210 - VRV 5 S-Series Product Flyer
210 - VRV 5 S-Series Product Flyer
a sustainable
future
CO ErP 2021
COMPLIANT
The time to act is now. Join us in creating a sustainable future for HVAC-R.
INNOVATION
www.daikin.eu/building-a-circular-economy
2
INNOVATION
-71%
Advantages of R-32 100%
Industry-leading
ErP 2021 real life efficiencies
COMPLIANT
3
The best VRV
we ever made
Lower CO2, equivalent and
market-leading versatility
Top sustainability
Reduced CO2 equivalent thanks to the use of R-32 refrigerant CO
› R-32 Global Warming Potential (GWP) is 68% lower than R-410A
› 15% less refrigerant charge
Leading to a GWP reduction of 71% on system level!
Top sustainability over the entire lifecycle, thanks to market leading real-life seasonal efficiency
Ideal for your green building certification, thanks to lower GWP refrigerant
No leak check requirement for majority of installations (up to 7,4 kg of total charge)
4
Maximum flexibility out of the box
With Shirudo technology your VRV 5 system takes care of small room applications in your building, without the need for any additional
considerations and equipment in the field.
› Fully compliant with the latest product standard IEC60335-2-40 (Ed.6)
› Third party CB certified by a Notified Body (SGS CEBEC)
Automatic and real time leak detection, alarm and refrigerant recovery
Shîrudo technology minimizes furthermore the risk of direct CO2 eq. impact from a refrigerant leak.
The system is continuously self monitoring, and in the unlikely event of a refrigerant leak, this is
immediately detected. An alarm is activated to notify tenants, while refrigerant is automatically recovered.
Specially designed new 10 class indoor unit for small, well-insulated rooms
5
Did you know …
different standards regarding F-gas safety regulations exist?
Two standards are applied to cover the safety regulations of refrigerants:
› EN378:2016: the generic standard on refrigerants covering the toxicity of the refrigerant (class A or B)
› IEC60335-2-40 (Ed.6): the specific heat pump product standard covering the flammability of the refrigerant (1, 2L, 2, 3)
A2L refrigerants are stricter than the ones for toxicity, 10.0
the application area of VRV 5 is covered by
IEC60335-2-40 (Ed.6)! 8.0
6.0
EN378:2016 Toxicity limit R-32
4.0
Very strict safety measures; installation not
2.0 possible (similar to R-410A situation today)
0.0
0 20 40 60 80 100
Minimum room surface (m2)
The true flexibility of a system is highly depending on keeping the considerations needed to select, install and maintain a system to
the minimium. Daikin has 2 factory-integrated measures, undertaking full responsibility about compliance to product standard and
offering maximum flexibilty if some simple installation requirements are respected.
Area 2
Area 3
10.0
Area 2: application area with 2 measures integrated
8.0 › Daikin Shîrudo technology enables to use the VRV
6.5 system to it‘s full potential with a minimum room
6.0 surface down to 10 m² (1)
Area 1: no additional measures
4.0 Highly increased
flexibility thanks to required under IEC60335-2-40 Ed.6 (1) For applications below 10 m2 contact your local Daikin representative.
factory-mounted
2.0 measures Reaction time of Extended application
Daikin VRV 5 system area of VRV 5
0.0 20 39 40 60 80 100 Refrigerant charge for a Application area
10.0 typical mini VRV installation without any measures
Minium room surface (m2) with 90~110m pipe length
6
Taking care
of every room in your building
With Shirudo technology your VRV 5 system takes are of any room down to 10 m², without
the need for time consuming selections and additional measures to be taken in the field.
With all measures factory-integrated, VRV 5 is the most flexible and quick to design, fully
compliant to the latest product standards.
With new
Madoka
BRC1H52W/S/K !
ceiling unit
› Small capacity unit developted for small of well-insulated rooms
Auto cleaning
› Reduced energy consumption thanks to DC fan motor
filter option
Concealed Slimmest yet most powerfull medium static pressure unit on the market!
ceiling unit
› Slimmest unit in class, only 245mm
› Low operating sound level
with
medium
› Medium external static pressure up to 150Pa facilitates using flexible ducts of
varying lengths
FXSA-A
ESP › Automatic air flow adjustment function measures the air volume and static
pressure and adjusts it towards the nominal air flow, guaranteeing comfort
Wall mounted
(1) Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m
(2) Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m
8
VRV 5 indoor unit benefit overview Ceiling mounted
cassette units
Concealed ceiling units
Wall
moun-
ted
unit
Home leave operation During absence, indoor comfort levels can be maintained
Fan only The air conditioner can be used as fan, blowing air without cooling or heating
We care
Daikin indoor units are whisper quiet. Also the outdoor units are guaranteed
Whisper quiet
not to disturb the quiet of the neightbourhood
Auto cooling-heating
changeover
Automatically selects cooling or heating mode to achieve the set temperature
G1(2)
treatment
Air filter Removes airborne dust particles to ensure a steady supply of clean air G1(2) G1(2)
of auto cleaning
panel)
Humidity
control
Dry programme Allows humidity levels to be reduced without variations in room temperature
The air discharge of the indoor unit is specially designed to prevent air being
Ceiling soiling prevention
blown against the ceiling to prevent ceiling stains
Possibility to select automatic vertical moving of the air discharge louvre, for
Vertical auto swing
uniform air flow and temperature distribution
Air flow
Fan speed steps Multiple fan speeds to select,to optimize comfort levels 5 + auto 3 + auto 3 3 + auto 3
Individual louver control via the wired remote controller makes it simple
Individual louver control to fix the position of each louver individually, to suit any new room
configuration. Optional closure kits are available as well
Daikin residential controller Can control and monitor the status of your Daikin heating or air conditioning
(BRP069C51) system
Remote control & timer
NEW
Timer can be set to start and stop operation anytime on a daily or weekly
Weekly timer
basis
Infrared remote control Infrared remote control with LCD to remotely control your indoor unit (1) (1) (1) (1) (1)
Wired remote control Wired remote control to remotely control your indoor unit Only connectable to new BRC1H52W/S/K
Centralised control Centralised control to to control several indoor units from one single point
Auto-restart The unit restarts automatically at the original settings after power failure
Other funtcions
Compact dimensions
› Easy to transport thanks to compact size
and single-fan design
Specially
designed grille
› Low pressure drop Refrigerant cooled PCB
› No risk for accidental With integrated:
reach of the fan › cool/heat selector input
› 7-segment display for quicker
and more precise error and
setting reading
10
NEW RXYSA-AV1/AY1
VRV 5 S-series
1.100 mm 460 mm
Lower CO2 equivalent and market-leading flexibility
RXYSA-AV/AY1
Only
869mm
high!
level difference
CO ErP 2021
COMPLIANT
(1) Actual number of units depends on the indoor unit type and the connection ratio restriction for the system (being 50% <= 130%)
11
The most comfortable cassette
just got better
› Widest ever choice in panels for cassette units, with up to 8 different panels
Black auto cleaning panel Black designer panel Full white standard panel White designer panel
* Available as an option
12
NEW FXFA-A
Main unit
› Standard drain pump with 675mm lift increases flexibility White panel White auto cleaning panel Black panel Black design panel
and installation speed
Indoor unit FXFA 20A 25A 32A 40A 50A 63A 80A 100A 125A
Cooling capacity Total capacity at high fan speed kW 2.20 2.80 3.60 4.50 5.60 7.10 9.00 11.20 14.00
Heating capacity Total capacity at high fan speed kW 2.50 3.20 4.00 5.00 6.30 8.00 10.00 12.50 16.00
Power input - 50Hz Cooling at high fan speed kW 0.04 0.05 0.06 0.09 0.12 0.19
Heating at high fan speed kW 0.04 0.05 0.06 0.09 0.12 0.19
Dimensions Unit HeightxWidthxDepth mm 204x840x840 246x840x840 288x840x840
Weight Unit kg 18 19 21 24 26
Casing Material Galvanised steel plate
Decoration panel Model Standard panels: BYCQ140E - white with grey louvers / BYCQ140EW - full white / BYCQ140EB - black
Auto cleaning panels BYCQ140EGF - white / BYCQ140EGFB - black
Designer panels: BYCQ140EP - white / BYCQ140EPB - black
Dimensions HeightxWidthxDepth mm Standard panels: 65x950x950 / Auto cleaning panels: 148x950x950 / Designer panels: 106x950x950
Weight kg Standard panels: 5.5 / Auto cleaning panels: 10.3 / Designer panels: 6.5
Fan Air flow rate - Cooling At high fan speed m³/min 12.8 14.8 15.1 16.6 23.3 28.8 33.0
50Hz Heating At high fan speed m³/min 12.8 14.8 15.1 16.6 23.3 28.8 33.0
Air filter Type Resin net
Sound power level Cooling At high fan speed dBA 49 (4) 51 (4) 53 (4) 55 (4) 60 (4) 61 (4)
Sound pressure Cooling L/ML/M/MH/H dBA 31/30/29/29.5/28 (4) 33 / 32 / 31 /30 / 29 (4) 35 / 34 / 33/32/30 (4) 38/ 36 /34 /32/30 (4) 43/41/37/34 /30 (4) 45/43/41/39 /36 (4)
level Heating L/ML/M/MH/H dBA 31/30/29/29.5/28 (4) 33 / 32/31 /30 /29 (4) 35 / 34 / 33 / 32/30 (4) 38/ 36 /34 /32 /30 (4) 43/41/37/34 /30 (4) 45/43/41/39 /36 (4)
Refrigerant Type/GWP R-32 / 675
Piping connections Liquid OD mm 6.35 9.52
Gas OD mm 9.52 12.7 15.9
Drain VP25 (O.D. 32 / I.D. 25)
Power supply Phase/Frequency/Voltage Hz/V 1~/50/60/220-240/220
Current - 50Hz Maximum fuse amps (MFA) (1) A 6
Control systems Infrared remote control BRC7FA532F (2)
Wired remote control BRC1H52W/S/K
(1) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing
(2) Must be combined with Madoka wired remote controller.
(3) L/ML/M/MH/H are the different fan speeds availble. L= low; ML= medium low; M= medium; MH= medium high; H= high
(4) Sound of designer panel: +3dB
13
14
NEW FXZA-A
15
Auto cleaning filter for
concealed ceiling units
0%
start 6 months 12 months
› The dust box can be emptied with a vacuum cleaner for fast
and easy cleaning How does it work?
› No more dirty ceilings
› Optimum airflow eliminates draft and insulates sound 2 Dust collects in a dust box that’s
integrated into the unit
Superb reliability
› Prevents clogged filters for seamless operation 3 The dust can easily be removed with
a vacuum cleaner
Unique technology
Combination table
www.youtube.com/DaikinEurope
Split / Sky Air VRV
Specifications
FDXM-F9 FXDA-A/FXDQ-A3
16
NEW FXDA-A
FXDA-A
200 mm
NEW
700 mm
50 mm
Indoor unit FXDA 10A 15A 20A 25A 32A 40A 50A 63A
Cooling capacity Total capacity At high fan speed kW 1.10 1.70 2.20 2.80 3.60 4.50 5.60 7.10
Heating capacity Total capacity At high fan speed kW 1.30 1.90 2.50 3.20 4.00 5.00 6.30 8.00
Power input - 50Hz Cooling At high fan speed kW 0.042 0.057 0.068 0.075 0.096 0.107
Heating At high fan speed kW 0.042 0.057 0.068 0.075 0.096 0.107
Required ceiling void > mm 240
Dimensions Unit HeightxWidthxDepth mm 200x750x620 200x950x620 200x1,150x620
Weight Unit kg 22.0 26.0 29.0
Casing Material Galvanised steel
Fan Air flow rate - 50Hz Cooling At high fan speed m³/min 5.2 6.5 8.0 10.5 12.5 16.5
External static Factory set/High Pa 10/30.0 15/44.0
pressure - 50Hz
Air filter Type Removable / washable
Sound power level Cooling At high fan speed dBA 48 50 51 52 53 54
Sound pressure level Cooling Low/Medium/High fan speed dBA 26 / 28 / 29 27.0/31.0/32.0 27.0/31.0/33.0 28.0/32.0/34.0 29.0/33.0/35.0 30.0/34.0/36.0
Refrigerant Type/GWP R-32 / 675
Piping connections Liquid OD mm 6.35
Gas OD mm 9.52 12.7
Drain VP20 (I.D. 20/O.D. 26)
Power supply Phase/Frequency/Voltage Hz/V 1~/50/60/220-240/220
Current - 50Hz Maximum fuse amps (MFA) A 6
Control systems Infrared remote control BRC4C65 / BRC4C66 (1)
Wired remote control BRC1H52W/S/K
(1) Must be combined with Madoka wired remote controller.
17
NEW FXSA-A
› Slimmest unit in class, only 245mm (300mm built-in height) and bottom
suction
therefore narrow ceiling voids are no longer a challenge FXSA-A
245 mm
NEW
For free use into a false For connecting onto a For direct connection to
ceiling suction canvas Daikin panel
(not supplied by Daikin) (via EKBYBSD kit)
Indoor unit FXSA 15A 20A 25A 32A 40A 50A 63A 80A 100A 125A 140A
Cooling capacity Total capacity At high fan speed kW 1.70 2.20 2.80 3.60 4.50 5.60 7.10 9.00 11.20 14.00 16.00
Heating capacity Total capacity At high fan speed kW 1.90 2.50 3.20 4.00 5.00 6.30 8.00 10.0 12.5 16.0 18.0
Power input - 50Hz Cooling At high fan speed kW 0.086 0.147 0.150 0.183 0.209 0.285 0.326 0.382
Heating At high fan speed kW 0.086 0.147 0.150 0.183 0.209 0.285 0.326 0.382
Dimensions Unit HeightxWidthxDepth mm 245x550x800 245x700x800 245x1,000x800 245x1,400x800 245x1,550x800
Weight Unit kg 23.5 24.0 28.5 29.0 35.5 36.5 46.0 47.0 51.0
Casing Material Galvanised steel plate
Fan Air flow rate - 50Hz Cooling At high fan speed m³/min 8.7 9.0 9.5 15.0 15.2 21.0 23.0 32.0 36.0 39.0
Heating At high fan speed m³/min 8.7 9.0 9.5 15.0 15.2 21.0 23.0 32.0 36.0 39.0
External static Factory set/High Pa 30/150 40/150 50/150
pressure - 50Hz
Air filter Type Resin net
Sound power level Cooling At high fan speed dBA 54 55 60 59 61 64
Sound pressure level Cooling Low/Medium./High dBA 25.0/28.0/29.5 25.0/28.0/30.0 26.0/29.0/31.0 29.0/32.0/35.0 27.0/30.0/33.0 29.0/32.0/35.0 31.0/34.0/36.0 33.0/36.0/39.0 34.0/38.0/41.5
Heating Low/Medium/High dBA 26.0/29.0/31.5 26.0/29.0/32.0 27.0/30.0/33.0 29.0/34.0/37.0 28.0/32.0/35.0 30.0/34.0/37.0 31.0/34.0/37.0 33.0/37.0/40.0 34.0/38.5/42.0
Refrigerant Type/GWP R-32 / 675
Piping connections Liquid OD mm 6.35 9.52
Gas OD mm 9.52 12.7 15.9
Drain VP20 (I.D. 20/O.D. 26), drain height 625 mm
Power supply Phase/Frequency/Voltage Hz/V 1~/50/60/220-240/220
Current - 50Hz Maximum fuse amps (MFA) A 6
Control systems Infrared remote control BRC4C65 (1)
Wired remote control BRC1H52W/S/K
(1) Must be combined with Madoka wired remote controller.
18
NEW FXAA-A
BRC1H52W BRP069C51
Indoor unit FXAA 15A 20A 25A 32A 40A 50A 63A
Cooling capacity Total capacity At high fan speed kW 1.7 2.2 2.8 3.6 4.5 5.6 7.1
Heating capacity Total capacity At high fan speed kW 1.9 2.5 3.2 4.0 5.0 6.3 8.0
Power input - 50Hz Cooling At high fan speed kW 0.017 0.019 0.028 0.030 0.025 0.033 0.050
Heating At high fan speed kW 0.025 0.029 0.034 0.035 0.030 0.039 0.060
Dimensions Unit HeightxWidthxDepth mm 290x795x266 290x1,050x269
Weight Unit kg 15 18.5
Fan Air flow rate - 50Hz Cooling Low/High m³/min 6.5/7.1 6.5/7.9 6.5/8.3 6.5/9.4 9.8/12.2 10.9/14.2 12.9/18.2
fan speed
Air filter Type Washable resin net
Sound power level Cooling At high fan speed dBA 51.0 52.0 53.0 55.0 58.0 63.0
Sound pressure level Cooling Low/Medium/High dBA 28.5/30.5/32.0 28.5/31.0/33.0 28.5/32.0/35.0 28.5/33.0/37.5 33.5/35.5/37.0 35.5/38.5/41.0 38.5/42.5/46.5
Heating Low/Medium/High dBA 28.5/31.0/33.0 28.5/31.5/34.0 28.5/32.5/36.0 28.5/33.5/38.5 33.5/36.0/38.0 35.5/39.0/42.0 38.5/43.0/47.0
Refrigerant Type/GWP R-32 / 675
Piping connections Liquid OD mm 6.35
Gas OD mm 9.52 12.7
Drain VP13 (I.D. 15/O.D. 18)
Power supply Phase/Frequency/Voltage Hz/V 1~/50/220-240
Current - 50Hz Maximum fuse amps (MFA) A 6
Control systems Infrared remote control BRC7EA630 (1)
Wired remote control BRC1H52W/S/K
(1) Must be combined with Madoka wired remote controller. | Contains fluorinated greenhouse gases
19
Options & accessories -
Outdoor units VRV S-series
RXYSA-AV1/AY1
Heater tape kit - Optional electrical heater to guarantee trouble-free operation in extremely cold and humid climates EKBPH250D
(one per outdoor unit needed)
DTA104A53/61/62 - For installation into an indoor unit: exact adapter type
External control adapter for outdoor unit - Allows to activate Low Noise Operation and three levels of demand control, limiting power consumption via external dry contacts. depends on type of indoor unit.
Connects to the F1/F2 communication line and requires power supply from an indoor unit, BSVQ box, or VRV-WIII outdoor unit. For 14-20 HP the demand PCB mouting plate is required. See Options &
Adapters
Indoor units Ceiling mounted cassette units Concealed ceiling units (duct units)
Round flow (800x800) 4-way (600x600) Slim
FXFA-A FXZA-A FXDA-A
Standard panels:
Decoration panel (obligatory for cassette units, optional BYCQ140E (white) / BYCQ140EW (full white)(3) / BYCQ140EB (black) BYFQ60C4W1W (white panel) (19) / BYFQ60C4W1S (grey panel)
for others, rear panel for FXLQ) Auto cleaning (5)(6): BYCQ140EGF (white) / BYCQ140EGFB (black) (19) / BYFQ60B3W1 (standard panel) (20)
Designer panels: BYCQ140EP (white) / BYCQ140EPB (black)
Panels
Panel spacer for reducing required installation height KDBQ44B60 (standard panel)
Sealing kit for 3- or 2-directional air discharge KDBHQ56B140 (7) BDBHQ44C60 (white & grey panel)
BRYQ140B (white panels)
Sensor kit BRYQ140BB (black panels) BRYQ140C (white designer panel) R-32 models: BRYQ60A3W (white) / BRYQ60A3S (grey)
BRYQ140CB (black designer panel)
BRC7FA532F (white panels) / BRC7FA532FB (black panels) BRC7F530W (9) (10) (white panel) / BRC7F530S (9) (10)
Individual control systems
Auto cleaning filter see decoration panel 15-32: BAE20A62 / 40-50: BAE20A82 / 63: BAE20A102
sensors
Wiring
K.RSS - External wireless temperature sensor SB.K.RSS_RFC (EKEWTSC-2 + K.RSS) SB.K.RSS_FDA (EKEWTSC-1 + K.RSS) SB.K.RSS_FDA (EKEWTSC-1 + K.RSS)
Adapter with 2 output signals (Compressor / Error, Fan output) KRP1BA58 (2)(7) ERP02A50 (2)
Adapter with 4 output signals (Compressor / Error, Fan,
EKRP1C12 (2)(7) EKRP1C14 (2) ERP02A50
Aux. heater, Humidifier output)
Adapter for centralised external monitoring/control via
KRP4A53 (2)(7) KRP4A53 (2) KRP4A54-9
dry contacts and setpoint control via 0-140Ω
Adapter for external central monitoring/control
KRP2A52 KRP2A53
(controls 1 entire system)
Adapters
Fresh air intake kit (direct installation type) KDDP55C160-1 + KDDP55D160-2 (7)(8) KDDQ44XA60
Air discharge adapter for round duct
(1) Pump station is necessary for this option. (5) To be able to control the BYCQ140EGF(B) the controller BRC1E or BRC1H* is needed.
(2) Installation box is necessary for these adapters. (6) The BYCQ140EGF(B) is not compatible with Multi and Split Non-Inverter Outdoor units.
(3) The BYCQ140EW has white insulation. Be informed that formation of dirt on white insulation is (7) Option not available in combination with BYCQ140EGF(B).
visibly stronger and that it is consequently not advised to install the BYCQ140EW decoration panel in (8) Both parts of the fresh air intake are needed for each unit.
environments exposed to concentrations of dirt. (9) Cannot be combined with sensor kit.
(4) Not recommended because of the limitation of the functions. (10) Independently controllable flaps function not available .
20
Concealed ceiling units (duct units) Wall mounted units
Medium ESP
FXSA15-32A FXSA40-50A FXSA63-80A FXSA100-125A FXSA140A FXAA-A
• • • • • •
• (mandatory for R-32) • (mandatory for R-32) • (mandatory for R-32) • (mandatory for R-32) • (mandatory for R-32) • (mandatory for R-32)
• • • • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
• • • • •
• • • • •
• • • • •
• • • • •
• • • • • •
• • • • • •
• • • • • •
• • • • •
• • • • • •
• • • • • •
(11) Only possible in combination with BRC1H* / BRC1E*. (16) Up to 2 adaptor PCBs can be installed per installation box.
(12) When fixing box is required, use KJB212A, KJB311A or KJB411A depending on the size of (17) Only one installation box can be installed per indoor unit.
the controller. (18) VRV R-32 indoor units cannot be connected to this controller.
(13) Option KEK26-1A (noise filter) is required when installing DCS301B51. (19) The BYFQ60C4* R-32 panels can be connected to R-410A indoor units with wire harness EKRS22.
(14) Wire harnass EKEWTSC is necessary. (20) Wire harness EKRS23 is necessary.
(15) The active airflow circulation function is not available for this controller.
21
Technical drawings
Outdoor units
RXYSA-AV1/AY1 23
FXFA-A 27
FXZA-A 29
FXDA-A 30
FXSA-A 32
FXAA-A 35
22
RXYSA-AV1/AY1
171 758 171
30
(480~490)
485
460
55
36
41
30
4 holes for anchor bolts 101
M12
4 3
40 1100
7
7 51 45
6
869
6
5
5
325
45
45
190
95
95
95
175
26
90 25 25 90 12 99
53
70
53
70
53
150 150
8
71 17
17
6
50
109 7 Knockout hole.
289 163 163 163 8 Drain outlet
RZA-D
250 250
Wall
*
For optimal serviceability, provide ≥·250·mm of free space.
For more installation and service space guidelines, see drawing ·3D069554·.
3D1209
23
RXYSA-AV1/AY1
RXYSA-AV1
RXYSA-AY1
Single unit ( ) | Single row of units ( )
Suction side
In the illustration below, the service space at the suction side is based on 35°C DB and cooling
operation. Foresee more space in the following cases:
- When the suction side temperature regularly exceeds this temperature.
- When the heat load of the outdoor units is expected to regularly exceed the maximum operating
capacity.
Discharge side
Take refrigerant piping work into account when positioning the units. If your lay
out does not match with any of the layouts below, contact your dealer.
eB A,B,C
B,E
-
-
≥ 100(1) ≥ 100
≥ 100
≥ 100
≥ 1000 ≤500
eD A,B,C,E - ≥ 150(1) ≥ 150 ≥ 150 ≥ 1000 ≤500
D - ≥ 500
E e D,E - ≥ 500 ≥ 1000 ≤500
Hd>Hu ≥ 100 ≥ 500
C B H B,D
Hd≤Hu ≥ 100 ≥ 500
HD c HU B
Hb≤½Hu ≥ 250 ≥ 750 ≥ 1000 ≤500
b Hd>Hu ½Hu>Hb≤Hu ≥ 250 ≥ 1000 ≥ 1000 ≤500
D d a A B,D,E Hb>Hu
1
Hd≤½Hu ≥ 100 ≥ 1000 ≥ 1000 ≤500
Hd≤Hu ½Hu<Hd≤Hu ≥ 200 ≥ 1000 ≥ 1000 ≤500
Hd>Hu
eB A,B,C - ≥ 200(1) ≥ 300 ≥ 1000
A,B,C,E - ≥ 200(1) ≥ 300 ≥ 1000 ≥ 1000 ≤500
eD D - ≥ 1000
E e
D,E -
Hd>Hu ≥ 300
≥ 1000
≥ 1000
≥ 1000 ≤500
C B,D
Hd≤Hu
Hd≤½Hu ≥ 250 ≥ 1500
c HU ≥100(1)
B
½Hu<Hd≤Hu
Hb≤½Hu
≥ 300
≥ 300
≥ 1500
PATTERN 1
≥ 1000 ≥ 1000 ≤500
≥100(1) HB ≥ 300 ≥ 1250 ≥ 1000 ≤500
HD b B,D,E
Hd>Hu ½Hu<Hb≤Hu
Hb>Hu
D d Hd≤½Hu ≥ 250 ≥ 1500 ≥ 1000 ≤500
1+2
a A Hd≤Hu ½Hu<Hd≤Hu
Hd>Hu
≥ 300 ≥ 1500 ≥ 1000 ≤500
24
1D128513
RXYSA-AV1/AY1
RXYSA-AV1
RXYSA-AY1
Multiple rows of units ( )
≥100(1)
≥100(1)
≥100 H
B
b
≥100(1)
≥2000
≥100(1)
≥3000
≥100(1)
≥200
≥100(1)
≥1000
H
U ≥ 600
≥1500
Hb Hu b (mm)
Hb≤½Hu b≥250
½Hu<Hb≤Hu b≥ 300
Hb>Hu
1D128513
25
RXYSA-AV1/AY1
RXYSA-AV1
RXYSA-AY1
Stacked units (max.2 levels) ( )
A1
≥100(1)
A2 ≥100(1)
≥500
A2
≥500
≥1000
≥300
B2
B1
≥100(1)
B2
≥100(1)
≥100(1)
B2
≥100(1)
≥1000
≥300
1D128513
26
FXFA-A WITH STANDARD PANEL
FXFQ-B
Notes
1. Location of nameplate
The unit nameplate is located on the control box cover.
The decoration panel nameplate is located on the piping-side panel frame, under the corner cover.
2. When installing optional accessories, refer to their respective documentation.
3. Make sure the distance between the ceiling and the cassette does not exceed ·35·mm.
The maximum ceiling opening is ·910·mm.
4. When the conditions in the ceiling exceed 30°C ambient temperature and 80% relative humidity, or when fresh air is inducted into the ceiling, additional insulation is required (polyethylene foam, thickness ≥·10·mm)
5. When installing a sensor kit, there will be a sensor on this location. For details, see the drawing of the sensor kit.
6. When installing a wireless controller, there will be a receiver on this location. For details, see the drawing of the wireless controller.
·300· or less 7 6
See note ·5·.
420
8
Drain side
DETAIL A DETAIL A
·2· places ·2· places
Opposite side Opposite side
80
80
860-910
950
780
100
100
25.4
25.4
213
Ceiling opening
121.5
121.5
350
350
100
100
Ø75
10
80
80
95
420 AB Piping side
See note ·6·. FCAG100/125/140BVEB
710
Suspension position
950
FCAHG71/100/125/140HVEB FCAG35/50/60/71BVEB
860-910 840
FXFQ80/100/125BVEB FXFQ20/25/32/40/50/63BVEB
Ceiling opening See note ·3·.
DETAIL B
Adjustable
55 840 55
340 DETAIL B
4 1 2 ·2· places ·2· places
3
0-675
Opposite
350
side Opposite side
2D121655
130
350
C
Required installation space
121.5 121.5
AA
175
150
10
110
95
53
67
B
·2700· or more
40
96.5
See note ·3·. 5 See note ·3·. 4 - M8 OR M10 330
81 100 100 85
Suspension bolt
FCAG100/125/140BVEB FCAG35/50/60/71BVEB
ARROW VIEW C FCAHG71/100/125/140HVEB FXFQ20/25/32/40/50/63BVEB
FXFQ80/100/125BVEB
Item Name
Respect the distances shown on the figure. ·1500· or more 1 Liquid pipe connection port
Ceiling-mounted lighting Air fan ·200· or more 2 Gas pipe connection port
Other unit
3 Drain pipe connection
·1500· or more ·1500· or more
4 Power supply wiring intake
·200· or more 5 Transmission wiring intake hole
·1500· or more
·1500· or more 6 Air discharge outlet
·2000· or more
·4000· or more
Required installation space 7 Air suction grille
8 Corner decoration cover
If a discharge outlet is closed up with the "sealin g member" option kit, then the required
installation space on that (closed up) side is ·500·mm instead of ·1500·mm. 9 Drain hose
10 Knockout hole. 2D121655
DETAIL A DETAIL A
See note ·3·.
Suspension position
·2· places
9 A ·2· placesDETAIL A DETAIL A
Suspension position
9 ·2· places
Opposite side
A Opposite side
·2· places 67 96.5
860-910
53Opposite side
950
54.554.5 96.5
780
53
950
54.554.5 96.5
780
213
80
80
Ceiling opening
213
100 80
80
Ceiling opening
Ø75
350 25.4
100
350 25.4
100
121.5
121.5
350
75
350
25.4
100
25.4
10 Ø
121.5
121.5
100
100
10
100
100
420 AB
80
Piping side
80
710 AB
420 950
80
710 95
860-910position
Suspension 950
DETAIL B
Adjustable
840
0-675
55 840
Ceiling opening See note55
·3·. 4 1 2 FCAG100/125/140BVEB
FXFQ80/100/125BVEB FCAG35/50/60/71BVEB
3 340 ·2· places
Opposite side FCAHG71/100/125/140HVEB FXFQ20/25/32/40/50/63BVEB
0-675
55 840 55
210
4 1 2 FXFQ80/100/125BVEB
3 350
Opposite
121.5 side
210
Required installation space
350
AA
255
121.5
Required installation space
54.5
AA
190 230
255
190
95
B
96.5 54.5
90
54.5
C
230
·2700· or more
95
B
96.5 54.5
90
35 5
·2700· or more
35 330
Suspension bolt 280 81 100 100 85
See note
35 ·3·. See note ·3·. 4 - M8 OR M10
40
5 35
See note ·3·. See note ·3·.
ARROW VIEW C 330
Suspension bolt FCAG100/125/140BVEB
·1500· or more
ARROW VIEW C FCAHG71/100/125/140HVEB
FCAG100/125/140BVEB
FXFQ80/100/125BVEB
·200· or more ·1500· or more FCAHG71/100/125/140HVEB
FXFQ80/100/125BVEB
·200· or more
·1500· or more ·1500· or more
Ceiling-mounted lighting
Air fan Other unit
Ceiling-mounted lighting ·1500· or more
·200· or more
·1500· or more DETAIL B Item Name
Air fan Other unit
·200· or more
·1500· or more DETAIL B
·2· places 1 Item Name
Liquid pipe connection port
(*2) (*3) (*1) ·1500· orspace
more Opposite side
·2· places 2
Required installation 1Gas pipe connection
Liquid port port
pipe connection
(*2) 256 (*3) (*1) If a discharge outlet is closed up with the "sealing member" option kit, then the required 350
Opposite side 3
Required installation space 121.5 2DrainGas
pipepipe
connection
connection port
256 ·1500· or more installation space on that (closed up) side is ·500·mm instead of ·1500·mm. 350 4 Power supply wiring intake
If a discharge outlet is closed up with the "sealing member" option kit, then the required 3 Drain pipe connection
·2000· or more Dust(closed
opening 121.5 5
7
·1500· or more installation space on that up) side is ·500·mm instead of ·1500·mm. 4Transmission wiringwiring
Power supply intakeintake
hole
·4000·
·2000· or more
or more Dust opening 6 5Air discharge outletwiring intake hole
53
96.5 67
53 7
Transmission
10° 10° 7 6Air suction grille outlet
Air discharge
·4000· or more
96.5 67
81 100 100 85 8
10° 10° 7Corner
Airdecoration cover
suction grille
Piping 81 100 100 85 9 8DrainCorner
hose decoration cover
Piping 10 9Knockout hole.
Drain hose
Piping FCAG35/50/60/71BVEB
(*1)Not applicable to recessed lighting. Piping FXFQ20/25/32/40/50/63BVEB 10 Knockout hole.
FCAG35/50/60/71BVEB
(*2)Required
(*3)Make
space for entering
(*1)Not applicable
sure the decoration
withlighting.
to recessed vacuum cleaner tube.
panel discharge outlet is not tube.
blocked. Air suction grille FXFQ20/25/32/40/50/63BVEB 2D121658
(*2)Required space for entering with vacuum cleaner
(*3)Make sure the decoration panel discharge outlet is not blocked. Installation direction
Air suction grille 2D121658
Installation direction
27
FXFA-A WITH DESIGNER PANEL
FXFQ-B
Notes
1. Location of nameplate
The unit nameplate is located on the control box cover.
The decoration panel nameplate is located on the piping-side panel frame, under the corner cover.
2. When installing optional accessories, refer to thei r respective documentation.
3. Make sure the distance between the ceiling and the cassette does not exceed ·35·mm.
The maximum ceiling opening is ·910·mm.
4. When the conditions in the ceiling exceed 30°C ambient temperature and 80% relative humidity, or when fresh air is inducted into the ceiling, additional insulation is required (polyethylene foam, thickness ≥·10·mm).
5. When installing a sensor kit, there will be a sensor on this location. For details, see the drawing of the sensor kit.
6. When installing a wireless controller, there will be a receiver on this location. For details, see the drawing of the wireless controller.
·300· or less 7 6
See note ·5·. 8
420 Drain side
DETAIL A DETAIL A
·2· places ·2· places
Opposite side Opposite side
860-910
80
80
950
780
25.4
100
25.4
100
213
Ceiling opening
121.5
121.5
350
350
100
100
Ø75
10
80
80
95
420 AB
Piping side FCAG35/50/60/71BVEB
710 See note ·6·. 950 FCAG100/125/140BVEB FXFQ20/25/32/40/50/63BVEB
Suspension position FCAHG71/100/125/140HVEB
860-910 FXFQ80/100/125BVEB
See note ·3·. 840
Ceiling opening DETAIL B
Adjustable
350 350
C
Required installation space
121.5 121.5
AA
52
217
152
192
96.5 54.554.5
95
53
67
·2700· or more
96.5
5 81 100 100 85
4 - M8 ORM10 330
See note ·3·. See note ·3·. Suspension bolt
FCAG100/125/140BVEB FCAG35/50/60/71BVEB
ARROW VIEW C FCAHG71/100/125/140HVEB FXFQ20/25/32/40/50/63BVEB
FXFQ80/100/125BVEB
Item Name
Respect the distances shown on the figure. ·1500· or more 1 Liquid pipe connection port
Ceiling-mounted lighting ·200· or more 2 Gas pipe connection port
Air fan Other unit
3 Drain pipe connection
·1500· or more ·1500· or more 4 Power supply wiring intake
5 Transmission wiring intake hole
·1500· or more ·200· or more 6 Air discharge outlet
·1500· or more 7 Flat grille assembly
·2000· or more
Corner decoration cover
Required installation space
8
·4000· or more
9 Drain hose
10 Knockout hole.
If a discharge outlet is closed up with the "sealing member" option kit, then the required
installation space on that (closed up) side is ·500·mm instead of ·1500·mm.
2D121703
140
Static pressure in chamber [Pa]
130
120
840
110
100
328
90
427
80
70
See note ·3·.
Drain side 60
50
40
30
448 Duct View ·A· 20
Service access panel (1000) 10
508 Right side ·450 x 450 mm· or more
Ø148
0 2 1 4 5 3 6
See note ·1·. Air flow rate [m³/min]
AA
275
165
725
A Inlet
AB
317
207
Notes
455
Suction chamber
1. When installing a fresh air intake kit, provide a service access panel. Designer decoration panel
2. Field construction Ceiling opening
3. This corner discharge outlet needs to be closed.
4. When installing a duct fan, use a wiring adapter to link the duct fan to the fan of the indoor unit.
5. The intake air flow rate is recommended to be ≤20% of the air flow rate at high fan speed.
If the intake air flow rate is too large, the operating sound may increase, and the detection of the indoor unit suction temperature may be affected.
6. This indicates the distance between the T-joint inlet and the indoor unit inlet when the T-tube is connected.
3D121741
28
FXZA-A
FXZQ-A
Decoration panel
585-595 (Ceiling opening space)
BYFQ60C2W1W Fresh white N9.5
BYFQ60C2W1S Daikin Silver 300 or less 533 (Suspension position)
B Arrow view
Drain connection side
• Required space
A Arrow view Note) 2. 1500 mm or more
1500 mm or more
1500 mm or more
1500 mm or more
is 200mm or more
C Arrow view
300 mm or more
2 Gas piping connection ø 12.7 Flare connection
3 Drain piping connection VP20 (O.D. ø 26)
4 Power supply connection
5 Remote control code and
wiring connection
6 Air discharge grille
1500 mm or more
10 or less
Suspension bolt 8 Drain hose (accessory) I.D. ø 25 Outlet
Required space
Note ) 4.
Notes:
FXZA-A
Decoration panel
585-660 (Ceiling opening space)
4-M4 Hole
Outdoor air intake
(direct connection)
B Arrow view
1500 mm or more
1500 mm or more
1500 mm or more
is 200mm or more
45 or less 45 or less
Required space
Notes:
29
FXDA10-32A
FXDQ15-32A
300 or more 300 or more
(Service space of (Service space)
installation box for
adapter PCB)
240 or more
20 or more
400 or more
(In case of
bottom-suction)
20 or more
Ceiling
Service space
16x ø 4,7 holes
View A
(Suspension bolt pitch) 300 or more Inspection door (ceiling opening)
Adjustable (0-600)
Suspension bolt
16xM5 holes
14xM4 holes
Notes:
1 Liquid pipe connection ø 6.4 Flare connection
2 Gas pipe connection ø 12.7 Flare connection 1. In case of back-suction, mount chamber cover to
3 Drain pipe connection VP20 (O.D. ø 26, I.D. ø 20)
4 Drain hose (accesory) ID ø 25 (Outlet)
botttom side of the unit.
5 control box In case of bottom-suction, mount chamber cover to
6 Transmisiion wiring connection back side of the unit.
7 Power supply connection
2. Locations of unit`s name plate: control box cover.
8 Suspension bracket
9 Inspection cover 3. Mount the air filter at the suction side. (Use an air filter
16xM5 holes
10 Socket for drain whose dust collecting efficiency is at least 50% in a
11 Air filter (accessory) gravimetric technique). It can not be equipped with air
In case of bottom-suction
filter (accessory) when connecting duct to suction side.
3D081435
FXDA40-50A
FXDQ40-50A
300 or more 300 or more
(Service space of (Service space)
installation box for
20 or more
(In case of
bottom-suction)
20 or more
(Suspension bolt pitch)
Ceiling
Service space
22 x ø 4,7 hole
Adjustable (0-600)
20xM5 holes
18xM4 holes
20xM5 holes
Notes:
1 Liquid pipe connection ø 6.4 Flare connection 1. In case of back-suction, mount chamber cover to
2 Gas pipe connection ø 12.7 Flare connection botttom side of the unit.
3 Drain pipe connection VP20 (O.D. ø 26, I.D. ø 20)
4 Drain hose (accesory) ID ø 25 (Outlet)
In case of bottom-suction, mount chamber cover to
5 control box back side of the unit.
6 Transmission wiring connection 2. Locations of unit`s name plate: control box cover.
7 Power supply connection
8 Suspension bracket
3. Mount the air filter at the suction side. (Use an air filter
In case of bottom-suction 9 Inspection cover whose dust collecting efficiency is at least 50% in a
10 Socket for drain gravimetric technique). It can not be equipped with air
11 Air filter (accessory)
filter (accessory) when connecting duct to suction side.
30 3D081436
FXDA63A
300 or more 300 or more
(Service space of installation box for adapter PCB) (Service space)
400 or more
240 or more
20 or more
(Suspension bolt pitch)
(in case of bottom suction)
20 or more
Ceiling
26 x dia. 4.7 holes
Service space
(Suspension bolt pitch) View A
Inspection door (ceiling opening)
300 or less
24x M5 holes
Adjustable (0~600)
Suspension bolt
4x m8 ~ m10
In case of bottom suction, mount chamber cover to back side of the unit.
24x M5 holes
It can not be equipped with air filter (accessory) when connecting duct to suction side
31
FXSQ15-32A
FXSA15-32A
Service space
300 or more
342 40 301
Fresh air intake position KJ KH
KC KE
2x65=130
50
109
100
65
38
140
178
110
210
245
ARROW VIEW A
KK
2x140=280 32
50
126 P.C.D. KF 179.2 50 KD
4-M4 (CLASS 2) 365 500 or more
Service space
504
588 Suspension position 145 150 145
4x65=260
210
KA
95
Suspension position KB
ARROW VIEW A KG
630
FXSA40-50A
XSQ40-50A
Service space
(Knockout hole. ) 25 800
300 or more
492 40
301
2x65=130
38
140
178
245
110
210
ARROW VIEW A
KK
126 P.C.D. 3x140=420 32 KF 179 50
50
KD
515 500 or more
4-M4 (CLASS 2)
Service space 654
4x145=590
738 Suspension position
6x65=390
KA
210
95
KB
Suspension position
ARROW VIEW A KG
630
32
FXSQ63-80A
FXSA63-80A
Service space
792 40
300 or more
301
2x65=130
Fresh air intake position 50 KC KE KH
KJ
109
38
100
65
140
178
110
210
245
ARROW VIEW A
KK
50
126 P.C.D. 5x146=730 32 179 50
KF KD
4 x M4 (CLASS 2) 815 500 or more
Service space
954
1038 Suspension position
6x145=890
11x65=715
210
95
KA
KB
ARROW VIEW A
630Suspension position
KG KG
3D094916A
FXSQ100-125A
FXSA100-125A
Service space
(Knockout hole. )
300 or more
1192 40 301
KC
2x65=130
178
110
210
245
ARROW VIEW A
KK
126 P.C.D. 7x156=1092 32 179 50
50
KF
1215 500 or more KD
4 x M4 (CLASS 2)
Service space
1354
1438 Suspension position 8X150=1200
16x65=1040
226
95
KA
KB KG
KG ARROW VIEW A
630Suspension position
42 150 147.5 147.5 115 115 150 147.5 147.5 115 10x Ø 4.7 HOLE
KK Nameplate / 2. The ceiling depth varies according to the documentation of the specific system. 3D094917A
33
FXSQ140A
FXSA140A
Ø100
(Knockout hole. )
Suspension bolt 1550 69 25 800
Service space
170
300 or more
Fresh air intake position
1342 40
2x65=130
301
50 KC KE
109
KJ KH
62
100
38
65
140
178
245
110
210
ARROW VIEW A
KK
126 P.C.D. 8x156=1248 32
50
KF 179 50 KD
1365 500 or more
4 x M4 (CLASS 2) Service space
1504
9x150=1350
1588 Suspension position
60 18x65=1170 60
210
95
KA
KB
KG ARROW VIEW A KG
630 Suspension position
42 151 123 122 123 116 115 151 123 122 123 116 10x Ø4.7 HOLE
34
FXAA15-32A
FXAQ15-32A
Required space
90 or more
Hole for piping Hole for piping
About 365
Drain hose
About 420
Gas pipe
About 460
Liquid pipe
Required space
Dimensions of fully opened front panel
30 or more
450
2500 or more
Front grille fixing screws 120 or less
Location of nameplate
Front panel
Air outlet
Horizontal blade
Front grille Hole for piping Hole for piping
50 or more 795 50 or more
Knockout hole. Required space Required space
Standard location of holes in the wall
Blade angle 107.6 625 62
14
Up/down (automatic)
Cooling Outer dimensions of the unit
Heating Fan
Dry
Refrigerant filter
4° Hole for embedded piping
12° Hole for embedded piping
19°
16°
27°
55°
25° 42° 0
8
105
50° 64° 80
58°
44
57°
Left/right (manual)
About 290
60 Flexible pipe
About 308 98
44
Flexible pipe
45° ° About 415
45 Gas pipe
Ø 12.7mm CuT
About 460
Liquid pipe
Notes Ø 6.4mm CuT
1) The mark shows the piping direction. About 475
Drain hose VP13
2) Do not place any objects under the indoor unit. In case of high humidity (>80%), clogged drain
outlets, or dirty air filters, condensate may drop out. Inside diameter: 15mm
3D111370
Outside diameter: 18mm
29
FXAQ40-50A
FXAA40-50A
450
Indoor air flow
Location of nameplate
Knockout hole.
269
2500 or more
104 894 52
Up/down (automatic)
Cooling
Heating Fan
Dry Outer dimensions of the unit
4°
12°
Hole for embedded piping
19°
16°
27° 25° 42° Refrigerant filter
0
8
55°
105
50° 64° 80
58°
44
57°
Left/right (manual)
About 290
44
60 Flexible pipe
About 300 98
Hole for embedded piping Flexible pipe
45° ° About 415
45
Gas pipe
Ø 12.7mm CuT
About 460
Liquid pipe
Ø 6.4mm CuT
Notes About 475
Drain hose VP13
1) The mark shows the piping direction.
Inside diameter: 15mm
2) Do not place any objects under the indoor unit. In case of high humidity (>80%), clogged drain outl
ets, or dirty air filters, condensate may drop out. 3D111369
Outside diameter: 18mm
35
FXAA63A
FXAQ63A
Hole for piping Hole for piping
Required space
90 or more
About 365
Drain hose Hole for piping Hole for piping
About 420
Gas pipe
About 460
Liquid pipe
Required space
Dimensions of fully opened front panel
30 or more
Indoor air flow
Location of nameplate Knockout hole
2500 or more
Front grille fixing screws 120 or less
WITH SCREW
36
Definitely the best VRV
we ever made
37
Notes
38
39
Creating
a sustainable
future together
The present publication is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V. Daikin Europe N.V. has
FSC compiled the content of this publication to the best of its knowledge. No express
or implied warranty is given for the completeness, accuracy, reliability or fitness
for particular purpose of its content and the products and services presented
ECPEN20 -210C 01/2021 therein. Specifications are subject to change without prior notice. Daikin Europe
N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest
sense, arising from or related to the use and/or interpretation of this publication.