Substation Grounding & Lightning Protection - Rev6
Substation Grounding & Lightning Protection - Rev6
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
(2013 EDITION)
BY:
1
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
Seminar Objective
Designing an effective substation grounding system is challenging. Many input parameters affect
the outcome of the design. For a grounding system to be safe, it needs to carry the electric
currents into the ground under normal and faulted conditions. Also, it must provide assurance that
a person in the vicinity would not be endangered.
❖This seminar provides necessary background information for substation ground grid design.
❖It will provide a set of guidelines that can be used during design.
❖It will provide design suggestions to rectify the preliminary design if the mesh and step voltages
exceed the tolerable voltages.
❖Finally, a mathematical example will be provided that can be used as a design template.
2
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
3
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
1) For 1 kV nominal voltage and below, grounding and ground systems shall be in accordance
with the IEEE 142 and meet the requirements of ANSI/NFPA 70 (NEC), and ANSI C2. This
includes:
• Residential facilities.
• Recreational facilities.
• Schools.
• Office buildings (including those associated with plants and industrial facilities).
• Swimming pools and fountains including equipotential bonding requirements stated in the
Saudi Building Code and/or NEC Article 680.
2) For substations having equipment operating at a nominal system voltage exceeding 1 kV, a
ground grid meeting the requirements of IEEE 80 for step and touch potential shall be installed.
4
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
5
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
Overview
ML20220247-010
7
Figure 30 – Typical Current Division for a Fault on High Side of Distribution Transformer
7
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
Exposure Conditions
ASSUMPTIONS:
RB = 1000 Ω
R (hand & foot contact = 0 Ω
EFFECT OF MAGNITUDE
OF CURRENT
1 mA = THRESHOLD PERCEPTION
1-6 mA = LET-GO CURRENT
9-25 mA = DIFFICULT TO RELEASE
ENERGIZED OBJECT, DIFFICULTY
OF BREATHING
60-100 mA = STOPPAGE OF HEART
GFCI rating = 4 - 6 mA
per UL 943
8
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
3xR f = 0
Zf = 18 + j60 = (62.642L73.3˚)
X= 60
R= 18
X/R = 3.33333
9
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
TRANSFORMER IMPEDANCE:
B1) OHMIC VALUES
FAULT @ 13 kV SECONDARY:
3xR f = 0
Zf = 0.204 +j3.298 =
(3.304L86.46˚)
X= 3.298
R= 0.204
X/R = 16.167
10
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
11
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
12
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
13
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
Design Parameters
14
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
Design Parameters
(continued)
15
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
16
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
17
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
18
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
19
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
𝑋
𝑇𝑎 = 𝐼𝐹 = 𝐷𝑓 𝑥 𝐼𝑓 (79*)
(2Π𝑓) × 𝑅
Ta = 0.043 DC offset time constant
2𝑡𝑓
𝑇𝑎 −
𝐷𝑓 = 1 + (1 − 𝑒 𝑇𝑎 ) (84)
𝑡𝑓
2.5 Df = 1.042 Decrement Factor (see Table 10)
2.6 Use = 97Con/1084Tm/Copper, commercial hard-drawn (See Table 2)
2.7 Kf = 7.06 [Material Constant @ Various Temperature ™]
IF = 7.101 kA (asym)
20
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
Akcmil = 35.45
Use 1 mm2 = 1.974 kcmil
Amm2 = 17.96
Select Amm2 = 70 (++) Ground Grid Conductor (see Cable Catalog)
dmm = 10.40 dia
d= 0.010 meter
AAWG =
2/0
Akcmil =
167.69
If = 6814 A
t = 3 seconds
K = 143 for Copper XLPE Insulated (see Table 2B)
A = 95 sq. mm.
21
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
22
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
Table 2B: Values of k for Phase and Neutral Conductors Short-Circuit Ratings
𝐴𝑚𝑚2 = (𝐼𝑓 × √t )÷ k
23
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
24
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
CURREN
− 𝑿
( )
𝑴𝑭𝑴 = 𝟏 + 𝟐𝒆 𝑹
TIME 1.1415
1.9648
DECAYING DC COMPONENT
CURREN
1.009
I F = Df x I f
Parameters:
X/R = 3.33
If
TIME
f = 60
tf tf = 0.5
Cycles = 30
25
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
𝐼𝐹 × 197.4
𝐴𝑘𝑐𝑚𝑖𝑙 =
𝑇𝐶𝐴𝑃 𝐾0 + 𝑇𝑚 (B.3)
√[ ln ]
𝑡𝑐 × α𝑟 × ρ𝑟 𝐾0 + 𝑇𝑎
Akcmil = 69.12
Amm2 = 35.01
d= 0.0067 meter
2.2 Calculate the Short-Circuit Capability of the Selected Ground Grid Conductor
26
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
27
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
ρ − ρ𝑠
𝐾= (B.4)
ρ + ρ𝑠
K= -0.724
ρ
0.09 𝑥 (1 − )
ρ𝑠 (B.5)
𝐶𝑠 = 1 −
2ℎ𝑠 + 0.09
Cs = 0.743
Note:
29
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
(29)
0.116
𝐸 𝑠𝑡𝑒𝑝 50 = 1000 + 6𝐶𝑠 𝑥 ρ𝑆 𝑥
√𝑡𝑠
ES50 = 1992.021 Volt (tolerable step for 50 kg body weight)
0.157
𝐸 𝑠𝑡𝑒𝑝 70 = 1000 + 6𝐶𝑠 𝑥ρ𝑆 𝑥 (B.6)
√𝑡𝑠
ES70 = 2696.097 Volt (tolerable step for 70 kg body weight)
30
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
0.116
𝐸 𝑡𝑜𝑢𝑐ℎ 50 = 1000 + 1.5𝐶𝑠 𝑥ρ𝑆 𝑥 (32)
√𝑡𝑠
ET50 = 621.042 Volt (tolerable touch for 50 kg body weight)
0.157
𝐸 𝑡𝑜𝑢𝑐ℎ 70 = 1000 + 1.5𝐶𝑠 𝑥ρ𝑆 𝑥 (B.7)
√𝑡𝑠
ET70 = 840.548 Volt (tolerable touch for 70 kg body weight)
31
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
3.7 Calculate the Tolerable Metal-to-Metal Touch Voltage for 50 kg Body Weight
116
𝐸 (𝑚𝑚 − 𝑡𝑜𝑢𝑐ℎ 50) = (34)
√𝑡𝑠
EMMT50 = 164.049 Volt (tolerable metal to metal touch for 50 kg body weight)
3.8 Calculate the Tolerable Metal-to-Metal Touch Voltage for 70 kg Body Weight
157
𝐸 (𝑚𝑚 − 𝑡𝑜𝑢𝑐ℎ 70) = (35)
√𝑡𝑠
EMMT70 = 222.032 Volt (tolerable metal to metal touch for 70 kg body weight)
32
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
Given:
4.1 Ly = 70 meter Grid Dimension in y direction
4.2 Lx = 70 meter Grid Dimension in x direction
4.3 Dy = 7 meter Conductor Spacing in y direction
4.4 Dx = 7 meter Conductor Spacing in x direction
4.5 h = 0.5 meter Burial Depth of Conductor
4.6 h0 = 1 meter Grid Reference Depth
4.7 20 ea Number of Ground Rods
4.8 7.5 meter Length of Ground Rods
Calculated Values:
1 1 1
𝑅𝑔 = ρ[ + (1 + )] (B.8)
𝐿𝑇 √20𝐴 1+ℎ√(20÷𝐴)
Rg = 2.753 Ω
Given:
6.1 3Io = 3180 A (Ground Fault Current (3I0) @115KV)
6.2 X/R = 3.33 Current for Ground Potential Rise (GPR)
6.3 Sf = 0.6 Current Division Factor
6.4 f = 60 Hz
6.5 tf = tc = 0.5 sec (Duration of Ground Fault Current)
= 30 Cycle
𝑋
𝑇𝑎 = (79*)
(2Π𝑓) × 𝑅
Ta = 0.009 DC offset time constant
2𝑡𝑓
𝑇𝑎 −
𝐷𝑓 = 1 + (1 − 𝑒 𝑇𝑎 ) (84)
𝑡𝑓
Df = 1.009 Decrement Factor (see Table 10)
34
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
𝑋 2𝑡𝑓
𝑇𝑎 = 𝑇𝑎 −
(2Π𝑓) × 𝑅 𝐷𝑓 = 1 + (1 − 𝑒 𝑇𝑎 )
𝑡𝑓
35
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
𝐼𝐺 = 𝐷𝑓 𝑥 𝑆𝑓 x 3𝐼0 (B.11)
IG = 1925 A
𝐺𝑃𝑅 = 𝐼𝐺 x 𝑅𝑔 (B.12)
versus 70 kg
840.548 Volt Tolerable Touch
Note:
36
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
37
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
2 𝑥 𝐿𝑐 (B.18)
𝑛𝑎 =
𝐿𝑃 11
8.2
𝐿𝑃 (91)
𝑛𝑏 =√( )
4 𝑥 √𝐴
1
0.7𝑥 𝐴
8.3 𝐿𝑥 𝑥 𝐿𝑦 (92)
𝑛𝑐 = [ ] 𝐿𝑥 𝑋 𝐿𝑦
𝐴
Notes:
1 nb =1, for square grid
nc =1, for square, & rectangular grids
𝑛𝑑 = (93)
GRID SHAPE na nb nc nd
2 2
𝐿𝑥 + 𝐿𝑌 SQUARE
RECTANGULAR
L-SHAPE
-
-
-
-
-
1
-
1
1
1
1
1
SQUARE - 1 1 1
1
38
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
8.5
𝑛 = 𝑛𝑎 𝑥 𝑛𝑏 𝑥 𝑛𝑐 𝑥 𝑛𝑑 11 (B.17)
8.6
𝐾ℎ = √(1 + ) 1.225
ℎ0
8.8 2.272 (B.16)
𝐾𝑖 = 0.644 + 0.148 𝑥 𝑛
8.9
𝟏 𝑫𝟐 (𝑫 +𝟐 𝒙 𝒉)𝟐 𝒉 𝑲𝒊𝒊 𝟖
𝑲𝒎 = 𝒙[𝒍𝒏 [ + − ]+ 𝒙 𝒍𝒏[ ]]
𝟐 𝒙𝝅 𝟏𝟔 𝒙 𝒉 𝒙 𝒅 𝟖𝒙𝑫𝒙𝒅 𝟒𝒙𝒅 𝑲𝒉 𝝅(𝟐 𝒙 𝒏−𝟏)
0.764 (B.13) 39
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
ρ(𝐼𝐺 𝑥 𝐾𝑚 𝑥 𝐾𝑖 )
𝐸𝑚 = (B.19)
𝐿𝐶 + 𝐿𝑅
790.696 Volt at corner mesh, Compare with the Tolerable Touch Voltage
versus 70 kg
840.548 Volt Tolerable Touch
Design Note:
40
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
1 1 1 1
1 − 0.5𝑛−2 ]
9.1
𝐾𝑆 = [ + + (B.24)
𝜋 2𝑥ℎ 𝐷+ℎ 𝐷
0.406
𝜌 𝑥𝐼𝐺 𝑥𝐾𝑆 𝑥 𝐾𝑖
𝐸𝑆 = (B.25)
0.75 𝑥 𝐿𝐶 + 0.85 𝑥 𝐿𝑅
553.94 Volt Compare with the Tolerable Step Voltage
versus 70 kg
2696.097 Volt Tolerable Step
Design Note:
Summary of Design
a) Given
400 ohm-m Soil Resistivity
6,814 A (sym) (Ground Fault Current (3I0) @13KV)
16.20 X/R Ratio
0.5 sec (Duration of Ground Fault Current)
1.042 Decrement Factor (see Table 10)
70 (++) Sq. mm Ground Grid Conductor
2,500 ohm-m Resistivity of Surface Layer Material (see Table 7)
0.102 meter Thickness of Surface Material
70 meter Grid Dimension in y direction
70 meter Grid Dimension in x direction
7 meter Conductor Spacing in y direction
7 meter Conductor Spacing in x direction
20 ea Number of Ground Rods
7.5 meter Length of Ground Rods
3,180 A (Ground Fault Current (3I0) @115KV)
3.33 X/R Ratio
0.6 Current Division Factor
0.5 sec (Duration of Shock Current, if no Re-closer then = tc)
1.009 Decrement Factor (see Table 10)
b) Calculated Values
42
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
1 METER SURFACE
Et POTENTIAL
Em PROFILE
E mm
E transferred ≈ GPR
Es
DANGEROUS
SITUATION!
44
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
END
THANK YOU…
45
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
(2020 EDITION)
BY:
JULIUS R. GO
(PEE, ASEAN ENGR)
46
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
Seminar Objective
❖This seminar provides necessary background information for substation lightning protection
design.
❖It will provide a set of guidelines that can be used during design.
❖Finally, a mathematical example will be provided that can be used as a design template.
47
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
49
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
• Obtain the lightning ground flash density from Flash Rate map.
• Obtain the structure coefficients (C2, C3, C4, C5) from NFPA 780 Table-L.5 (a) through
L.5(d).
• Calculate Tolerable Lightning Frequency (Nc) as per NFPA 780.
• Calculate The Equivalent Collective Area (AD) (ECA) using structure dimensions.
• Obtain the structure environmental coefficient (CD) from NFPA 780 Table-L.4.2.
• Calculate the lightning strike frequency (Nd) as per NFPA 780.
• Proceed for selection of the lightning protection system and level of protection.
50
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
The lightning ground flash density expressed in terms of ground strokes per square kilometer per
year may be determined by following formula.
Ng = 0.04 Td 1.25
Ng is the frequency of flashes per km2 per year
Td is the number of thunderstorm days per year (keraunic level)
As per Saudi building code (SBD 802) Section no.44-3.3.2.1, thunderstorm per days can be taken as
25
Ng = 0.04 X (25)1.25
= 2.24
51
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
The tolerable values of the acceptable lightning frequency (NC) shall be calculated by
the following formula from NFPA 780-L.5:
NC = 1.5 x 10-3
C
Where,
C = C2 × C3× C4× C5
The values of C2, C3, C4 and C5 are obtained from table – L.5.1.2 (a) through table
L.5.1.2 (d); 1.5 x 10-3 is an amount selected to represent the acceptable frequency of
property losses.
52
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
53
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
54
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
The equivalent collection area of a building Ae refers to the ground area having the same yearly
direct lightning flash probability as the structure. It is an increased area for the structure that includes
the effect of the height and location of the structure.
55
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
AD = LW + 6H (L + W) + π9H2 = 8,380.2658 m2
Where:
“L” is the building length (m) = 53.25 m
“W” is the building width (m) = 19.5 m
“H” is the building height (m) = 10.15 m
56
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
57
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
Since the structure height not exceeding 23m, then as per NFPA 780 article 4.1.1.1 this structure
shall be protected with class I protection level
58
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
5. CONCLUSION
59
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
60
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
61
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
62
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
63
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
64
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
65
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
66
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
67
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
• The sphere rolls up and over (and is supported by) lightning masts, shield wires,
substation fences, and other grounded metallic objects that can provide lightning
shielding.
68
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
69
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
70
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
75
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
76
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
77
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
78
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
79
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
80
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
81
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
82
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
83
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
84
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
85
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
86
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
87
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
88
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
89
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
90
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
91
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
92
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
Keraunic Map
94
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
95
Institute of Integrated Electrical Engineers of the Philippines, Inc
FOREIGN REGION
EASTERN REGION CHAPTER SAUDI ARABIA
First IIEE Accredited Foreign Chapter (Charter No.62)
END
THANK YOU…