Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0 Issued: 2012-05-11
Revision: F
ABB 3
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Functionality A B C
Protection1)
4 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Control
Circuit-breaker control ● ● ●
Auto-reclosing - o o
Condition Monitoring
Measurement
Disturbance recorder ● ● ●
ABB 5
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
GUID-B8CBF357-474F-4F61-BE28-D107515A09AA V4 EN
6 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
GUID-81A76312-4CC1-4AE8-A0A3-14C9800EE0E2 V3 EN
ABB 7
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
GUID-4F4A066F-28C1-40FB-B3A6-B2CC3119E587 V3 EN
8 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
combination of binary signal transfer and end users. As a result of the closed loop
horizontal GOOSE communication performance configuration, any fault spot in the system will be
as to speed, selectivity and reliability are hard to fed with fault current from two directions. Using
match with conventional loss-of-mains protection. plain overcurrent protection, either directional or
non-directional, it is difficult to obtain fast and
RED615 is the ideal IED for the protection of selective short circuit protection. With RED615
feeders in network configurations containing line differential protection IEDs the faulty part of
closed loops. Under normal operating conditions the network can be selectively isolated, thus
the feeder loop is closed. The aim of the closed securing power distribution to the healthy part of
loop is to secure the availability of power for the the network.
GUID-D4440C4D-6C02-4A37-A38B-1AEDCA9246FC V1 EN
Figure 4. Closed loop network configuration with RED615 line differential protection and control IEDs
Under certain operational circumstances, such as the protection devices of the network when the
maintenance of primary equipment or substation network topology is changed, line differential
extension projects there will be a need for protection IEDs can be used to obtain absolutely
interconnecting network parts, which normally are selective feeder protection in looped networks.
separated. To avoid major re-parameterization of
ABB 9
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
GUID-245166BA-1052-4EDC-8C2D-9C968FA05C66 V3 EN
Figure 5. RED615 protecting an interconnecting feeder between two primary distribution substations
10 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
GUID-9DC3BAB9-9FA4-4A6D-83C4-E1A7FCE811B0 V3 EN
Figure 6. Line differential protection of an overhead line feeder using RED615 with the standard configuration B
ABB 11
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
In figure 6 selectivity of earth-fault protection is tripping of the circuit breaker. If the earth-fault is
ensured using binary signal transfer (BST) within the protected zone, no blocking signal will
between the directional E/F protection stages of be issued, and the internal fault is cleared by the
the local and remote end. The lowest directional E/ tripping stages of the directional E/F protection.
F stages are not used for tripping purposes, but To ensure simultaneous tripping of the local and
set to detect earth-faults in the reverse direction. remote end circuit breakers, BST is also used for
Upon detection of an out-of-zone earth-fault, a sending an intertrip signal to the remote end
blocking signal is sent to the remote end during earth-fault situations within the protected
directional E/F protection stage preventing zone.
12 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
GUID-9EFBFF56-5045-4B24-9C29-01C98ABA81A1 V3 EN
Figure 7. Line differential protection of an overhead line feeder using RED615 with the standard configuration C
and auto-reclosing option.
ABB 13
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Product Version
14 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
GUID-66EB52A0-21A1-4D1F-A1EF-61060B371384 V3 EN
Figure 8. Utility power distribution network example using 615 series IEDs, Grid Automation controller COM600
and MicroSCADA Pro
GUID-6984D893-45D5-427A-BABF-F1E1015C18E2 V3 EN
Figure 9. Industrial power system example using 615 series IEDs, Grid Automation controller COM600 and
System 800xA
ABB 15
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Further, the IED offers one control block which is of the IED the number of unused binary inputs
intended for motor-operated control of one and binary outputs varies. Further, some standard
earthing switch control and its position indication. configurations also offer optional hardware
modules that increase the number of available
Two physical binary inputs and two physical binary inputs and outputs. The amount of binary
binary outputs are needed in the IED for each inputs and binary outputs freely available per
controllable primary device taken into use. standard configuration in RED615 is listed in the
Depending on the chosen standard configuration table below.
- 1 1 0
A
● 7 4 2
- 0 1 0
B
● 6 4 2
- 0 1 0
C
● 6 4 2
In case the amount of available binary inputs and/ The suitability of the binary outputs of the IED
or outputs of the chosen standard configuration is which have been selected for controlling of
not sufficient, the following alternatives are primary devices should be carefully verified, for
recommended: example the make and carry as well as the
• To modify the chosen standard configuration of breaking capacity. In case the requirements for
the IED in order to release some binary inputs the control-circuit of the primary device are not
or binary outputs which have originally been met, the use of external auxiliary relays should to
configured for other purposes, when applicable. be considered.
• To integrate an external input or output module
for example, RIO600 to the IED. The binary The optional large graphical LCD of the IED's HMI
inputs and outputs of the external I/O module includes a single-line diagram (SLD) with position
can be used for the less time critical binary indication for the relevant primary devices.
signals of the application. The integration Interlocking schemes required by the application
enables releasing of some initially reserved are configured using the signal matrix or the
binary inputs and outputs of the IED in the application configuration functionality of PCM600.
standard configuration.
16 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
The analog channels can be set to trigger the 11. Condition monitoring
recording function when the measured value falls The condition monitoring functions of the IED
below or exceeds the set values. The binary constantly monitors the performance and the
signal channels can be set to start a recording on condition of the circuit breaker. The monitoring
the rising or the falling edge of the binary signal or comprises the spring charging time, SF6 gas
both. pressure, the travel-time and the inactivity time of
the circuit breaker.
By default, the binary channels are set to record
external or internal IED signals, for example the The monitoring functions provide operational
start or trip signals of the IED stages, or external circuit breaker history data, which can be used for
blocking or control signals. Binary IED signals scheduling preventive circuit breaker maintenance.
such as a protection start or trip signal, or an
external IED control signal over a binary input can 12. Trip-circuit supervision
be set to trigger the recording. The recorded The trip-circuit supervision continuously monitors
information is stored in a non-volatile memory and the availability and operability of the trip circuit. It
can be uploaded for subsequent fault analysis. provides open-circuit monitoring both when the
circuit breaker is in its closed and in its open
9. Event log position. It also detects loss of circuit-breaker
To collect sequence-of-events (SoE) information, control voltage.
the IED incorporates a non-volatile memory with a
capacity of storing 1024 events with associated 13. Self-supervision
time stamps. The non-volatile memory retains its The IED’s built-in self-supervision system
data also in case the IED temporarily loses its continuously monitors the state of the IED
auxiliary supply. The event log facilitates detailed hardware and the operation of the IED software.
pre- and post-fault analyses of feeder faults and Any fault or malfunction detected is used for
disturbances. The increased capacity to process alerting the operator.
and store data and events in the IED offers
prerequisites to support the growing information A permanent IED fault will block the protection
demand of future network configurations. functions to prevent incorrect operation.
ABB 17
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
15. Protection communication and supervision RPW600 modems (master and follower) are
The communication between the IEDs is enabled galvanically connected to either end of the pilot
by means of a dedicated fibre-optic wire and optically connected to the IEDs using
communication channel. 1300 nm multi-mode or short optical single-mode cables. Using 0.8 mm 2
single-mode fibres with LC connectors are used twisted pair cables pilot wire link distances up to
for line differential communication. The channel is 8 km are typically supported. However, twisted
used for transferring the phase segregated pair pilot wire cables in good conditions may
current value data between the IEDs. The current support even longer distances to be covered. The
phasors from the two IEDs, geographically length of the supported pilot wire link also
located apart from each other, must be time depends on the noise environment in the
coordinated so that the current differential installation. Should the need arise to replace the
algorithm can be executed correctly. The so pilot wire cables with fibre-optic cables, the single
called echo method is used for time mode fibre-optic LC connectors of the IEDs can
synchronization. No external devices such as be utilized for direct connection of the fibre-optic
GPS clocks are thereby needed for the line communication link.
differential protection communication.
Apart from the continued protection
As an option to the fibre-optic communication link communication, the communication channel can
a galvanic connection over a pilot wire link also be used for binary signal transfer (BST) that
composed of a twisted pair cable and RPW600 is, transferring of user configurable binary
link-end communication modems can be information between the IEDs. There are a total of
established. The optional pilot wire eight BST signals available for user definable
communication link is also an ideal and cost purposes. The BST signals can originate from the
efficient retrofit solution for electromechanical line IED’s binary inputs or internal logics, and be
differential protection installations. Compared to assigned to the remote IED’s binary outputs or
conventional combined sequence line differential internal logics.
protection solutions with analog pilot wire
communication, RED615 IEDs in combination The protection communication supervision
with RPW600 communication modems offer a continuously monitors the protection
modern phase-segregated line differential communication link. The IED immediately blocks
protection solution over existing pilot wire cables. the line differential protection function in case that
severe interference in the communication link,
The pilot wire link supports the same protection risking the correct operation of the function, is
and communication functionality as the fibre-optic detected. An alarm signal will eventually be issued
link. The quality of service (QoS) is indicated by if the interference, indicating permanent failure in
the modems and the communication link is the protection communication, persists. The two
continuously supervised by the IED. The RPW600 high-set stages of the overcurrent protection are
modem offers a 5 kV (RMS) level of isolation further by default released.
between the pilot wire terminals and ground. The
18 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
RED615 RED615
GUID-8CE71CC9-F0EA-4BE9-B693-173CAEA9FA58 V1 EN
RED615 RED615
GUID-12C57326-6CB9-4FA9-B9F4-3D8F21015DCF V1 EN
ABB 19
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
All binary inputs and outputs contacts are freely Please refer to the Input/output overview table
configurable with the signal matrix or application and the terminal diagrams for more detailed
configuration functionality of PCM600. information about the inputs and outputs.
CT VT BI BO
A 4 - 12 (18)1) 10 (13)1)
B 4 1 11 (17)1) 10 (13)1)
C 4 - 12 (18)1) 10 (13)1)
20 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Modbus implementation supports RTU, ASCII and The IED supports the following time
TCP modes. Besides standard Modbus synchronization methods with a time-stamping
functionality, the IED supports retrieval of time- resolution of 1 ms:
stamped events, changing the active setting
group and uploading of the latest fault records. If Ethernet-based:
a Modbus TCP connection is used, five clients • SNTP (Simple Network Time Protocol)
can be connected to the IED simultaneously.
Further, Modbus serial and Modbus TCP can be With special time synchronization wiring:
used in parallel, and if required both IEC 61850 • IRIG-B (Inter-Range Instrumentation Group -
and Modbus protocols can be run simultaneously. Time Code Format B)
When the IED uses the RS-485 bus for the serial
Remote-end station time reference:
communication, both two- and four wire
• Line differential
connections are supported. Termination and pull-
up/down resistors can be configured with jumpers
on the communication card so external resistors
are not needed.
ABB 21
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Client A Client B
Network
Network
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V3 EN
IEC 61850 ● - -
MODBUS RTU/ASCII - ● ●
MODBUS TCP/IP ● - -
DNP3 (serial) - ● ●
DNP3 TCP/IP ● - -
IEC 60870-5-103 - ● ●
● = Supported
22 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Table 7. Dimensions
Description Value
case 164 mm
case 160 mm
Uauxnominal 100, 110, 120, 220, 240 V AC, 50 and 24, 30, 48, 60 V DC
60 Hz
Burden of auxiliary voltage supply DC < 12.0 W (nominal)/< 18.0 W (max) DC < 12.0 W (nominal)/< 18.0 W (max)
under quiescent (Pq)/operating AC< 16.0 W (nominal)/< 21.0W (max)
condition
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
ABB 23
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Description Value
• Continuously 4A 20 A
Voltage withstand:
• Continuous 240 V AC
• For 10 s 360 V AC
Description Value
Reaction time 3 ms
Description Value
24 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Description Value
Description Value
Description Value
Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s
ABB 25
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Connector Fibre type Wave length Max. distance Permitted path attenuation1)
Description Value
Modulation Unmodulated
Description Value
Front side IP 54
Description Value
Altitude Up to 2000 m
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For IEDs with an LC communication interface the maximum operating temperature is +70 ºC
26 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
1) For IEDs with an LC communication interface the maximum operating temperature is +70 o C
ABB 27
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
• Contact discharge 8 kV
• Air discharge 15 kV
• All ports 4 kV
• 2s 100 A/m
28 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
150 V rms
• Conducted
• Radiated
Impulse voltage test 5 kV, 1.2/50 μs, 0.5 J IEC 60255-5 and
1 kV, 1.2/50 μs, 0.5 J, communication IEC 60255-27
ABB 29
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Description Reference
LV directive 2006/95/EC
Description Reference
Description
30 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Protection functions
Characteristics Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the set value or ±20 ms 4)
1) With the symmetrical communication channel (as when using dedicated fiber optic).
2) Without additional delay in the communication channel (as when using dedicated fiber optic).
3) Including the delay of the output contact. When differential current = 2 x High operate value and f n = 50 Hz with galvanic pilot wire link + 5 ms.
4) Low operate value multiples in range of 1.5 to 20.
Operate curve type 1=ANSI Ext. inv. Selection of time delay curve for
3=ANSI Norm. inv. stabilized stage
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
ABB 31
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Characteristic Value
Characteristic Value
PHIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value
11 ms 12 ms 14 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0
x In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
32 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
PHHPTOC 40...200000 ms 10
PHIPTOC 20...200000 ms 10
ABB 33
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Characteristic Value
EFIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value 11 ms 12 ms 14 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Measurement mode = default (depends on stage), current before fault = 0.0 x I n, f n = 50 Hz, earth-fault current with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20
34 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
EFHPTOC 40...200000 ms 10
EFIPTOC 20...200000 ms 10
ABB 35
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Characteristic Value
DEFLPDEF Current:
±1.5% of the set value or ±0.002 x In
Voltage
±1.5% of the set value or ±0.002 x Un
Phase angle:
±2°
DEFHPDEF Current:
±1.5% of the set value or ±0.002 x In
(at currents in the range of 0.1…10 x In)
±5.0% of the set value
(at currents in the range of 10…40 x In)
Voltage:
±1.5% of the set value or ±0.002 x Un
Phase angle:
±2°
DEFHPDEF
IFault = 2 x set Start value 42 ms 44 ms 46 ms
DEFLPDEF 61 ms 64 ms 66 ms
IFault = 2 x set Start value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0
x In, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20
36 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
DEFHPDEF 40...200000 ms 10
Characteristic Value
Operation accuracy (Uo criteria with transient protection) Depending on the frequency of the current measured: fn
±2 Hz
ABB 37
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Characteristic Value
±1.0% or ±0.01 mS
(In range of 0.5 - 100 mS)
56 ms 60 ms 64 ms
Reset time 40 ms
1) Uo = 1.0 x Un
2) Includes the delay of the signal output contact. Results based on statistical distribution of 1000 measurements.
38 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Voltage start value 0.05...5.00 xUn 0.01 0.05 Voltage start value
ABB 39
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode ±5.0% of the set value or ±20 ms
1) Io varied during the test. Uo = 1.0 x Un = phase to earth voltage during earth-fault in compensated or un-earthed network. The residual power value
before fault = 0.0 p.u., fn = 50 Hz, results based on statistical distribution of 1000 measurement.
2) Includes the delay of the signal output contact.
40 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode 3) ±5.0% of the set value or ±20 ms
-3dB at f= 13 x fn
1) Fundamental frequency current = 1.0 x In. Harmonics current before fault = 0.0 x In, harmonics fault current 2.0 x Start value. Results based on
statistical distribution of 1000 measurement.
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x In, Start value multiples in range of 2 to 20
ABB 41
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Residual voltage before fault = 0.0 x U n , f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Negative sequence current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20
42 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Characteristic Value
ABB 43
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Characteristic Value
44 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Characteristic Value
Current measurement:
±1.5% of the set value or ±0.002 x In
Ratio I2f/I1f measurement:
±5.0% of the set value
ABB 45
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
46 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Supervision functions
Characteristic Value
ABB 47
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Control functions
Characteristic Value
48 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Measurement functions
Characteristic Value
±0.5% or ±0.002 x In
(at currents in the range of 0.01...4.00 x In)
Characteristic Value
±1.0% or ±0.002 x In
at currents in the range of 0.01...4.00 x In
Characteristic Value
±0.5% or ±0.002 x In
at currents in the range of 0.01...4.00 x In
Characteristic Value
±0.5% or ±0.002 x Un
ABB 49
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
20. Local HMI default single line diagram. The SLD view can also
The IED is available with two optional displays, a be accessed using the web-browser based user
large one and a small one. The large display is interface. The default SLD can be modified
suited for IED installations where the front panel according to user requirements by using the
user interface is frequently used and a single line graphical display editor in PCM600.
diagram is required. The small display is suited for
remotely controlled substations where the IED is The local HMI includes a push button (L/R) for
only occasionally accessed locally via the front local/remote operation of the IED. When the IED
panel user interface. is in the local mode, the IED can be operated only
by using the local front panel user interface. When
Both LCD displays offer front-panel user interface the IED is in the remote mode, the IED can
functionality with menu navigation and menu execute commands sent from a remote location.
views. However, the large display offers increased The IED supports the remote selection of local/
front-panel usability with less menu scrolling and remote mode via a binary input. This feature
improved information overview. In addition, the facilitates, for example, the use of an external
large display includes a user-configurable single switch at the substation to ensure that all IEDs
line diagram (SLD) with position indication for the are in the local mode during maintenance work
associated primary equipment. Depending on the and that the circuit breakers cannot be operated
chosen standard configuration, the IED displays remotely from the network control centre.
the related measuring values, apart from the
IECA070904 V3 EN IECA070901 V3 EN
50 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
190
6
18
164
177 25°
160
160
177
230
177
107
133
98
48
1 53
103
IECA070902 V4 EN
IECA070900 V4 EN IECA070903 V4 EN
Figure 17. Semi-flush with a 25º
Figure 15. Flush mounting Figure 16. Semi-flush mounting tilt
22. IED case and IED plug-in unit operating contacts for short-circuiting the CT
For safety reasons, the IED cases for current secondary circuits when a IED unit is withdrawn
measuring IEDs are provided with automatically from its case. The IED case is further provided
ABB 51
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
with a mechanical coding system preventing on the upper part of the plug-in-unit. An order
current measuring IED units from being inserted number label is placed on the side of the plug-in
into a IED case for a voltage measuring IED unit unit as well as inside the case. The order number
and vice versa, i.e. the IED cases are assigned to consists of a string of codes generated from the
a certain type of IED plug-in unit. IED's hardware and software modules.
H B D CACADBKC1BAN1XE
# Description
1 IED
615 series IED (including case) H
615 series IED (including case) with test switch, wired and in -
K
stalled in a 19” equipment panel
615 series IED (including case) with test switch, wired and in -
stalled in a mounting bracket for CombiFlex rack mounting (RGHT L
19” 4U variant C)
2 Standard
IEC B
3 Main application
Line differential protection and control D
GUID-4753ED2D-5A23-4F34-A689-9E47511ED8C7 V5 EN
The standard configuration determines the I/O hardware and available options. HBD CACAD BKC1BAN1XE
The example below shows standard configuration “C” with chosen options.
# Description
4-8 Standard configurations, analog and binary I/O options
Standard configuration descriptions in short:
A = Line-differential protection, CB control and with the optional I/O module
control of two network objects
B = Line-differential protection with directional earth-fault protection, CB condi -
tion monitoring, CB control and with the optional I/O module control of two
network objects
C = Line-differential protection with non-directional earth-fault protection, CB
condition monitoring, CB control and with the optional I/O module control of
two network objects
Std. conf. I/O options
A 4I (Io 1/5 A) + 12 BI + 10 BO AACAD
A 4I (Io 1/5 A) + 18 BI + 13 BO AACAF*
B 4I (Io 1/5 A) + Uo + 11 BI + 10 BO BAAAC
B 4I (Io 1/5 A) + Uo + 17 BI + 13 BO BAAAE*
B 4I (Io 0.2/1 A) + Uo + 11 BI + 10 BO BABAC
B 4I (Io 0.2/1 A) + Uo + 17 BI + 13 BO BABAE*
C 4I (Io 1/5 A) + 12 BI + 10 BO CACAD
C 4I (Io 1/5 A) + 18 BI + 13 BO CACAF*
52 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
The communication module hardware determines the available communication proto - HBD CACAD B K C1BAN1XE
cols. Choose the hardware from one of the rows below to define the digits # 9-10.
# Description
9 Communication modules (Serial/Ethernet)
-
Serial RS-485 incl. IRIG-B + Line differential, multi mode fibre (LC) AA
10
Serial RS-485 incl. IRIG-B + Line differential, single mode fibre
AB
(LC)
Serial RS-485 incl. IRIG-B + Ethernet 100Base-TX (RJ-45) + Line
AG
differential, multi mode fibre (LC)
Serial RS-485 incl. IRIG-B + Ethernet 100Base-TX (RJ-45) + Line
AH
differential, single mode fibre (LC)
Serial RS-485 incl. IRIG-B + Ethernet 100Base-TX (2 x RJ-45) +
AJ
Line differential, multi mode fibre (LC)
Serial RS-485 incl. IRIG-B + Ethernet 100Base-TX (2 x RJ-45) +
AK
Line differential, single mode fibre (LC)
Serial glass fibre (ST) incl. an input for IRIG-B + Line differential,
BA
multi mode fibre (LC)
Serial glass fibre (ST) incl. an input for IRIG-B + Line differential,
BB
single mode fibre (LC)
Serial glass fibre (ST) incl. an input for IRIG-B + Ethernet
BG
100Base-TX (RJ-45) + Line differential, multi mode fibre (LC)
Serial glass fibre (ST) incl. an input for IRIG-B + Ethernet
BH
100Base-TX (RJ-45) + Line differential, single mode fibre (LC)
Serial glass fibre (ST) incl. an input for IRIG-B + Ethernet
BJ
100Base-TX (2 x RJ-45) + Line differential, multi mode fibre (LC)
Glass fibre (ST) incl. an input for IRIG-B + Ethernet 100Base-TX (2
BK
x RJ-45) + Line differential, single mode fibre (LC)
Line differential, multi mode fibre (LC) NA
Line differential, single mode fibre (LC) NB
Ethernet 100Base-TX (RJ-45) + Line differential, multi mode fibre NG
(LC)
Ethernet 100Base-TX (RJ-45) + Line differential, single mode fibre NH
(LC)
Ethernet 100Base-TX (2 x RJ-45) + Line differential, multi mode NJ
fibre (LC)
Ethernet 100Base-TX (2 x RJ-45) + Line differential, single mode NK
fibre (LC)
If serial communication is chosen, please choose a serial communication module including Ethernet (for example “BK”) if a service
bus for PCM600 or the WebHMI is required.
GUID-9FD2F37D-BDBB-4729-81D7-D6027C11E7A4 V2 EN
HBDCACADBK C 1BAN1XE
# Description
11 Communication protocols
IEC 61850
(for Ethernet communication modules and IEDs without a A
communication module )
Modbus
(for Ethernet/serial or Ethernet + serial communication B
modules)
IEC 61850 + Modbus
C
(for Ethernet or serial + Ethernet communication modules)
IEC 60870-5-103
D
(for serial or Ethernet + serial communication modules)
DNP3
(for Ethernet/serial or Ethernet + serial communication E
modules)
GUID-353B93B5-ABB9-4B3B-83C9-7D5A43A81C86 V2 EN
ABB 53
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
HBD CACADBKC 1 B A N 1 XE
# Description
12 Language
English 1
English and German 3
English and Swedish 4
English and Spanish 5
English and Russian 6
English and Polish 7
English and Portuguese (Brazilian) 8
English and Italian A
English and French C
English and Czech E
13 Front panel
Small LCD A
Large LCD with single line diagram (SLD) B
14 Option 1
GUID-A0044B6F-5B14-4D16-8A43-A32DA568A815 V2 EN
Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Code
GUID-7FB496F7-7514-4B77-9E1A-F24B6AC17BF3 V5 EN
54 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Pilot Wire communication package including two Pilot Wire modems: RPW600AM RPW600AMF
(master) and RPW600AF (follower)
Diagnostics kit including the RPW-diagnostic tool, a diagnostic cable and a CD with RPW600ADP
necessary drivers and information
3.0 meter LC-LC single-mode fibre-optic patch cable for connecting one Pilot Wire 1MRS120547-3
modem to the RED615 IED1)
1) Please note that two patch cables are required for connecting the Pilot Wire communication package (RPW600AMF).
19” rack mounting kit with cut-out for one IED 1MRS050694
19” rack mounting kit with cut-out for two IEDs 1MRS050695
Mounting bracket for one IED with test switch RTXP in 4U Combiflex (RHGT 19” variant C) 2RCA022642P0001
Mounting bracket for one IED in 4U Combiflex (RHGT 19” variant C) 2RCA022643P0001
19” rack mounting kit for one IED and one RTXP18 test switch (the test switch is not 2RCA021952A0003
included in the delivery)
19” rack mounting kit for one IED and one RTXP24 test switch (the test switch is not 2RCA022561A0003
included in the delivery)
Replacement kit for a Strömberg SP_J40 series relay (cut-out in the center of the 2RCA027871A0001
installation plate)
Replacement kit for a Strömberg SP_J40 series relay (cut-out on the left or the right of 2RCA027874A0001
the installation plate)
19” rack replacement kit for Strömberg SP_J3/J6 series relays (one cut-out) 2RCA027894A0001
19” rack replacement kit for Strömberg SP_J3/J6 series relays (two cut-outs) 2RCA027897A0001
ABB 55
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
PCM600 Basic/Engineering and PCM600 functionality of the interface can be limited to read-
Engineering Pro. Depending on the chosen only access by means of PCM600.
variant, PCM600 offers extensive IED
configuration functions such as IED signal The IED connectivity package is a collection of
configuration, application configuration, graphical software and specific IED information, which
display configuration including single line diagram enable system products and tools to connect and
configuration, and IEC 61850 communication interact with the IED. The connectivity packages
configuration including horizontal GOOSE reduce the risk of errors in system integration,
communication. minimizing device configuration and set-up times.
Further, the Connectivity Packages for the 615
When the web-browser based user interface is series IEDs include a flexible update tool for
used, the IED can be accessed either locally or adding one additional local HMI language to the
remotely using a web browser (IE 7.0 IE 8.0 or IE IED. The update tool is activated using PCM600
9.0). For security reasons, the web-browser and enables multiple updates of the additional
based user interface is disabled by default. The HMI language, thus offering flexible means for
interface can be enabled with the PCM600 tool or possible future language updates.
from the front panel user interface. The
56 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Signal monitoring ● ● ●
Modbus® communication
configuration (communication
management) - ● ●
Application configuration - ● ●
Event viewing ● ● ●
ABB 57
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
GUID-FBFA9940-E37D-4C32-A083-0367AAEDE267 V2 EN
58 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
GUID-A05D9233-4377-48D7-9F00-4218F0E7D4DC V2 EN
ABB 59
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
GUID-EBB33CDF-272D-4599-8673-9793D097D32E V2 EN
60 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Protection
Non-directional earth-fault protection, low stage EFLPTOC1 Io> (1) 51N-1 (1)
Non-directional earth-fault protection, high stage EFHPTOC1 Io>> (1) 51N-2 (1)
Directional earth-fault protection, low stage DEFLPDEF1 Io> -> (1) 67N-1 (1)
Admittance based earth-fault protection EFPADM1 Yo> -> (1) 21YN (1)
Wattmetric based earth-fault protection WPWDE1 Po> -> (1) 32N (1)
ABB 61
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
Control
Condition monitoring
Measurement
62 ABB
Line Differential Protection and Control 1MRS756500 F
RED615
Product version: 4.0
ABB 63