To Ksa: Same Sheet

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

N

KINGDOM OF
N SAUDI ARABIA
W E
KAH
MAK

S
W
MAKKAH E SITE LOCATION

KINGDOM OF BAHRAIN

C
SAME GENERAL NOTES
SHEET 56.00m
1. DO NOT SCALE FROM THE DRAWINGS.

6.00M
ROAD BLOCKER
2. ALL DIMENSIONS AND LEVELS ARE IN MILLIMETERS UNLESS
MASTER CONTROL
IN CUSTOM CABIN NOTED OTHERWISE.
3. ALL MEASUREMENTS MUST BE CHECKED AND VERIFIED AT SITE
BY THE CONTRACTOR AND NOTIFICATION TO BE MADE TO THE
CONTROL CABLE IN ENGINEER BEFORE COMMENCEMENT OF THE WORK IN THE
50mmØ uPVC DUCT LAID EVENT OF ANY DISCREPANCIES ARISING FROM THE DRAWINGS.
NEW TRAFFIC LIGHT
UNDER GROUND C 4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER
RELEVANT ARCHITECTURAL, STRUCTURAL, MECHANICAL,
ELECTRICAL AND CIVIL DRAWINGS AND ALL RELEVANT SECTIONS
OF THE SPECIFICATIONS.

3.00m
HYDRAULIC 5. CONTRACTOR SHALL SUBMIT MATERIAL SUBMITTALS (INCLUDING
45ATP ROAD BLOCKERS TO KSA ALL ACCESSORIES) FOR ENGINEER'S REVIEW AND APPROVAL.
6. CONTRACTOR SHALL SUBMIT FULLY-DETAILED COORDINATED
SHOP DRAWINGS FOR ENGINEER'S REVIEW AND APPROVAL,
SECURITY & 1 PRIOR TO PROCEEDING WITH WORKS AT SITE.
SAFETY 7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN OF
BOLLARDS ALL TEMPORARY WORK RELATED TO THE CONSTRUCTION
C 8.
PROCESS.
CONTRACTOR IS REQUIRED TO VISIT THE SITE AND GET
FAMILIARIZED WITH SITE CONDITIONS, PRIOR TO
COMMENCEMENT OF WORKS AT SITE.
ROAD BLOCKER
45ATP CONTROL IN
B
USING : Y:\03 KFCA Projects\02 Projects Section-3\20223078 Hydraulic Road blockers at VIP lane - KSA & BH\03 DesignDrawings\03 DetailedDesign\07 EL\SAUDI SIDE\CAD\20221026_DD VIP LANE_ROAD BLOCKERS_KSA.dwg

CUSTOM CABIN
18.00m TO BAHRAIN
SAME
SHEET
LEGEND:
45ATP

9.00m
SYMBOLS DESCRIPTION
A
SAME C ROAD BLOCKERS CONTROL
SHEET 4.00m

SA-24 ELV CABLE


3.00m FEEDER PILLAR
CONCRETE INSPECTION PIT
COMPLETE WITH ACCESS COVER 50mmØ uPVC DUCT FOR THE POWER
86.00m
GROUND LEVEL
50mmØ uPVC DUCT FOR THE ELV
4C x 25 mm²
/CU
XLPE/SWA/PVC
m² EC C

200MM MIN.
+1X1 6m
S SA-24 DRIVING STUD HYDRAULIC ROAD BLOCKER
CABLE FROM S/
NOTES: NEW TRAFFIC LIGHT
POWER SYSTEM NOTES :
PROTECTIVE CAP FILLED
WITH PETROLEUM JELLY 45ATP ISOLATOR TYPE RATING AS SHOWN
1. CONTRACTOR TO OBTAIN MATERIAL / SHOP DRAWINGS APPROVAL BEFORE PROCEEDING ANY
INSTALLATION / CONSTRUCTION WORK.
2. CONTRACTOR IS FULLY RESPONSIBLE FOR COORDINATION OF WORK WITH OTHER TRADES EARTH PIT WITH 20mm DIA X MIN 3000mm LONG
COPPER EARTHING LIKE MECHANICAL, ARCHITECTURAL, CIVIL ETC., SOLID COPPER ROD FOR BUIDLING & CLEAN
CONDUCTOR 3. POWER CIRCUITS TO BE CONNECTED TO DEDICATED "RCBO" CIRCUIT BREAKERS, COMMON EARTH, NO, OF EARTHS DEPENDS TO ACHIVE
EARTH RESISTANCE LESS TAN ONE OHMS.
EARTH LEAKAGE PROTECTION IS NOT PERMITTED.

1.50
MINIMUM 2 REQUIRE AT EACH LOACTION.
4. WIRING FOR BARRIER CONTROL PANEL, WITH 3cx4.0mm2 XLPE CABLE + 2.5mm2 ECC.(Min.)
5. 2X75 mm DIA DUCTS FOR THE POWER SUPPLY TO BE PROVIDED FROM NEAREST POWER
COPPER BOND ROD
MANHOLE. REV. DATE DESCRIPTION REMARKS
(1.5 METER LONG)
6. EARTH RESISTANCE TO BE ACHIEVED <1.0 OHMS. 01 02 jan. 2023 DIMENSIONS
7. ISOLATOR FOR THE BARRIER TO BE MOUNTED INSIDE THE BARRIER HOUSING ITSELF,
EARTH ROD COUPLING 8. IN CASE THE SPACE DOES NOT PERMITS IT CAN BE MOUTED OUTSIDE.
9. ALL THE DEVICES MOUNTED OUTSIDE SHOULD BE IP-65 (MIN)
10. POWER FEED TO OUTDOOR EQUIPMENTS TO BE BY MULTI-CORE CABLES, SINGLE CORE WIRES
ARE NOT PERMITTED.

PROJECT
PIPE ENCASEMENT DETAIL SECTION B-B (TYP.) EARTH ELECTRODE WITH ACCESS PIT
01 SCALE = 1:150
02 HYDRAULIC ROAD BLOCKERS SA
SCALE = NTS
AT VIP LANE
REINFORCED FABRIC REINFORCED FABRIC
JOINT UNDERSEAL JOINT UNDERSEAL
(SEE GENERAL NOTE "10") (SEE GENERAL NOTE "10") CLIENT
4 WAY TP+N (40 KW) EXISTING EXISTING
EXISTING EXISTING
FEEDER PILLAR
FEEDER PILLAR
ENCLOSED IN "UV" ASPHALT ROAD ℄ ASPHALT ASPHALT ROAD ℄ ASPHALT
RESISTANT WP REINFORCED
ROAD ROAD

FIBER ENCLOSURE.
"IP-65" EXISTING WEARING COURSE NEW WEARING COURSE EXISTING WEARING CO. EXISTING WEARING COURSE NEW WEARING COURSE EXISTING WEARING CO.
WITH LOCK & 3 NOS KEYS EXISTING BITUMINOUS BASE NEW BITUMINOUS EXISTING BITUMINOUS BASE EXISTING BITUMINOUS BASE NEW BITUMINOUS EXISTING BITUMINOUS BASE EXISTING EARTH
BASE COURSE BASE COURSE EXISTING EARTH
EARTH FILL
EXISTING ROAD BASE EXISTING ROAD BASE CONSULTANT
LEAN CONCRETE C21 LEAN CONCRETE C21
MARKER TAPE
CONCRETE FOUNDATION
UV STABILIZED EPOXY PAINT MARKER TAPE MARKER TAPE
EXISTING SUB BASE EXISTING SUB BASE FINE SAND
FINISH OVER PRIMER BASE CONCRETE C21 CONCRETE C21

4x50 Ø mm 2x50 Ø mm
1x50 Ø mm COEPP LICENSE No: FB/102
50 mm DIA PVC DUCTS uPVC DUCTS uPVC DUCTS
FGL uPVC DUCTS
ENTRY FOR POWER AND DRAWING TITLE
CONTROL CABLES SPACERS
SPACERS PROPOSED LOCATION OF ROAD BLOCKERS
AT VIP LANE
: Thursday, December 29, 2022

2x75 mm DIA PVC DUCTS


ENTRY FOR POWER
PRINTED BY: Ali, Umar [NN-BH]

AND CONTROL CABLES PROJECT No: 20223078


MASTER CONTROL TO BE DRAWN DESIGNED CHECKED APPROVED
EXTENDED TO THE CUSTOM CABIN
DC/UA MN MN HA
SCALE : AS SHOWN DATE DWG. SIZE
USER : p007327F

FEEDER PILLAR
: 1:52 PM

02 JAN. 2023 A1
INSTALLATION DETAIL PIPE ENCASEMENT DETAIL SECTION A-A (TYP.) PIPE ENCASEMENT DETAIL SECTION B-B (TYP.) SECTION C-C (TYP.)
03 SCALE = 1:10
04 05 06 DRAWING NO: REV. NO.
SCALE = 1:10 SCALE = 1:10 SCALE = 1:10
SA-EL-E1-101 R1
ON
AT

You might also like