Professional Documents
Culture Documents
Questions For Electrician
Questions For Electrician
Questions For Electrician
Bridge Megger is used to measure the lowest value of resistances accurately and it
is used to measure the motor winding resistance and transformer winding
resistance during preventive maintenance. The winding resistance of the three
windings should be equal.
A bridge Megger can be used for resistance measurement and fault location It is
so known because it measures high (mega-ohm) resistances, and uses a bridge
circuit, which is suited to this type of measurement.
VCB can make and break in fault condition, contactor cannot. Hence fuses are used
Questions for Electrician
The Tong Tester is called in other words as clip on meter. In this we can measure
the current flowing in each phase with out breaking the circuit for any unbalance,
if is noticed.
What is BASEEFA?
What are Fire Alarm Systems? How can detect the fire
Fire Triangle
For the fire above figures illustrates that for avoiding the fire generally two things
cannot be controlled in the Petrochemical industry i.e Oxygen and Fuel. Only
thing we can control is ignition part of it by keeping the environmental and
equipment in safe condition.
Detection of Fire:-
Smoke detector
Heat detector
Questions for Electrician
Gas detector
UV detector 3
Contain of electrical fire through fire extinguishers like BCF cylinders and Halon
Gas.
CABLES
a) Grouping factor:-
Generally cables laid in air and ground. When number of cables
laid for a plant then it is laid in a trench which will be grouped or laid one after one
which is called Grouping of cables. Grouping factor means since the cables are
arranged in a row, their current carrying capacity will be reduced which is given
below:
b) Derating factor:-
2.5 mmsquare
3. MICC cable is used for what purpose? What material used for this cable?
PILC:- Paper Insulated Lead Covered cable. It is used for chemical plant and refinery.
Lead cover is used to avoid chemical corrosion of cable
Cable glands are used to give mechanical protection of cable against damages of
cables during entering in MCC or junction box. It also gives earth continuity of
cable armour and equipment body.
Questions for Electrician
7. What is the type of armor you have in single core cable? Why?
Impregnated paper insulation over conductor is hygroscopic and will absorb moisture
if exposed.
10. What are the factors considered while sizing the cable?
Voltage drop
Load current
Ground factors / Grouping of cables
S.C.Current.
11. What cable do you recommend for hazardous area? What is the advantage of
lead cover for the cable?
Polarization index gives the true value of insulation of electrical equipment under
tish of 2.5/5 KV megger used to test a equipment. IR value taken after 15 seconds
and the 60 seconds gives the true value.
11
MOTORS
100%
3
4 What is the difference between VCB and motor starter combination?
Questions for Electrician
VCB can make and break in fault condition, contactor cannot. Hence fuses are used
Faulty bearing
Unbalance on rotor
Mis alignment
Faulty Foundation
Rotor bars open
6 What are the units of measurement for vibration and spike energy?
Plastic gauge or lead gauge wire to placed between the shaft and bearing and bolt
tightened to normal and measure flattened thickness of the gauge.
Frequency F= PN/120
No revolving field.
12 What is thrust bearing, where generally it is used? Where sleeve bearings used?
Questions for Electrician
Thrust Bearing is used for vertical plange mounted motor sin drive end side
Sleeve Bearing is used for HT motors in DE and NDE side.
13 YPM of motor
13
15 What is slip ring induction motor, how to take connection from rotor?
To get high starting Toque, we include external resistance to the Rotor winding.
After motor attain full speed Rotor winding one short circuited.
By using Slipring, Carbon brushes connections are taken from Rotor winding.
For selecting the cables, manufactures gives the voltage drop/A/Mtr. It should be
selected according to the size and the necessity of power required. The calculation
given in for voltage of cables is for the reference and theory point of it.
Questions for Electrician
17 Draw the power and control circuit for STAR-DELTA starter connected with 3
phase induction motor? And explain brief?
In start position the stator windings are connected in star. Then voltage on each
phase winding will be equal to line voltage i.e. 58% of the line voltage. Due to
this reduced voltage the starting current will also reduce 1/3 times the current
which would have been taken while starting the motor direct across the line in
Delta.
When the motor gains the speed the starter is quickly changed to run position.
Thus connecting the stator winding in Delta.
Figure:
14
18 Draw and explain these below motor? Also explain which type safety of hand
tools will be use when working with these motors?
a) A/C single phase motor. (b) Permanent capacitor motor. (c) Universal motor.
Single phase's induction motors are not self stating. The single winding of
single phase motor will not produce a rotating filed by itself and some
arrangement is required to turn the alternating field which is improved into
rotating field. By providing a second winding (Auxiliary winding) on the
stator and to alter the phase of the current in the second winding. Thus making
Questions for Electrician
Figure
Figure:-
15
c) Universal motor
Figure:-
Mostly all hand tools are high speed motors & Universal motors.
Earthing the machine is more important and the plug and sockets used
should have sufficient current rating. The flexible cable used for
extension should not be more than 15mts. All equipments should have
double insulated winding. The socket supply source should have a
ELCB (Earth Leakage Circuit Breaker) 0.03A protection.
16
20 Draw the DOL starter power and control circuit for L.T motor and explain?
Questions for Electrician
17
22 What are the causes for motor is over loaded?
Questions for Electrician
Over load ; b) Short circuit for motor winding ; c) Single phasing ; d) Loose
connection of power cable ; e) Bearing problem.
In single phasing if one fuse blown out the motor will run in the same condition,
Motor will take start.
Single phasing preventer is relay which is used to prevent the equipment from single
phasing. If any fuse blown the motor will take higher current. In that case the
humming sound will come.
a) Ball Bearing
b) Roller Bearing
c) Bush Bearing
d) Taper Roller Bearing
e) Sleeve Bearing
f) Thrust Bearing
Questions for Electrician
18
H.T MOTORS
Motors working with voltage 3.3 KV and above are HT motors. This motor
normally used for higher loads as the operating current can be reduced. Normally
these motors are star connected. These motors are having some special cooling
arrangements like forced air cooling. Condenser type cooling in which water is
circulated to cool the temperature inside. Instead of a ball bearing, sleeve bearings
are also used. For cooling the bearing, separate oil is used.
Earth fault
Set normally at 20% the rated operates when fault occurs between phase and
earth.
Motor is provided with the differential relay protection connected between Star side CTs
and phase side CTs as shown.
Figure
Questions for Electrician
19
VIBRATION
Vibration can be measured in terms of how fast the part moves. This is called the
peak velocity and is measured in inches/secs or millimeter/secs. Velocity is a
function of both displacement and frequency; it provides an added sensitivity to
high frequency vibrations.
Vibrations can be measured in terms of how far the part moves back and forth.
This is called the peak to peak displacement measured in mils. 1mil= 25.4
microns.
BEARINGS (TYPES)
The bearings used in electrical machineries are Ball bearings, Roller bearings,
Tapered roller bearings, Thrust bearings, Sleeve bearings, Needle bearings etc.
Generally on load side of the machine Roller bearings are used .
D.E - Drive end
N.D.E - Non drive end
Remove motor pulley with 3 leg puller if the motor is small and medium size. For
large pulley Hydraulic puller may be used
Remove fan cover and fan
Questions for Electrician
Remove outer bearing cover on both ends and remove end shields with markings
Take out the rotor from stator
Now the motor is dismantled totally while assembling reverse the above
procedure.
20
PROTECTION
Measuring CT
Ratio error is less
Saturates at almost 150% of rated current
Protection CT
Ratio error –more
Saturates at many times the rated current
With a connected Burden of 15 VA; it will have a ratio error of 5% or less for
values of primary current up to 10 times rated current.
This relay protects only the zone connected in between the neutral CT and
residually connected CT in the phase side i.e.,., it is protecting star winding of
transformer. When any unbalance or earth fault occurs after the phase CT there
will be unbalanced current in neutral CT as well as residually connected phase CT
and both currents nullified at point '0' so there wont be and current follow in the
relay and the relay wont operate.
When fault occurs in the winding there will be a current flow in the neutral CT
only. The current will operate the 87TG relay.
Figure
Questions for Electrician
The percentage differential relay employs two restrained coils and an operating
coil per phase. The contact closing torque produced by the operating coil is
opposed by the restrained coil torque. Therefore during through fault conditions
21
The setting of the relay is increased and relay operation due to spill current is
prevented. During internal faults torque produced by the restrained coil is
ineffective and the relay closed its contacts when setting current flows through the
operating coil.
The spill current level for the relay to just operate expressed as percentage of the
through fault current causing it, is defined as the % bias of the relay.
For the star winding three line current transformers are balanced against current
transformer in the reatral connection. An external fault on star side will result
incurrent flowing in the line CT of affected phase and a balancing current in
neutral CT. the resultant current in the relay is therefore zero. Hence relay will not
operate during an internal fault the neutral CT only carries current and results in
operation of the relay.
6 Will the restricted earth faulty relay respond to earth faults on both sides of
transformer why?
7 What precautions will you take while disconnecting an ammeter from CT why?
It is the relay whose characteristic is such that the time lag is not fixed but
varies inversely as the overload i.e. the longer the O/C the lesser the time lag.
Plug setting for current & time setting has to be done.
Advantage of inverse tike characteristic is that equipments can be utilized to
the most advantage so that it can safely take heavy over loads for short periods
and lesser over loads for longer periods.
22
9 What is relay coordination? What factors are considered in relay coordination?
Reverse current protection is used to protect parallel incoming feeders at S/S and
also generators operating in parallel. This safeguards the system against total
interruption of power supply in the event of fault in one of the feeders or one of
the generators.
EXPLIAN BRIEF
The characteristics of the relay should be selected and set to suit the protection
requirement of particular motor as the thermal time constant for the motor can
vary wildly(15 minutes to 1 hour) curve A indicates characteristic of motor
heating to reach maximum permissible temperature in 15 minutes for moderate
overload ( 1.3 times full load currents). The relay will trip according to
characteristics B for overload of 200% the relay will trip in less than 4 minutes.
Motor can with stand 200% overload for 4 minutes.
There are installed in the units near each motor for starting and stopping. The
control supply for the stations is 110v D.C leading from the respective switch
gears or 230V A.C
MEGGER VALUE
The insulation resistance value of the winding of the motor shall be checked
periodically during Preventive maintenance
For 3.3 KV motor the IR value shall be checked with 1KV megger
For 11 KV motor the IR value shall be checked with 5 KV megger
WINDING RESISTANCE
The winding resistance of the motor shall be checked during preventive
maintenance with the bridge. The winding resistance of the three windings should
be equal. 23
LOCKED ROTOR CURRENT
Due to mechanical overload in motor locked rotor can sometimes happen and
during this time the motor will draw the maximum current equal to the starting
current. This is called the locked rotor current.
STARTING TIME
The time taken for a motor from the starting to attain its full speed is called the
starting time. It will be generally 4 to 5 seconds for small and medium range
motors and 8 to 10 seconds for large motors.
Under voltage conditions in a motor greatly affect its performance. During this
condition the motor speed reduces it will draw more current and this will cause
rise in temperature of windings. For protecting the motor from this condition.
Under voltage release is provided.
POLARISATION INDEX
Polarization index gives the true value of insulation of electrical equipment under
tish of 2.5/5 KV megger used to test an equipment. IR value taken after 15
seconds and the 60 seconds gives the true value.
R60
R15 X IR (PI) should be 1.1 or greater
Questions for Electrician
EARTHING
GRID RESISTANCE
Grid resistance means in a industry or building the no. of earth pits joined parallel
together to get a minimum earth resistance value and the value should be less than
1.0 ohms acceptable in the industry.
24
PIT RESISTANCE
Individual pit resistance can vary according to the solid resistance and the value
can be 5 ohms or more than that. But to get a minimum value all the pits should
be connected in parallel as grid.
EARTH PITS
Earth pits are generally used by using charcoal, salt and G.I pipe of 3 mtrs in
length and 40mm diameter.
Another type of earth pits is plate earth electrode and mesh type electrode with
copper or GI strip brought out.
Another type in Gulf generally used are the solid rod of copper driven straightway
in to the earth to get minimum value by driving to a depth of max. 6 mtrs.
EARTH MEGGER
For measuring the earth resistance earth megger is used, and the diagram given
below how to measure the earth resistance.
Generally earth resistance of the total grid should be less than 1.0 ohms which is
acceptable for safe operation in industries.
ELCB
Figure ;-
25
COORDINATION OF RELAY
If any fault occurs in motor the nearest relay has trip D breaker itself so that it
won't affect the other system. Similarly if any fault occurs after A breaker the
nearest is A breakers relay. Sp A should trip and other system not affected.
Normally the operating and tripping of breaker time will be around 350 (Msec)
milliseconds.
If after A breaker fault occurs A will trip at 350 msec if it fails B will trip at 700
msec. If B also fails C will trip at 1 sec. This is called the co-ordination of Relays
This relay operates when under voltage occurs in a connected system, nor5mally
this relay setting will be 80% of the applied voltage. This relay having two types
instantaneous and IDMT (Inverse Definite Minimum Time)
ILDMT relays are all disc type and the setting can be done through plug setting
arrangement.
FREEQUENCY
Questions for Electrician
In AC the voltage which completes one cycle of Sine wave form is called
frequency and the unit is HERTZ. Hz.
Normally supply source will be 50hz.
POWER FACTOR
When AC voltage used to an inductive load. The current tags the voltage by an
angle Cosine of that angle will give pf.
P.F = cos0
Other ways of calculating P.F = KW/KVA=R/Z= Resistance/Impedance
26
ABOUT TRANSFORMER EXPLAIN
The transformer windings are placed in oil for cooling as well as for insulation.
Oil samples to be collected and tested for breakdown voltage as per the
recommendation of the manufacture. Generally the transformer oil will be tested
once in three years for the BDV. One oil sample collected will be placed in a test
kit and tested. It should withstand 30KV for one minute. The sphere gap will be
kept at 2.5mm
To adjust the operating voltage occasionally off load and on load tap chargers are
used. Off load tap changer can be operated only when the transformer is isolated
from service, the on load tap changer can be operated even in short times or at
peak load to obtain the desired output voltage without switching off the
transformer from service.
The primary is connected in Delta and secondary in Star. The star point is
connected to neutral. There is phase displacement of plus 30 between the primary
and secondary. There is a phase shift of 30 forward. Hence the number 11 refers
to hour 11'0' clock.
Figures:-
27
ONAN
Oil Natural. Air Natural cooling:- The oil converts the heat from core winding to
the tank and equalizes temperature on natural ventilation. Dissipation of heat is
assisted by constructi0on of tank with corrugated surface or by fitting cooling
Questions for Electrician
tube to it. This type of transformers most common and can be used in output up to
3000 KVA.
ONAF
Oil Natural. Air Forced Cooling:- in this type of cooling the winding is cooled by
air with alternative additional forced air cooling by running the fan fixed at the
radiator tubes.
4. PERCENTAGE IMPEDEMCE
6.5% which means the percentage of normal voltage required on primary to cause
full load current flow through secondary bei9ng shorted. It refers to the short
circuit current. A short circuit on the secondary with full primary voltage the
current will be 100/6.5 times the full load current. Hence for an example the
percentage impedance of a desalted transformer will be 100% so that even at
shorted H.T terminals ( because of water high level) the primary current will not
go beyond the full load current and continue to work.
The power transformer is provided with dial thermometer for oil temperature
range 0-100degress C. alarm contact set at 84.5c on actuation, flag relay falls and
initiate Minor trouble winding temperature indicator facilities monitoring and
indicating transformer hot spot temperature which initiates alarm and trip circuits.
6. PROTECTIONS OF TRANSFORMER
28
Differential relay
Questions for Electrician
This relay detects the internal defects by comparing the input current and the
output current of the Transformer. If it functions combined with other protection
devices. It is indicative, in almost all cases of an internal fault. Note that this relay
sometimes functions by the exciting current when the Transformer is made line.
And this is of course not attributed to internal defects.
TRANSFORMERS
Transformer is a static device. Which converts high voltage to low voltage and
low voltage to high voltage? But temperatures kept constant (Frequency)
Transformation ratio (K) = V1 = N1 = I2
o V2 N2 I1
It is the gas and oil operated relay. It has two circuits, one is trip and second is
alarm. Any minor fault develops that time the evaporated gas will actuate the
alarm circuit, otherwise any major fault rush of oil will actuate the Trip Circuit.
Bucholz relay
Overheated relay
Earth fault relay
Temperature sensor
It is a small container, contains silicagel and oil. It absorbs the moisture from, the
atmospheric air and allow the fresh air to the conservator
CT is a Current Transformer which step down the current. It is used for current
measurement and protection.
6 Y.P.M of transformer..?
Fresh - Blue
Used - Pink
High dielectric strength 30 kv with 2.5 mm gap between spheres, moisture content
low (2 to 3 mgm JOH/g0). Acidity low, flash pint & pour point, viscosity.
Two transformers feeding a system with bus coupler closed and opened. What are the
advantages and disadvantages?
Bus closed :
Bus open :
31
13 Which of loss is kept to the minimum in (a) distribution transformer, (b) power
transformer? Why?
The management inrush current of a transformer is in the tune of 16-20 times its
rated current.
32
H V CIRCUIT BREAKERS
Rated voltage
Rated insulation level
Questions for Electrician
The rated short circuit breaking current of a circuit breaker is the highest value of
short circuit current which a circuit breaker is capable of breaking under specified
condition of transient recovery voltage and power frequency voltage. Express in
KA, RMS at contact separation.
It is the R.M.S value of current that the circuit breaker can carry in fully closed
position during a specified time under prescribed conditions of use and behavior.
Expressed as KA for period of 1 second or 3 seconds.
5 What are the techniques employed to extinguish the arc in AC circuit breaker?
Vacuum Gauge
Questions for Electrician
34
11 How do you carry out the maintenance of A.C.B?
35
LAMPS
INCANDESCENT LAMP
The lamps consist of an evacuated glass bulb or gas filled having fine metallic
wire within it. The filament material normally used is tungsten. Tantrum & carbon
also used for filament. The filament should have the following properties.
Melting point should be high.
Vapour pressure and temp coefficient should be low
Material should be ductile and mechanically strong enough to bear vibration
during use.
Tungsten filament lamps have an average life of 1000 hours under normal
condition.
This type of lamp is of low luminously so the length of this lamp is large. To get
the required length it is made in the form of a U tube. Two oxide coated
electrodes are sealed in to the ends. The tube contains a little sodium and neon
gas. The U tube is enclosed in a double walled vacuum flask to keep the
temperature with in working range. Before the lamp starts working sodium is in
the form of a solid deposited on the side of tube walls. In the beginning it operates
as a low pressure neon lamp with pink colour. The lamp gets warm, sodium is
vaporized and it radiates yellow light and after about 10-15 minutes the lamp
starts giving full light.
It consists of a glass tube of borosilicate which is quite hard. At the two ends in
the tube are provided with specially coated electrodes. Near the upper electrode is
another auxiliary starting electrode which is connected to the bottom electrode
through a high resistance. The tube is sealed with an inside pressure of 1.5
atmosphere. This tube is further evolved by another tube the advantage of which
is that the heat of inner tube may not be dissipated outside.
The lamp has screwed cap and is connected to the main through choke. To
improve the P.F a condenser connected across the mains.
Questions for Electrician
The inner in addition to the mercury, also contains small quantity of argon gas.
Since at the time of starting the tube is cold and the mercury is in the condensed
form. When the tube is switched on, tube start is glowing between main and
auxiliary electrodes and after about five minutes the lamp starts giving the full
output.
36
FLUORCENT TUBES
Due to low pressure the lamp is in the form of long tube coated inside with
phosphor. The tube contains a small amount of mercury and a small quantity of
argon gas. When temperature increases the mercury changes into vapour form
which it takes over the conduction of current. At each end of the tube tungsten
electrode coated with an electron omitting material.
Figure:-
At the time of switching ON the starter switch is in closed position. Current flows
through the choke and starters. The starter switch is open due to heating of its
bimetallic strip. The energy stored in the choke is suddenly released in the form of
a voltage surge which causes starting of discharge through the tube between
electrodes. This discharge is self sustaining and tube continues to glow. The
colour of the fluorescent lamp depends on the coating used.
HALOGEN LAMP
This type of lamp will be having tungsten filament connected from one end to
another end of a lengthy thin glass tube. This glass tube is filled with Halogen
Gas.
Halogen is a family of gases. The gas the high temperature and the shape of glass
tube do not allow the evaporated gases of the filament to accumulate on the side
of the glass. Hence the life of this lamp is high.
37
If the Batteries are connected in Series the voltage will be increase and the
Batteries are connected in Parallel the Current will be increase
One by pass jumper is to be provided across the battery and replace it. After
replacing the by pass jumper must be removed.
38
DISTRIBUTION
In a ring main system each load current is connected to the next in the form of
closed ring around the system.
The ring main contains advantages of duplicate mains with less cost.
Quick isolation and more flexibility.
3 In a 11 KV bus if you add a transformer 1000 KVA or add 1000 KVA motor in
which case fault level will increase in 11 kv bus and why?
1000 KVA motor because if feeds fault current to 11KV bus during fault
conditions due to generator action.
39
O/H TRANSMISSION
5KW/KM
Lightning arrestors employ some form of non leaner type of resistance like thyrite
or matrosil whose resistance decreases rapidly with increases of applied voltage.
But as soon as energy has been dissipated resistance is restored to a high value
which suppresses the arc across the gap effectively when line voltage returns to
normal.
4 What are the points to se checked when carrying out inspection of O/H lines?
Questions for Electrician
SAFETY
What precautions should take while working with electrical supply?
How many types work permits explain?
What precautions should take while working with open bus bars?
UPS have Converter, Inverter, AVR Battery Bank, Static switch and Bypass
Switch.
The converter is feeding supply to the inverter.
The battery bank connected in between converter and inverter.
The static switch have supply on both end i.e Converter supply and AVR supply
(Static switch is nothing – the two SCR is connected in opposite direction)
The inverter is always taking the load, the converter fails to feed supply to the
inverter, it will work with the help of battery bank.
If the inverter is fails to take the load, the AVR supply will take the load without
power interruption through the static switch.
During the maintenance of UPS, changeover the load to standby supply by using
Bypass switch.
Figure:-
Questions for Electrician
From left to right: Pot (this one has an earth tail), pot seal, gland, potting
compound, joist ripper, pot crimper, stub sleeving, pliers.
The voltmeter is used to measure the voltage in the power system in low voltage
system the voltage is measured directly and in high voltage system through a
potential transformer.
Trace the cable fault through cable fault locator and cable route through rout
locator
If the cable resistance is high use the burning kit.
Voltage drop
Load current
Ground factors / Grouping of cables
S.C.Current.
8. What is Ammeter?
Load current is measured through an ammeter only. In A.C lower ranges are
directly can be read through an ammeter kept in series. For larger ranges are the
current transformers are used for measuring the current.
To measure the power consumed by the circuit (any type of feeder) energy meter
is used and the unit is in KWH
Bridge Megger is used to measure the lowest value of resistances accurately and it
is used to measure the motor winding resistance and transformer winding
resistance during preventive maintenance. The winding resistance of the three
windings should be equal.
The Tong Tester is called in other words as clip on meter. In this we can measure
the current flowing in each phase with out breaking the circuit for any unbalance,
if is noticed.
16.What is BASEEFA?
17.What are Fire Alarm Systems? How can detect the fire
Fire Triangle
For the fire above figures illustrates that for avoiding the fire generally two things
cannot be controlled in the Petrochemical industry i.e Oxygen and Fuel. Only
thing we can control is ignition part of it by keeping the environmental and
equipment in safe condition.
Detection of Fire:-
Detection of fires is achieved through the following monitors.
Smoke detector
Heat detector
Gas detector
UV detector 3
Containing of Electrical Fire:-
Contain of electrical fire through fire extinguishers like BCF cylinders and Halon
Gas.
CABLES
a) Grouping factor:-
Generally cables laid in air and ground. When number of cables
laid for a plant then it is laid in a trench which will be grouped or laid one after one
which is called Grouping of cables. Grouping factor means since the cables are
arranged in a row, their current carrying capacity will be reduced which is given
below:
b) Derating factor:-
2.5 mmsquare
14. MICC cable is used for what purpose? What material used for this cable?
PILC:- Paper Insulated Lead Covered cable. It is used for chemical plant and refinery.
Lead cover is used to avoid chemical corrosion of cable
Cable glands are used to give mechanical protection of cable against damages of
cables during entering in MCC or junction box. It also gives earth continuity of
cable armour and equipment body.
17. What is the type of armor you have in single core cable? Why?
Impregnated paper insulation over conductor is hygroscopic and will absorb moisture
if exposed.
Questions for Electrician
20. What cable do you recommend for hazardous area? What is the advantage of
lead cover for the cable?
Polarization index gives the true value of insulation of electrical equipment under
tish of 2.5/5 KV megger used to test a equipment. IR value taken after 15 seconds
and the 60 seconds gives the true value.
MOTORS
100%
3
4 What is the difference between VCB and motor starter combination?
VCB can make and break in fault condition, contactor cannot. Hence fuses are used
Questions for Electrician
Faulty bearing
Unbalance on rotor
Mis alignment
Faulty Foundation
Rotor bars open
6 What are the units of measurement for vibration and spike energy?
Plastic gauge or lead gauge wire to placed between the shaft and bearing and bolt
tightened to normal and measure flattened thickness of the gauge.
Frequency F= PN/120
No revolving field.
12 What is thrust bearing, where generally it is used? Where sleeve bearings used?
Thrust Bearing is used for vertical plange mounted motor sin drive end side
Questions for Electrician
13 YPM of motor
13
15 What is slip ring induction motor, how to take connection from rotor?
To get high starting Toque, we include external resistance to the Rotor winding.
After motor attain full speed Rotor winding one short circuited.
By using Slipring, Carbon brushes connections are taken from Rotor winding.
For selecting the cables, manufactures gives the voltage drop/A/Mtr. It should be
selected according to the size and the necessity of power required. The calculation
given in for voltage of cables is for the reference and theory point of it.
Questions for Electrician
17 Draw the power and control circuit for STAR-DELTA starter connected with 3
phase induction motor? And explain brief?
In start position the stator windings are connected in star. Then voltage on each
phase winding will be equal to line voltage i.e. 58% of the line voltage. Due to
this reduced voltage the starting current will also reduce 1/3 times the current
which would have been taken while starting the motor direct across the line in
Delta.
When the motor gains the speed the starter is quickly changed to run position.
Thus connecting the stator winding in Delta.
Figure:
14
18 Draw and explain these below motor? Also explain which type safety of hand
tools will be use when working with these motors?
a) A/C single phase motor. (b) Permanent capacitor motor. (c) Universal motor.
Single phase's induction motors are not self stating. The single winding of
single phase motor will not produce a rotating filed by itself and some
arrangement is required to turn the alternating field which is improved into
rotating field. By providing a second winding (Auxiliary winding) on the
stator and to alter the phase of the current in the second winding. Thus making
Questions for Electrician
Figure
Figure:-
15
c) Universal motor
Figure:-
Mostly all hand tools are high speed motors & Universal motors.
Earthing the machine is more important and the plug and sockets used
should have sufficient current rating. The flexible cable used for
extension should not be more than 15mts. All equipments should have
double insulated winding. The socket supply source should have a
ELCB (Earth Leakage Circuit Breaker) 0.03A protection.
16
20 Draw the DOL starter power and control circuit for L.T motor and explain?
Questions for Electrician
17
22 What are the causes for motor is over loaded?
Questions for Electrician
Over load ; b) Short circuit for motor winding ; c) Single phasing ; d) Loose
connection of power cable ; e) Bearing problem.
In single phasing if one fuse blown out the motor will run in the same condition,
Motor will take start.
Single phasing preventer is relay which is used to prevent the equipment from single
phasing. If any fuse blown the motor will take higher current. In that case the
humming sound will come.
g) Ball Bearing
h) Roller Bearing
i) Bush Bearing
j) Taper Roller Bearing
k) Sleeve Bearing
l) Thrust Bearing
Questions for Electrician
18
H.T MOTORS
Motors working with voltage 3.3 KV and above are HT motors. This motor
normally used for higher loads as the operating current can be reduced. Normally
these motors are star connected. These motors are having some special cooling
arrangements like forced air cooling. Condenser type cooling in which water is
circulated to cool the temperature inside. Instead of a ball bearing, sleeve bearings
are also used. For cooling the bearing, separate oil is used.
Earth fault
Set normally at 20% the rated operates when fault occurs between phase and
earth.
Motor is provided with the differential relay protection connected between Star side CTs
and phase side CTs as shown.
Figure
Questions for Electrician
19
VIBRATION
Vibration can be measured in terms of how fast the part moves. This is called the
peak velocity and is measured in inches/secs or millimeter/secs. Velocity is a
function of both displacement and frequency; it provides an added sensitivity to
high frequency vibrations.
Vibrations can be measured in terms of how far the part moves back and forth.
This is called the peak to peak displacement measured in mils. 1mil= 25.4
microns.
BEARINGS (TYPES)
The bearings used in electrical machineries are Ball bearings, Roller bearings,
Tapered roller bearings, Thrust bearings, Sleeve bearings, Needle bearings etc.
Generally on load side of the machine Roller bearings are used .
D.E - Drive end
N.D.E - Non drive end
Remove motor pulley with 3 leg puller if the motor is small and medium size. For
large pulley Hydraulic puller may be used
Remove fan cover and fan
Questions for Electrician
Remove outer bearing cover on both ends and remove end shields with markings
Take out the rotor from stator
Now the motor is dismantled totally while assembling reverse the above
procedure.
20
PROTECTION
Measuring CT
Ratio error is less
Saturates at almost 150% of rated current
Protection CT
Ratio error –more
Saturates at many times the rated current
With a connected Burden of 15 VA; it will have a ratio error of 5% or less for
values of primary current up to 10 times rated current.
This relay protects only the zone connected in between the neutral CT and
residually connected CT in the phase side i.e.,., it is protecting star winding of
transformer. When any unbalance or earth fault occurs after the phase CT there
will be unbalanced current in neutral CT as well as residually connected phase CT
and both currents nullified at point '0' so there wont be and current follow in the
relay and the relay wont operate.
When fault occurs in the winding there will be a current flow in the neutral CT
only. The current will operate the 87TG relay.
Figure
Questions for Electrician
The percentage differential relay employs two restrained coils and an operating
coil per phase. The contact closing torque produced by the operating coil is
opposed by the restrained coil torque. Therefore during through fault conditions
21
The setting of the relay is increased and relay operation due to spill current is
prevented. During internal faults torque produced by the restrained coil is
ineffective and the relay closed its contacts when setting current flows through the
operating coil.
The spill current level for the relay to just operate expressed as percentage of the
through fault current causing it, is defined as the % bias of the relay.
For the star winding three line current transformers are balanced against current
transformer in the reatral connection. An external fault on star side will result
incurrent flowing in the line CT of affected phase and a balancing current in
neutral CT. the resultant current in the relay is therefore zero. Hence relay will not
operate during an internal fault the neutral CT only carries current and results in
operation of the relay.
6 Will the restricted earth faulty relay respond to earth faults on both sides of
transformer why?
7 What precautions will you take while disconnecting an ammeter from CT why?
It is the relay whose characteristic is such that the time lag is not fixed but
varies inversely as the overload i.e. the longer the O/C the lesser the time lag.
Plug setting for current & time setting has to be done.
Advantage of inverse tike characteristic is that equipments can be utilized to
the most advantage so that it can safely take heavy over loads for short periods
and lesser over loads for longer periods.
22
9 What is relay coordination? What factors are considered in relay coordination?
Reverse current protection is used to protect parallel incoming feeders at S/S and
also generators operating in parallel. This safeguards the system against total
interruption of power supply in the event of fault in one of the feeders or one of
the generators.
EXPLIAN BRIEF
The characteristics of the relay should be selected and set to suit the protection
requirement of particular motor as the thermal time constant for the motor can
vary wildly(15 minutes to 1 hour) curve A indicates characteristic of motor
heating to reach maximum permissible temperature in 15 minutes for moderate
overload ( 1.3 times full load currents). The relay will trip according to
characteristics B for overload of 200% the relay will trip in less than 4 minutes.
Motor can with stand 200% overload for 4 minutes.
Questions for Electrician
There are installed in the units near each motor for starting and stopping. The
control supply for the stations is 110v D.C leading from the respective switch
gears or 230V A.C
MEGGER VALUE
The insulation resistance value of the winding of the motor shall be checked
periodically during Preventive maintenance
For 3.3 KV motor the IR value shall be checked with 1KV megger
For 11 KV motor the IR value shall be checked with 5 KV megger
WINDING RESISTANCE
The winding resistance of the motor shall be checked during preventive
maintenance with the bridge. The winding resistance of the three windings should
be equal. 23
LOCKED ROTOR CURRENT
Due to mechanical overload in motor locked rotor can sometimes happen and
during this time the motor will draw the maximum current equal to the starting
current. This is called the locked rotor current.
STARTING TIME
The time taken for a motor from the starting to attain its full speed is called the
starting time. It will be generally 4 to 5 seconds for small and medium range
motors and 8 to 10 seconds for large motors.
Under voltage conditions in a motor greatly affect its performance. During this
condition the motor speed reduces it will draw more current and this will cause
rise in temperature of windings. For protecting the motor from this condition.
Under voltage release is provided.
POLARISATION INDEX
Polarization index gives the true value of insulation of electrical equipment under
tish of 2.5/5 KV megger used to test an equipment. IR value taken after 15
seconds and the 60 seconds gives the true value.
R60
Questions for Electrician
EARTHING
GRID RESISTANCE
Grid resistance means in a industry or building the no. of earth pits joined parallel
together to get a minimum earth resistance value and the value should be less than
1.0 ohms acceptable in the industry.
24
PIT RESISTANCE
Individual pit resistance can vary according to the solid resistance and the value
can be 5 ohms or more than that. But to get a minimum value all the pits should
be connected in parallel as grid.
EARTH PITS
Earth pits are generally used by using charcoal, salt and G.I pipe of 3 mtrs in
length and 40mm diameter.
Another type of earth pits is plate earth electrode and mesh type electrode with
copper or GI strip brought out.
Another type in Gulf generally used are the solid rod of copper driven straightway
in to the earth to get minimum value by driving to a depth of max. 6 mtrs.
EARTH MEGGER
For measuring the earth resistance earth megger is used, and the diagram given
below how to measure the earth resistance.
Generally earth resistance of the total grid should be less than 1.0 ohms which is
acceptable for safe operation in industries.
ELCB
Figure ;-
25
COORDINATION OF RELAY
If any fault occurs in motor the nearest relay has trip D breaker itself so that it
won't affect the other system. Similarly if any fault occurs after A breaker the
nearest is A breakers relay. Sp A should trip and other system not affected.
Normally the operating and tripping of breaker time will be around 350 (Msec)
milliseconds.
If after A breaker fault occurs A will trip at 350 msec if it fails B will trip at 700
msec. If B also fails C will trip at 1 sec. This is called the co-ordination of Relays
This relay operates when under voltage occurs in a connected system, nor5mally
this relay setting will be 80% of the applied voltage. This relay having two types
instantaneous and IDMT (Inverse Definite Minimum Time)
ILDMT relays are all disc type and the setting can be done through plug setting
arrangement.
FREEQUENCY
Questions for Electrician
In AC the voltage which completes one cycle of Sine wave form is called
frequency and the unit is HERTZ. Hz.
Normally supply source will be 50hz.
POWER FACTOR
When AC voltage used to an inductive load. The current tags the voltage by an
angle Cosine of that angle will give pf.
P.F = cos0
Other ways of calculating P.F = KW/KVA=R/Z= Resistance/Impedance
26
ABOUT TRANSFORMER EXPLAIN
The transformer windings are placed in oil for cooling as well as for insulation.
Oil samples to be collected and tested for breakdown voltage as per the
recommendation of the manufacture. Generally the transformer oil will be tested
once in three years for the BDV. One oil sample collected will be placed in a test
kit and tested. It should withstand 30KV for one minute. The sphere gap will be
kept at 2.5mm
To adjust the operating voltage occasionally off load and on load tap chargers are
used. Off load tap changer can be operated only when the transformer is isolated
from service, the on load tap changer can be operated even in short times or at
peak load to obtain the desired output voltage without switching off the
transformer from service.
The primary is connected in Delta and secondary in Star. The star point is
connected to neutral. There is phase displacement of plus 30 between the primary
and secondary. There is a phase shift of 30 forward. Hence the number 11 refers
to hour 11'0' clock.
Figures:-
27
ONAN
Oil Natural. Air Natural cooling:- The oil converts the heat from core winding to
the tank and equalizes temperature on natural ventilation. Dissipation of heat is
assisted by constructi0on of tank with corrugated surface or by fitting cooling
tube to it. This type of transformers most common and can be used in output up to
3000 KVA.
ONAF
Oil Natural. Air Forced Cooling:- in this type of cooling the winding is cooled by
air with alternative additional forced air cooling by running the fan fixed at the
radiator tubes.
6.5% which means the percentage of normal voltage required on primary to cause
full load current flow through secondary bei9ng shorted. It refers to the short
circuit current. A short circuit on the secondary with full primary voltage the
current will be 100/6.5 times the full load current. Hence for an example the
percentage impedance of a desalted transformer will be 100% so that even at
shorted H.T terminals ( because of water high level) the primary current will not
go beyond the full load current and continue to work.
The power transformer is provided with dial thermometer for oil temperature
range 0-100degress C. alarm contact set at 84.5c on actuation, flag relay falls and
initiate Minor trouble winding temperature indicator facilities monitoring and
indicating transformer hot spot temperature which initiates alarm and trip circuits.
28
Differential relay
This relay detects the internal defects by comparing the input current and the
output current of the Transformer. If it functions combined with other protection
devices. It is indicative, in almost all cases of an internal fault. Note that this relay
sometimes functions by the exciting current when the Transformer is made line.
And this is of course not attributed to internal defects.
TRANSFORMERS
Transformer is a static device. Which converts high voltage to low voltage and
low voltage to high voltage? But temperatures kept constant (Frequency)
Transformation ratio (K) = V1 = N1 = I2
o V2 N2 I1
It is the gas and oil operated relay. It has two circuits, one is trip and second is
alarm. Any minor fault develops that time the evaporated gas will actuate the
alarm circuit, otherwise any major fault rush of oil will actuate the Trip Circuit.
Bucholz relay
Overheated relay
Earth fault relay
Temperature sensor
It is a small container, contains silicagel and oil. It absorbs the moisture from, the
atmospheric air and allow the fresh air to the conservator
CT is a Current Transformer which step down the current. It is used for current
measurement and protection.
6 Y.P.M of transformer..?
Fresh - Blue
Used - Pink
High dielectric strength 30 kv with 2.5 mm gap between spheres, moisture content
low (2 to 3 mgm JOH/g0). Acidity low, flash pint & pour point, viscosity.
Two transformers feeding a system with bus coupler closed and opened. What are the
advantages and disadvantages?
Bus closed :
Bus open :
31
Questions for Electrician
13 Which of loss is kept to the minimum in (a) distribution transformer, (b) power
transformer? Why?
The management inrush current of a transformer is in the tune of 16-20 times its
rated current.
32
H V CIRCUIT BREAKERS
Rated voltage
Rated insulation level
Rated normal current
Rated frequency
Rated duration of short time current
Rated short circuit breaking current
Rated short circuit making current
Rated peak with stand current
Rated TRV (Transit Recovery Voltage for terminal fault)
The rated short circuit breaking current of a circuit breaker is the highest value of
short circuit current which a circuit breaker is capable of breaking under specified
condition of transient recovery voltage and power frequency voltage. Express in
KA, RMS at contact separation.
It is the R.M.S value of current that the circuit breaker can carry in fully closed
position during a specified time under prescribed conditions of use and behavior.
Expressed as KA for period of 1 second or 3 seconds.
5 What are the techniques employed to extinguish the arc in AC circuit breaker?
Vacuum Gauge
By judging the pulling force of contact by hand or by spring balance
By applying power frequency high voltage test.
34
11 How do you carry out the maintenance of A.C.B?
35
LAMPS
INCANDESCENT LAMP
The lamps consist of an evacuated glass bulb or gas filled having fine metallic
wire within it. The filament material normally used is tungsten. Tantrum & carbon
also used for filament. The filament should have the following properties.
Melting point should be high.
Vapour pressure and temp coefficient should be low
Material should be ductile and mechanically strong enough to bear vibration
during use.
Tungsten filament lamps have an average life of 1000 hours under normal
condition.
This type of lamp is of low luminously so the length of this lamp is large. To get
the required length it is made in the form of a U tube. Two oxide coated
electrodes are sealed in to the ends. The tube contains a little sodium and neon
gas. The U tube is enclosed in a double walled vacuum flask to keep the
temperature with in working range. Before the lamp starts working sodium is in
the form of a solid deposited on the side of tube walls. In the beginning it operates
as a low pressure neon lamp with pink colour. The lamp gets warm, sodium is
vaporized and it radiates yellow light and after about 10-15 minutes the lamp
starts giving full light.
It consists of a glass tube of borosilicate which is quite hard. At the two ends in
the tube are provided with specially coated electrodes. Near the upper electrode is
another auxiliary starting electrode which is connected to the bottom electrode
through a high resistance. The tube is sealed with an inside pressure of 1.5
Questions for Electrician
atmosphere. This tube is further evolved by another tube the advantage of which
is that the heat of inner tube may not be dissipated outside.
The lamp has screwed cap and is connected to the main through choke. To
improve the P.F a condenser connected across the mains.
The inner in addition to the mercury, also contains small quantity of argon gas.
Since at the time of starting the tube is cold and the mercury is in the condensed
form. When the tube is switched on, tube start is glowing between main and
auxiliary electrodes and after about five minutes the lamp starts giving the full
output.
36
FLUORCENT TUBES
Due to low pressure the lamp is in the form of long tube coated inside with
phosphor. The tube contains a small amount of mercury and a small quantity of
argon gas. When temperature increases the mercury changes into vapour form
which it takes over the conduction of current. At each end of the tube tungsten
electrode coated with an electron omitting material.
Figure:-
At the time of switching ON the starter switch is in closed position. Current flows
through the choke and starters. The starter switch is open due to heating of its
bimetallic strip. The energy stored in the choke is suddenly released in the form of
a voltage surge which causes starting of discharge through the tube between
electrodes. This discharge is self sustaining and tube continues to glow. The
colour of the fluorescent lamp depends on the coating used.
HALOGEN LAMP
This type of lamp will be having tungsten filament connected from one end to
another end of a lengthy thin glass tube. This glass tube is filled with Halogen
Gas.
Halogen is a family of gases. The gas the high temperature and the shape of glass
tube do not allow the evaporated gases of the filament to accumulate on the side
of the glass. Hence the life of this lamp is high.
37
If the Batteries are connected in Series the voltage will be increase and the
Batteries are connected in Parallel the Current will be increase
One by pass jumper is to be provided across the battery and replace it. After
replacing the by pass jumper must be removed.
38
DISTRIBUTION
In a ring main system each load current is connected to the next in the form of
closed ring around the system.
The ring main contains advantages of duplicate mains with less cost.
Quick isolation and more flexibility.
3 In a 11 KV bus if you add a transformer 1000 KVA or add 1000 KVA motor in
which case fault level will increase in 11 kv bus and why?
1000 KVA motor because if feeds fault current to 11KV bus during fault
conditions due to generator action.
39
O/H TRANSMISSION
5KW/KM
Lightning arrestors employ some form of non leaner type of resistance like thyrite
or matrosil whose resistance decreases rapidly with increases of applied voltage.
But as soon as energy has been dissipated resistance is restored to a high value
which suppresses the arc across the gap effectively when line voltage returns to
normal.
4 What are the points to se checked when carrying out inspection of O/H lines?
SAFETY
What precautions should take while working with electrical supply?
Questions for Electrician
Motor protection depending on size and voltage level (on photo 3-phase asynchronous
motor 55 kW)
Motor protections vary widely depending on the size of the motor and voltage level
involved, thus only the more common ones are discussed in this technical article.
Protection Index
1. Motor Instantaneous Over-current Protection
3. Thermal OverLoad
Tap settings and time characteristic adjustments can be made to alter the time delay of
the relay. The major benefit of the induction disk timed over current relay is that the
speed of rotation is proportional to the motor current.
Questions for Electrician
Hence major over-current conditions will trip the supply breaker almost instantaneously,
while currents just above rated load will cause operation after several seconds (or
minutes).
Index Top
3. Thermal OverLoad
Another common type of relay used for timed overload protection is a thermal overload
relay. In this type of relay, the motor current or a fraction of the current through a
currenttransformer is connected to an in-line heater. Figure 2 shows a simplified thermal
overload relay. The heater (heated by I2R action) is used to heat a bimetallic strip, which
causes the displacement of a relay contact. A bimetallic strip consists of two different
materials bonded together, each having different thermal expansion properties.
As the materials are heated, one side will lengthen more than the other, causing bending.
Normal operating currents or short duration overload conditions, will not cause the
bimetallic element tobend enough to change the relay contact positions.
Excessive currents will cause increased heating of the bimetallic strip, which will cause relay contacts to
open and/or close, tripping the motor.
The thermal overload relay has an inherent reaction time, since the heater and bimetallic
element take time to heat. Care must be taken to match the current heating
characteristics of the motor or else the motor could be damaged during the locked rotor
starting conditions.
This type of relay can be used for direct protection against excessive motor current
caused by electrical faults and motor overloads. Also, it is often used in combination with
the timed over-current protection.
Thermal overload relays using in-line heaters and bimetallic strips, provide an alarm in
the case of continuous overload. This provides an opportunity for the operator to correct
the problem before it reaches trip level magnitude.
As we have stated, thermal over-load trips can occur during repetitive starts on a motor
or during motor over-loading. Thermal overload trips will seal-in to prevent the motor
contactor from closing. This lock-out will require manual reset before the motor can be
re-started. The operator or attendant will have to physically confirm that the motor has
had sufficient time to cool down and that the cause for the overload has been removed. If
the operator is confident that there is not a permanent fault on the motor the relay can be
reset.
Note however, that if an instantaneous over-current trip has occurred, no attempt at closing the motor
contactor should be made. An instantaneous trip will only occur if there is a fault in the motor or supply
cable and this must be corrected before any attempt to reset the relay.
Index Top
If a ground fault develops, a current imbalance will be present and a current will flow in
the protection circuit, causing it to operate to trip the supply breaker.
Figure 4 shows a similar protection scheme, with each of the windings of the motor
protected individually (this scheme is not normally installed in small motors, but may
appear in the protection of very large motors).
Index Top
starts, due to high currents combined with low cooling air flows (due to the low speed of
the motor, cooling fans are delivering only small amounts of air).
This is also why some larger motors have a limit on the number of attempted motor starts
before a cooling off period is required. However, stall conditions can occur during
normal operation. For example, mechanical faults such as a seized bearing, heavy
loading or some type of foreign object caught in a pump could be possible causes of
motor stalling.
The loss of a single phase while the motor is not rotating or under high load, is another
situation in which a motor may stall.
The typical starting time of a motor is less than ten seconds. As long as this start time is not exceeded, no
damage to a motor will occur due to overheating from the high currents.During operation, a motor could
typically stall for twenty secondsor more without resulting in excessive insulation deterioration.
We use a stalling relay to protect motors during starts, since a standard thermal relay
has too much time delay. A stalling relay will allow the motor to draw normal starting
currents (which are several times normal load current) for a short time, but will trip the
motor for excessive time at high currents.
A stalling relay uses the operating principle of a thermal overload relay, but operates
faster than a standard thermal relay.
excessive heating of the windings and will cause the insulation to be damaged. If the open circuit is present
before the motor start is attempted, it is unlikely that the motor will be able to start rotating.
The phase-unbalance relay used to protect against this scenario is similar in design to
the stall relay, but is set for about 20% of the full load current. A rough representation of
the operation of the relay is included in Figures 6 and 7 for reference only.
If any one of the phases in the motor loses power, the heater will cool down. The
bimetallic strip will turn, causing the unbalance contacts to close and the motor to be
tripped. This relay will also protect against thermal overload, as the heaters cause the
bimetallic strips to close the overload trip contact.
You will also see a compensating bimetal element, which will compensate for ambient
temperature changes, thus preventing unnecessary trips.