Press MENU
MENU PAGE
ADJUST MENU
Now you have to enter a PIN CODE for access to the calibration menu.
The code is written by the “scroller button.
Turn the scroller button until the right No. is shown in the marked square, press then the
scroller button to move to the next No.
When all 4 No. are written and OK is marked, press the scroller button to open the
calibration menu.
JOYSTICK MENU
”Scroller button”
Highlight the function to be calibrated and press the “scroller button” to select.
JS TELESCOPE – CALIBRATION
Min: Press A button to select calibration of MIN value for the joystick telescope.
Move the joystick to left end position, turn the “scroller button” to adjust
Actual value to -100, and press the ”scroller button” to save the value.
Max: Press B button to select calibration of MAX value for the joystick telescope.
Move the joystick to right end position, turn the “scroller button” to adjust
Actual value to 100, and press the ”scroller button” to save the value.
Actual value: This is the value the joystick is sending to IQAN-MDL display.
When the joystick is in Neutral position, should the value be as close to 0 as possible.
If the value goes over -5, 5 after calibration, then the calibration has to be fine adjusted.
Fine adjusting: One of the values has to be adjusted so it will be more then -100, 100 to
make sure that the Actual value will be as closes possible to 0.
IMPORTANT !
During calibration, you have to make sure that the
Joystick is in its mechanical min /max positions !!
Ex. Move the Joystick to left and right end positions,
If not, the joystick will NOT transmit the correct values !!
JS LIFT – CALIBRATION
Min: Press A button to select calibration of MIN value for the joystick lift.
Pull the joystick back to its end position, turn the “scroller button” to adjust
Actual value to -100, and press the ”scroller button” to save the value.
Max: Press B button to select calibration of MAX value for the joystick lift.
Push the joystick to forward end position, turn the “scroller button” to adjust
Actual value to 100, and press the ”scroller button” to save the value.
Actual value: This is the value the joystick is sending to IQAN-MDL display.
When the joystick is in Neutral position, should the value be as close to 0 as possible.
If the value goes over -5 or 5 after calibration, then the calibration has to be fine adjusted.
Fine adjusting: One of the values has to be adjusted so it will be more then -100 or 100
to make sure that the Actual value will be as closes possible to 0.
IMPORTANT !
During calibration, you have to make sure that the
Joystick is in its mechanical min /max positions !!
Ex. Push the Joystick to forward end position.
If not, the joystick will NOT transmit the correct values !!