XX-XX_PreFilAlm = “NORMAL”

Check the Pre-filter, second


13. AHU-XX-XX_SecFilAlm = “NORMAL”
filter and Tertiary filter alarm
condition is “Normal”
AHU-XX-XX_TertiaFilAlm =
“NORMAL”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

AHU-XX-XX_PreFilAlm = “ALARM”
Simulate the Pre-filter and
14.
Second filter alarm condition to AHU-XX-XX_SecFilAlm = “ALARM”
“Alarm”
AHU-XX-XX_TertiaFilAlm = “ALARM”

TEST – 2 UV Status Monitoring Points LMCP-UVC

1. Monitor the Incoming Power


UV-XX-XX_IncPwrSts= “NORMAL”
Status is “Normal”

2. Switch off the Incoming Power


UV-XX-XX_IncPwrSts= “ALARM”
Status is “Alarm”

3.
Monitor the Mode to “Local” UV-XX-XX_Mode = “LOCAL”

4.
Switch the Mode to “BMS” UV-XX-XX_Mode = “BMS”

5. Monitor the LMCP Status is


UV-XX-XX_LMCPSts = “ON”
“ON”

6. Monitor the LMCP Status is


UV-XX-XX_LMCPSts = “OFF”
“OFF”

7. Monitor the Common Alarm is


UV-XX-XX_CmnAlm = “NORMAL”
“Normal”

8. Simulate the Common Alarm is


UV-XX-XX_CmnAlm = “ALARM”
“ALARM”

9. Monitor the LMCP Status is


UV-XX-XX_LMCPSts = “ON”
“ON”

10. Monitor the LMCP Status is


UV-XX-XX_LMCPSts = “OFF”
“OFF”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

11. Monitor the Lights Status is


UV-XX-XX_LightSts = “ON”
“ON”

12. Monitor the Lights Status is


UV-XX-XX_LightSts = “OFF”
“OFF”

TEST – 3 Analog input Monitoring Points

1. Check the Chilled Water Supply Chilled Water Supply Temp Sensor
Temp Sensor. readings: ______ ºC

2. Check the Chilled Water Return Chilled Water Return Temp Sensor
Temp Sensor. readings ______ ºC

Chilled Water Flow Rate Sensor


readings
3. Check the Chilled Water Flow
Rate Sensor.
AHU-XX-XX _ChwFlw = ________
L/s

Supply air temp sensor readings


4. Check the Supply air
temperature sensor. AHU-XX-XX _SaT = ____________
ºC

Return air temp sensor readings.


5. Check the Return temperature
sensor. AHU-XX-XX _RaT = ____________
ºC

Fresh air temp sensor readings


6. Check the Fresh air
temperature sensor. AHU-XX-XX _FaT = ____________
ºC

Room high level alarm temp sensor


readings
7. Check the Room high level
alarm temperature sensor.
AHU-XX-XX _FaT = ____________
ºC
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Air flow switch sensor readings


8. Check the Air flow switch
sensor. AHU-XX-XX _Airflw = ____________
cmh

Duct Air Humidity readings


9. Check the Duct Air Humidity
sensor. AHU-XX-XX _Humidity =
____________ %

Room Humidity readings


10. Check the Room Humidity
sensor AHU-XX-XX _RmHumidity = ______
%

Verification of Valve control


TEST – 4 selection under Off coil AHU-XX-XX _Offcoil =______ ºC
Temperature mode.

Simulate Chilled Water Valve


1. Control selection software AHU-XX-XX_TempCtrl =
switch in to “Offcoil OFFTempMode
Temperature Control” position

Valve Command to modulate to open


position:
Adjust temperature set point
2.
value below the Offcoil
AHU-XX-XX _CVlvCtrl =______%
Temperature reading.

AHU-XX-XX _CVlvFdb =______%

Valve Command to modulate to close


position:
Adjust temperature set point
3.
value above the Offcoil
AHU-XX-XX _CVlvCtrl =______%
Temperature reading.

AHU-XX-XX _CVlvFdb =______%

Verification of Valve control


AHU-XX-XX _SupAirTemp =______
TEST – 5 selection under Supply Air
ºC
Temperature mode.
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Simulate Chilled Water Valve


1. Control selection software AHU-XX-XX_TempCtrl =
switch in to “Supply Air SuppAirTempMode
Temperature Control” position

Valve Command to modulate to open


position:

Adjust temperature set point


2. AHU-XX-XX _CVlvCtrl =______%
value below the Supply Air
Temperature reading.
AHU-XX-XX _CVlvFdb =______%

Valve Command to modulate to close


position:

Adjust temperature set point


3. AHU-XX-XX _CVlvCtrl =______%
value above the Supply Air
Temperature reading.
AHU-XX-XX _CVlvFdb =______%

Verification of Static pressure


TEST-6 AHU-XX-XX _StaPrs =______ Pa
VSD control

VSD Command to modulate to ramp


down the speed:

Adjust the static pressure set


AHU-XX-XX _VSDCtrl =______%
1. point value below the static
pressure reading
AHU-XX-XX _VSDFdb =______%

VSD Command to modulate to ramp


up the speed:

Adjust the static pressure set


AHU-XX-XX _VSDCtrl =______%
2. point value above the static
pressure reading
AHU-XX-XX _VSDFdb =______%
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Verification of Fresh Air Damper


TEST-7 AHU-XX-XX _CO2 =______ ppm
control

Fresh air damper control modulates


to open position.
Adjust CO2 set point value
1.
below the Return air CO2
AHU-XX-XX _FaDmpCtrl =______%
reading.

AHU-XX-XX _FaDmpFdb =______%

Fresh air damper control modulates


to close position.
Adjust CO2 set point value
2.
above the Return Air CO2
AHU-XX-XX _FaDmpCtrl =______%
reading.

AHU-XX-XX _FaDmpFdb =______%

TEST – 8 Monitoring BTU meter

BMS Reading Site Reading


Ensure the BTU consumption
1. reading from site tally with BMS
reading.
kWh

BMS Reading Site Reading


Ensure the BTU reading from
2.
site tally with BMS reading.
kWh

EST – 9 Monitoring Power meter

BMS Site Reading


Ensure the power consumption Reading
1 reading from site tally with BMS
reading.
kWh

2 Ensure the power reading from BMS Site Reading


site tally with BMS reading.
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Reading

kW

BMS Site Reading


Reading
Ensure the power reading from
3
site tally with BMS reading.

Volt

BMS Site Reading


Reading
Ensure the power reading from
4
site tally with BMS reading.

Amp

BMS Site Reading


Reading
Ensure the power reading from
5
site tally with BMS reading.

PwFtr

Tested By: Acknowledged


Honeywell Pte Ltd
By: Kilowatts

NAME: NAME:

DATE: DATE:

Submitted and Penta-Ocean Construction Witnessed and


RE/RTO
Checked By: Co,Lto. Checked BY:
NAME: NAME:

DATE: DATE: