PROTEAM EUROPA - Heat & Chill Pump Capacity Calculations

Project : Plot no. 345-438 at Burj Khalifa Dist. Contractor: ANC Contracting

Pool dimensions Ambient conditions: summer winter


L= length 0.00 [m] T1= desired pool temperature 28 [°C] 30 [°C]
W= width 0.00 [m] T2= initial water temperature 38 [°C] 12 [°C]
Ds= shallow-end depth 0.00 [m] T3= max/min aver. amb. temp. 44 [°C] 16 [°C]
Dd= deep-end depth 0.00 [m] ΔT1= daily pool temp raise/drop [K] [K]
AD= average depth 0.00 [m] ΔT2= dif between |T1-T2| 10 [K] 18 [K]
A= Area of pool 132.00 [m²] ΔT3= dif between |T1-T3| 16 [K] 14 [K]
V= Volume of pool 175.61 [m³]
Wind velocity Client specified requirements:
w= 5~8km/h multip. factor 1 θ1= 72 [h] Initial heating-up/cooling-down period
w= 8~16km/h multip. factor 1.25 θ2= 14 [h] Daily running hours (12~max.16h)
w= ≥ 16km/h multip. factor 2
Heating & cooling capacity requirements
Cooling Capacity : SUMMER Heating Capacity : WINTER Heat pump model selected
Initial cool down Initial heating up Code: 00500900

q1= 28.30 kW q1= 50.95 kW Heating: 90 KW


Daily heat gains ( from amb. Air & radiant energy) Daily heat loss ( from the surface) Cooling: 70 KW

q2= 6.34 kW q2= 36.96 kW Total No of Units: 1 Nos


I= 15.28 kW/m²

Total Cooling Loads Total Heat Loads


QCooling = 49.92 kW QHeating = 87.91 kW

q1= V*ρ*ΔT1/860*θ or q2=U*A*ΔT3 /2*


q1=( ρ*cp*V*ΔT2)/3600*θ q2= heat loss/gain from pool surface [kW]
q1 = Pool heat up/cool down rate [kW] U= surface heat transfer coefficient
ρ= density of water @ 998kg/m³ Uheatihg @ 0.04 [kW/m²]
cp= specific heat of water @ 4.18 [kJ/kgK] Ucooling @ 0.006 [kW/m²]
V= pool volume [m³] A= pool surface area [m²]
ΔT1= daily pool temperature drop / raise [K] ΔT3= pool temperature-ambient temperature [K]
*
ΔT2= desired temp. of water - initial temp. of pool [K] = As q2 is calculated for peak temperatures during
θ= pool heat up time [h] the respective seasons, the surface loss is considered
as 1/2 on daily basis and the Total heat losses as the
I= ((E*A)/θ2 )*0.25 (Applicable for Heat & Chill Pumps and Chillers) sum of The initial heat / cooling value & daily energy
I= Radiant energy loss. ( refer ASHRAE applications chapter 48.19)
E=6.484 kW/m²
E= Solar daily heat gain on the horizontal surface (ASHRAE Fundamentals Chapter 26.30)
24° North altitude, month of August (Consider 6 hrs of sunny days on an average)