Professional Documents
Culture Documents
Govpub C13
Govpub C13
NBS
Reference
PUBLICATIONS AlllDb E( 70
NBSIR 84-2860
Performance of
Field Hydraulic
One- and Two-Story Residential
Plumbing Systems With
Reduced-Size Vents
Robert S. Wyly
Plumbing Consultant
and
Lawrence S. Galowin
U S. DEPARTMENT OF COMMERCE
National Bureau of Standards
Center for Building Technology
Building Equipment Division
Gaithersburg, MD 20899
May 1984
Sponsored by
Tri Services,
Department of Defense,
and
QC
Department of Housing and Urban Development
100
.U56
NO. 84-2860
1984
NATJONAl BUREAU!
OF STANDARDS •
LIBRARY ,
NBSIR 84-2860
daoo
FIELDHYDRAULIC PERFORMANCE OF
ONE- AND TWO-STORY RESIDENTIAL
no. o
PLUMBING SYSTEMS WITH
REDUCED-SIZE VENTS MM
Robert S. Wyly
Plumbing Consultant
and
Lawrence S. Galowin
May 1984
Sponsored by
Tri Services,
Department of Defense,
and
iii
ACKNOWLEDGMENTS
Robert S. Wyly and Lawrence S. Galowin expanded the initial draft report
prepared by Mary Jane (Orloski) Phillips and consolidated the design criteria
in the appendices from other NBS reports.
The work was first sponsored by the Directorate of Civil Engineering, U.S. Air
Force and later by the Building Research Committee of the Tri Services. A
significant portion of the project costs to obtain field data on water usage
and frequency of fixture operation was borne by the NBS Center for Building
Technology. The preparation of this report was sponsored by the Department of
Housing and Urban Development.
1
Currently Plumbing Consultant.
O
^ Currently Mechanical Engineer, Bureau of Medicine and Surgery, Department of
the Navy.
iv
TABLE OF CONTENTS
Page
ABSTRACT iii
ACKNOWLEDGEMENTS iv
TABLE OF CONTENTS v
LIST OF TABLES . * . ix
LIST OF FIGURES xi
DEFINITIONS xii
1. INTRODUCTION 1
1.2 BACKGROUND 1
2. SIZING OF VENTS 5
4. CONCLUSIONS 37
5. REFERENCES 39
v
2
Page
vi
1
LIST OF TABLES
Page
Table A. 2. 4 Vent Pressure Data for the D/a Unit with Vent Terminal
Closed, W1 + W2 + T2 Discharged A- 1
Table B.2.1 Water Consumption in Occupied Test Unit D/a and Distribution
by Fixture and Outlet (data sample covering a 5 day
period) b-4
vii
LIST OF TABLES (continued)
Page
Table B.2.2 Water Consumption in Occupied Test Unit F/a and Distribution
by Fixture and Outlet (data sample covering a 5 day
period) B-5
Table C.4.1 Drainage Fixture Unit Load Ratings for Various Plumbing
Fixtures . C-l 1
Table C.4.2 Minimum Sizes for Individual and Common Fixture Vents and
for Stack Vents C-12
Table C.4.6 Minimum Sizes and Maximum Lengths for Vent Stacks C-16
viii
LIST OF FIGURES
Page
Figure 10. As-built design. E-house soil, waste, and vent piping,
showing vent sizes obtained from RSV criteria 15
Figure 11. As-built design, F-house soil, waste, and vent piping,
showing vent sizes obtained from RSV criteria 16
ix
LIST OF FIGURES (continued)
Page
Figure B.2.3 Distribution of combined hot and cold water flow rates
in master bath shower. D/a unit (data sample covering a
5 day period) B-10
Figure B.2.4 Distribution of combined hot and cold water flow rates
in common bath shower head. D/a unit (data samples covering
a 5 day period) B-ll
Figure B.2.7 Distribution of combined hot and cold water flow rates in
master bath shower, F/a unit (data sample covering a 5 day
period) B-14
x
LIST OF FIGURES (continued)
Page
xi
DEFINITIONS
In this report, a number of terms are used that require specialized definition
beyond the dictionary meaning of the words. Some terms used are adequately
defined in plumbing codes, but others are used in such a sense as to require
modified definition for the purposes of this report. Therefore, the following
definitions are provided as an aid to understanding.
Blowback - the ejection of suds, air, or other gases through the trap-seal
to the room side of a trap as a result of excessive positive pressure on
the drain side of the trap.
Branch - any part of the piping system other than a main, riser, or stack.
Branch vent - a vent pipe to which two or more fixture vents are connected
and which terminates by connection to a vent stack or a stack vent.
Building drain - that part of the lowest piping of a drainage system which
receives the discharge from soil, waste, and other drainage pipes inside
the walls of the building and conveys it to the building sewer.
Dip of trap - the highest point on the internal vertical cross section of
the trap at the lowest portion of the bend (inverted siphon).
Dry vent - any vent that does not carry water or waterborne wastes.
Fixture vent - a vent that provides the primary ventilation for one or
two traps located in the proximity of the base of the vent.
Flood-level rim - the top edge of a receptacle or fixture bowl from which
water can overflow in the absence of or malfunction of an overflow device
at a lower elevation.
xii
Individual vent - a fixture vent installed to vent a single fixture and so
connected with the vent system or with the open air that free movement of
air is possible at all times.
Reduced size venting (RSV) - a specially designed vent system (or the
procedure for such design) that contains dry vents smaller in size than
allowed by the applicable plumbing code for standard venting.
Stack - general term for the vertical main of the soil, waste, or vent
piping system.
Stack vent - a stack vent is the extension of a soil or waste stack above
the highest connection of a horizontal drain to the stack.
Trap-seal - the vertical distance between the trap weir and the dip of the
trap.
Trap weir (crown weir) - the lowest point in the vertical cross section of
the horizontal waterway at the exit of the trap.
Vent header - a generally horizontal vent that joins together two or more
stack vents and/or vent stacks, and terminates outside the building in the
atmosphere.
Vent stack - a vertical vent pipe extending through two or more stories,
installed to provide circulation of air between elements of the DWV
system. Usually, the vent stack is the vertical main of the vent system,
to which branch vents are connected.
xiii
Vent terminal - that portion of the vent piping extended outside the
building and open to the atmosphere.
xiv
.
1. INTRODUCTION
Laboratory-based criteria [1] were applied to resize the dry vents of two
living units each of three different standard DWV plans (a total of six units).
Sensors, transmission wiring, and a data acquisition system were installed for
the primary purpose of automatically monitoring, subsequent to occupancy:
(1) the hydraulic and pneumatic performance of the DWV system, (2) distribution
of fixture operations, (3) water consumption, and (4) energy used by the water
heaters
Preoccupancy field tests were made in three of the six units, in which trap-
seal reductions for idle traps and pneumatic pressure changes in vents were
measured when selected plumbing fixtures were discharged manually. Figure 1
is an aerial view of the test houses.
1 . 2 BACKGROUND
Before the present study was initiated several reports describing laboratory
investigations of reduced-size venting had been issued [1, 2, 3, 4], and one
field study had been reported [5]. Reduced-size venting was used in one single
family, one-story DWV design used in HUD's Operation Breakthrough Program [6]
apparently with satisfactory results. Those investigations showed the adequacy
of hydraulic and pneumatic performance of selected one- and two-story DWV sys-
tems with reduced-size vents under the conditions described. The principal
explanations offered for the satisfactory performance of those systems not
conforming to traditional vent sizing requirements were:
1
(b) Scientific criteria for the traditional sizing of individual and
common fixture vents and for branch vents could not be identified;
analysis of installation practices and laboratory measurements indi-
cated such vents, at least in one- and two-story systems are capable
of carrying much greater air flow rates that normally occur in service
when sized by plumbing code requirements.
2
might produce the results measured by criteria (a) and (b): the fluctuating
suction or back pressure within the vent system pipe network itself.
In the preoccupancy tests, the general approach was to impose test loads
considered somewhat more severe than would be expected in normal service, and
to measure trap-seal reduction (the complement of trap-seal retention) and
pressure fluctuations in the vents. At the same time, test personnel listened
for noises indicating air flow through idle trap-seals which could indicate
excessive levels of back pressure or suction.
3
Figure 1 . Aerial view of test houses
4
2. SIZING OF VENTS
The traditional code requirements for sizing of stack vents and vent stacks
(main vents) are based on data from laboratory studies with multistory test
systems, applied conservatively [7, 13, 14]. The traditional criteria for
sizing individual, common and branch vents are more or less "rule-of-thumb,"
based on experience with ferrous vent piping materials (commonly used when these
rules were being formulated), which, under some conditions, can be subject to
gradual diameter reduction and increased surface roughness as a result of
corrosion. Also, it is recognized that intermittent discharge of a fixture
may, under some conditions, deposit a layer of particulate matter inside the
lower portion of a vent, further contributing to gradual closing of the vent
over a period of time, regardless of the piping material used.
A review of this information indicated that in many systems dry vents sized
by traditional criteria are considerably larger than would be required to
accomodate the air flow with an acceptable pressure drop. The review suggested
that dry vent size reduction would be appropriate in low-rise systems, partic-
ular one- and two-story residences, and that such reduced-size venting should
be constructed of corrosion-resistant piping.
The essential features of the RSV criteria applied in this study were presented
in an earlier publication [1]. The criteria used were technically similar to
those presently recommended in appendix C using an updated format.
The first step in sizing the vents for the study was to apply the RSV criteria
to the DWV schematics furnished by the sponsor prior to the beginning of con-
struction. Figures 2 through 4 are floor plans showing the plumbing layouts
taken from the original design drawings. Figures 5 through 8 are soil, waste,
and vent piping riser diagrams showing vent sizes as originally specified by
the Air Force and as initially recommended by NBS on the basis of the RSV cri-
teria [1]. Appendix C presents the criteria and a recommended procedure for
applying them.
5
The second step was to make revisions to the initially recommended RSV designs
to provide consistency with modifications to the installations due to onsite
contractor practices or other alterations dictated by field conditions differing
from the assumptions made in producing the initial schematics (see 3.1). The
"as-built" schematics are shown in figures 9 through 11.
6
FLOOR
SECOND
U ]f It u
WH
7
FLOOR
SECOND
o cc
sZ
n co
IThm
co
6
4
SERVICE—
cw
8
SERVICE
1'CW
WH
o V
o \
9
^-3'V.T.R.
Figure 5. Original design, D-house soil, waste, and vent piping, showing
vent size reductions obtainable from RSV criteria
10
CRITERIA
RSV
BY
)
3/4
Figure 6. Original design, E-house soil, waste, and vent piping, showing
vent size reductions obtainable from RSV criteria
11
VTR
<
GC
UJ
H
GC
Hi ^
O CO
O GC
> >-
CO CQ
Figure 7. Original design, F—house soil, waste, and vent piping, showing
vent size reductions obtainable from RSV criteria
12
VTR
CRITERIA
LU
O
o RSV
o
> BY
CD
)
3/4
Figure 8. Modified original design, F-house soil, waste, and vent piping,
showing manifolding of vent terminals and vent size reductions
obtainable from RSV criteria
13
Figure 9. As—built design, D~house soil, waste, and vent piping, showing vent
sizes obtained from RSV criteria
14
Figure 10. As-built design, E-house soil, waste, and vent piping, showing
vent sizes obtained from RSV criteria
15
Figure 11. As-built design, F-house soil, waste, and vent piping, showing vent
sizes obtained from RSV criteria
16
3. INSTALLATION AND TESTING OF RSV SYSTEMS IN THE FIELD
At the outset it was necessary to consider the nature and sequence of project
activities in relation to the construction and occupancy schedules. Some
activities would have to be planned and/or completed before groundbreaking,
others during construction, and still others after completion of construction
but before occupancy of the test housing units. Table 1 shows the guide used
as an aid to the management and monitoring of these activities.
Figure 1 shows the locations of the test units in a family housing development
at Andrews Air Force Base. During the early construction phase, underground
cable was laid connecting each test unit with the DAS central control unit
placed in a closet in the D/a module. In this terminology, e.g.. D/a, the
capital letter refers to the house type and the lower case letter refers to a
particular module as designated in the architectural drawings (see figure 1).
Within each of the test dwelling units, wires were run within the walls between
the measurement points (primary sensors) and a centrally located closet selected
for housing the "satellite” DAS equipment cabinet. The DAS central unit
(recorder and printer), placed in the equipment closet of the D/a module, is
shown in figure 12.
Pressure taps were provided at selected points in the venting systems during
the installation of the DWV systems, and 3/8 in. O.D. diameter copper tubing
was run within the walls and floor-ceiling cavities to the equipment closet in
each test module. These tubes were continuously graded downward from the
highest point to assure moisture drainage. Each equipment cabinet contained,
among other things, three magnetically coupled differential pressure gages
connected to the tubing from the pressure taps.
Flow switches were installed in the individual hot and cold water supply lines
of lavatories, tubs and/or showers, kitchen sink, clothes washer, and in the
cold water supply to the water closets. Water meters were Installed in the
water service pipe and in the cold water branch to the hot water heater of each
instrumented housing unit.
Connections were made to telephone transmission lines from the data acquisition
system on the housing site. The telephone lines could be used to carry data
directly to the NBS site in Gaithersburg, an air distance of approximatly
47 km (29 miles).
17
At the appropriate time during the installation of the rough piping, the
reduced-size vents were installed. Ideally, that would have been done simply
in accordance with the original design schematics as modified for RSV (see
figures 5 through 8). However, some modifications in the planned DWV configu-
rations and sizes were necessitated because of building site conditions, and
because of field changes in the drainage piping systems introduced by the
plumbing contractor, (not an unusual situation). Before preoccupancy testing
was initiated, it was established that the as-built drainage (wet) systems
complied with the appropriate model plumbing code. In making the necessary
design revisions for the reduced-size vents of the as-installed, field test
systems, the sizing criteria were the same as previously applied for the first
modifications to the original design drawings. The "as-built" designs are
shown in figures 9 through 11.
3.3.1 Instrumentation
The project plan called for three types of data: (1) DWV system performance,
(2) water usage (distribution of fixture operations and volume of water used,
by time and fixture), and (3) energy usage (for each water heater). The
instrumentation developed for these measurements is described briefly in
table 2 and figures 12 and 13. See also appendix B.
Water seal depth changes in some of the bathtub or shower traps were measured
in the preoccupancy tests by means of the portable depth-detector probe (figure
12); the traps were also instrumented for post-occupancy automatic data acqui-
sition. Floor drain traps, however, were not instrumented for post-occupancy
automatic data collection because only relatively mild changes in water level
in the traps were expected during normal loading. This was confirmed in the
preoccupancy tests using the portable probe.
The flow switches on the hot and cold water supply lines to the fixtures
together with the two water meters (one in the house service pipe and the other
in the supply pipe to the water heater) provided a means of monitoring the time
distribution of water usage by fixture and the cumulative consumption of water.
18
It was planned that in the post-occupancy tests the data from the flow switches
and the traps would be processed to identify which fixture(s) were operated to
produce a water flow registered by the water meter(s), and to provide data on
the time distribution of the fixture operations.
In the preoccupancy tests, piezometers were utilized to read the water levels
in some of the instrumented traps. Peak vent pressures were observed visually
on the magnetically-coupled gauges for selected tests (see figure 13) while the
data acquisition system was automatically recording the cumulative time outside
the range + 0.25 kPa. Locations of pressure measurement taps are shown
schematically in figures 9 through 11.
The test plan covered four areas: organization of project activities; the
discharge characteristics of the fixtures; a selection of test conditions
(including specific test loads); and definitive test procedures.
Water depths for the waste fixtures (fixtures other than water closets) were
established, a selection of loading patterns was made, certain conditions of
test were selected, and the scope of measurements decided. Tables 4 through 6
and the following discussion describe these areas in greater detail.
The selection of hydraulic test loads for DWV system evaluation has not been
standardized. But preliminary analysis of the piping schematics showed that
specific hydraulic loads should be imposed to test the adequacy of particular
types of vents, and of the vent system as a whole. For example, appropriate
individual fixture discharges would test the fixture vents; simultaneous
discharge of two or more fixtures served by a particular branch vent would test
the branch vent; and generally three or more fixtures discharged simultaneously
would test the main vents and overall venting system. Some tests would be
necessary to evaluate the effect of detergents as used in the clothes washer
and the kitchen sink.
A review was made of several earlier reports on DWV testing. The load selection
guide, shown as table 5, for selecting test loads in the RSV preoccupancy field
study was based on [15] for single-branch interval portions of plumbing systems
and on other general requirements for hydraulic loading. The loads actually used
were considered equal, or greater, in effect than those indicated by table 5.
The effects of the loads used are believed to have been at least as severe as
might have been expected from service loadings imposed by building occupants.
19
combinations so as to produce effects more or less representative of service
conditions.
When the fixtures are distributed on two or three different levels, table 5 may
be used to aid in selecting test loads, using an approach similar to that given
above for back-to-back bathrooms on the same level. If some but not all of the
discharging fixtures are on the lowest level, measurable back pressure may be
produced at this elevation.
After a run was initiated, the peak readings on one or two selected pressure
gauges were observed visually. This information was correlated, where applicable,
with the elapsed time in seconds outside the range of + 0.25 kPa clocked by the
DAS (see figure 13).
Trap-seal elevations were read manually on the piezometers after each run. In
almost all cases, the trap monitor voltage values from the DAS were recorded
after each run (as a convenient means of comparing the changes in water level in
the traps as indicated by the DAS against level changes observed on the trap
piezometers). The traps were not filled between runs, so the value recorded by
the DAS after the fourth run corresponded to the cumulative trap-seal reduction
determined visually from the piezometer, within the limits of resolution of the
depth measurement electrode pins in the traps.
In the D and F houses, tests were first run with the vent terminal open, and
then with it taped shut, in accordance with the plan indicated in table 6. If
the first run produced a trap-seal reduction of more than 25 mm with the ter-
minal closed, the fixtures were refilled after each run. The four values of
trap-seal reduction obtained in this way yielded an average "single-run" dH, as
depicted in figure 14.
In all six of the houses, gate valves were installed in the vent lines of the
floor drain (F6 figures 9, 10, and 11). These were shut before the preoccupancy
20
tests. In the original test plan (see table 6), tests were to be made with the
floor drain vent valve both closed and open. Tests were first run with the
valve closed. Because of the small floor drain trap-seal reductions observed,
the series was not repeated with the valve open. These valves remained closed
after occupancy.
The piezometers used for the preoccupancy tests were removed before occupancy
and the installed DAS system was to monitor the performance.
The data tabulations presented are from the records prepared by visual/manual
readings. The pre-occupancy testing provided opportunity for check-out of
the DAS instruments and automated data compilations. The cumulative times
for pressure excursions in the over range periods were obtained from the DAS.
The precision of the visual/manual instrument readings were less than the
resolution capability of the automated systems; general agreement was found
between the sets of data compared.
The results of the fixture calibrations are given in tables 7 and 8. For the
waste fixtures, the average values were as follows:
For the water closets in the D/a unit (see table 8), the average water
consumption per flush was 14.7 liters (3.9 gal).
3.4.2 Trap-Seal Reduction and Vent Pressure with Vent Terminal Open
The principal and typical results from the tests with the vent terminal open
are summarized in tables 9 and 10. The detailed data are given in appendix A.
In a few instances an apparent rise in temperature level appeared and are noted
by the + readings (e.g., tables A. 1.1, A. 2. 2, A. 2. 3). Such readings may occur
as a result of: positive pressures or fluctuating miniscus and inadequate time
for the system to stabilize prior to the piezometer reading; capability to rend
the miniscus wetting the wall within a limit of 1 mm or a depth probe to
2.5 mm limit (as noted in table 2); combinations of capillary effects with
dirt in the tubing introducing a small error.
21
Results of all the tests with the vent terminal open show that the
reduced-size vents provided satisfactory performance in terms of trap-seal
retention and vent pressure.
The greatest trap-seal reduction in the D house was 10 mm, in the E house 7 mm,
and in the F house 5 mm (tables 9 and A. 1.1). The greatest vent suction was
40 mm WG (E house) and the greatest vent back pressure was 20 mm WG (F house).
See table 10 and section A.l.
The greatest trap-seal reductions in the E house, 7 mm, occurred for discharges
of W1 + W2 + W3 + C5, and for W1 + W2 + LI. Of special interest in the E house
was the shared (party wall) vent serving the first floor half baths (water
closets and lavatories). For a discharge of both these water closets and one
of the lavatories, the greatest seal reduction in the trap of the idle lavatory
was only 2 mm. See table A. 1.1(B).
For the RSV installation in the F house, the largest trap-seal reduction, 5 mm,
occurred for discharges of W1 + W2 + L; W1 + W2 + Tl; and W1 + W2 + K4. See
table A. 1.1(C).
For all tests with the vent terminal open, the largest trap-seal reduction was
10 mm, in a P-trap in the D/a unit (see table A. 1.1). It it is assumed that
the seal depth of the full-trap is 50 mm, then the trap-seal retention is given
by:
This means that P-trap-seal retention was at least 80 percent after four runs
(without filling of traps between runs).
Generally, the idle P-traps exhibited greater trap-seal reductions than the
W.C. traps. This has also been observed in other laboratory studies where idle
P-traps were subjected to transient, fluctuating suction. Probably a major
factor in this phenomenon is the relatively larger mass and inertia of the W.C.
trap, which minimizes the effect of transient pressure fluctuations such as
those associated with suction.
22
the W.C. case because the trap seal volume on the room side is much greater than
the volume on the sewer side of the seal.
Limited measurements relating to vent pressure fluctuations were made. The DAS
could automatically record the cumulative time that the pressure was outside
the preselected range of + 0.25 kPa, the generally accepted design range for
DWV systems. The pressure values observed were within these limits in idle
trap vents for nearly all of the tests with the vent terminal open.
Studies [1,3,10] of the relationship of peak suction in the vent and the
associated trap-seal reduction under normal conditions showed that a 25 mm
cumulative trap-seal reduction occurred only when the peak transient suction in
the vent was on the order of -0.40 kPa. A similar result was found in the pre-
occupancy field test, based on the pressure gauge peak readings observed visu-
ally and the corresponding trap-seal reductions actually measured with the vent
terminal open.
3.4.3 Trap-Seal Reduction and Vent Pressure with Vent Terminal Closed
Data from load tests with vent terminal closed, some of which produced trap-
seal reductions near failure (»25 mm), presented an additional opportunity
to examine, in this critical area of unusually severe conditions, the
relationship between the traditional + 25 mm pressure criterion and the more
meaningful criterion: trap-seal reduction not exceeding 25 mm together with
the absence of adverse back pressure effects. These data are also presented in
detail in appendix A.
The data support the earlier laboratory findings that a repetitive peak suction
of 38 mm (1 1/2 in WG) is roughly comparable to a cumulative P-trap seal reduc-
tion of 25 mm (1 in WG). Also, the trap-seal failures or near-failures observed
in some instances, with closed vent terminals and heavy hydraulic loads, indi-
cate the general desirability of keeping the vent terminals open, although this
may not be essential for every system and is dependent on system configuration
and location of fixtures.
23
Table 1. Organization and Sequence of Activities Relating to PreoCcupancy
Hydraulic Tests
I. BEFORE GROUNDBREAKING
2. Select sensors and decide scope of measurements within each test unit;
design data collection system for post-occupancy measurements; and order
equipment.
7. Verify RSV sizes taking into account wet-piping field changes, and make
modifications as necessary to satisfy (6).
10. Install DAS, connect sensor wires to transmission wires, and connect
pressure tubes to pressure gauges.
11. Check all instruments and the Data Acquisition System for operational
readiness.
24
Table 2. Characteristics of Instruments and Purposes for Which Used
Range or Resolution
Instrument Size of Utilization of System
Instrument
In Preoccupancy Tests
In Post-Occupancy Tests
c This was read visually during manual tests and it is estimated that the
readings made this way would be accurate to within 0.5 cm water gauge.
This is 2-1/2 times the manufacturer's claimed accuracy.
d For a flow duration greater than 5 s. Water meter resolution 1/350 gal; with
counter card 0.1 gal.
25
Table 3. Symbols for Fixtures
a The D house had a shower stall in the master bathroom instead of a bathtub.
b A clothes washer was not furnished with these units, although laundry piping
was installed in the units. A clothes washer used in earlier NBS laboratory
tests was taken to each house in turn for the preoccupancy tests.
26
Table 4. Water Level in Waste Fixtures for Discharge Rate Measurements
27
Table 5. Guide for Selecting Test Loads for Residential Plumbing Systems
Number of Fixtures
Served by System
or Component Being Maximum Reasonable Number of Concurrently
Tested Operating Fixtures to Comprise Test Load
1 1
2-5 2*
6-12 3
13-32 4
For a two fixture system or component, also discharge each fixture individually.
28
Table 6. Plan for Testing Sequence and Certain Test Conditions in Preoccupancy
Hydraulic Tests
Status of Use of
Gate Valve Status of Detergent
in Floor Vent Terminal as an
Drain Vent Additive
29
1 s
30
Table 8. Water Closet Water Consumption Measured in D/a Unit
31
Table 9. Summary of Findings on Trap-Seal Reductions D, E, and F Houses with
Vent Terminals Open
B. Trap-seal reduction after four runs for two different leads in the E/e
unit
32
)
Pressure Tap
Fixtures Discharged 1 Location 2 and Peak Pressure
Vent Size Excursions
D/a Unit Tests
W1 + W2 + W3 + W5 S1U/2") -2 cm W.G.
(199 Pa)
+1/2 cm W.G.
W1 + W2 + W3 + W5 W3(3/4" -1.5 cm W.G.
(149 Pa)
+1 cm W.G.
(96 Pa)
E/e Unit Tests
Wl + W2 + W3 K4( 1/2") -2 cm W.G.
(199 Pa)
+0
W3(e) + W3(f) + L3(f) L3(e,f) -1/2 cm W.G.
and (50 Pa)
W3 (e,f
(1 1/4") +0
F/b Unit Tests
W1 + W2 + L2 LI (3/4") -1 cm W.G.
(100 Pa)
K4(a) + K4(b) K4(a,b) -3 cm W.G.
(1") (299 Pa)
+0
W1 + W2 + K4(b) C5 (1/2") -1 cm W.G.
(100 Pa.)
+2 cm W.G.
(199 Pa)
1
See section A.l for additional data.
2 Lower case letters in parenthesis indicate the applicable modules where party
wall DWV piping existed.
33
m
34
PRESSURE
MAGNETICALLY-COUPLED
PRESSURE SWITCH-GAGE
35
CUMULATIVE dH
(Reading after final run)
tsU
Run 1 Run 2
^ ^
Run 3 Run 4
*Hh
36
4. CONCLUSIONS
4.1 ADEQUACY OF PERFORMANCE OF THE RSV SYSTEMS AT ANDREWS AIR FORCE BASE AND
ADEQUACY OF THE RSV CRITERIA
1. The data show the adequacy of performance of properly designed and installed
RSV systems for one- and two-story residential designs connected to a
standard drainage system, conforming to the criteria presented in
appendix C.
3. The data support the elimination of requirements for floor drain vents in
one- and two-story residential housing designs at typical building sites.
Some current codes recognize that such vents may be omitted under specified
conditions.
Published results from studies on the economics of RSV are limited [8]. A
review of such information available to the investigation described herein
indicated potential savings ranging up to about $150 per dwelling unit,
expressed in 1975 dollars. In many situations, RSV does in fact offer signi-
ficant potential for savings. The actual extent of savings in a given situa-
tion depends on a number of factors.
Among lingering issues are: (a) what is the impact of frost closure of vent
terminals, and (b) are reduced-size dry vents really subject to a signifi-
cantly greater risk of blockage than are standard size vents? If so, can
opening the vents be satisfactorily accomplished through simple maintenance
procedures?
37
heat transfer in roof vents is needed as a guide for the design of roof vents
in very cold regions. Probably only a very small proportion of the U.S. would
require special precautions.
38
,
5. REFERENCES
[2] Minimum Venting for Plumbing Systems . National Bureau of Standards Tech.
News Bulletin, May 1966.
[6] Guide Criteria for the Evaluation and Design of Operational Breakthrough
Housing Systems . Report 10-200, 4 volumes, National Bureau of Standards,
September 1970.
[9] Performance Concepts for Water Supply and Drainage Systems in Buildings .
39
[12] The Evolution of the Performance Approach in Plumbing , Proceedings of
the First NBS/NCSBCS Joint Conference on Research and Innovation in the
Building Regulatory Process, Providence, R. I. September 1976. R. S.
,
Wyly, et al.
[16] Frost Closure of Roof Vents . National Bureau of Standards BMS 142, 1954.
H. N. Eaton and R. S. Wyly.
[17] Reduced Size Venting Design . ASPE Data Book, Vol. I, Sec. II, Chapter 1,
Sanitary Drainage Systems, American Society of Plumbing Engineers, 1980.
40
.
Tests with the vent terminal open were described and the findings summarized in
section 3.3.1. Detailed data on trap-seal reductions are presented in table
A. 1 . 1
With the vent terminal open, the greatest trap-seal reductions of the idle traps
after four runs with the most severe loads (see tables A. 1.1 (a), A. 1.1(b) and
A. 1.1(c)) were:
Greatest Reduction
Unit Tested
Load Trap AH
mm
D/a Wl + W2 + LI t2 10
Wl + W2 + W3 T2 10
W1 + W2 + W3 + C5 t2 10
Wl + W2 + W3 + C5 + DET t2 10
E/e Wl + W2 + LI t2 5
F/b W1 + W2 + LI t2 5
W1 + W2 + T1 t2 5
a The designation DET means that detergent was used in the indicated
detergent-using fixture.
The greatest vent pressure fluctuations measured in the tests with the
vent terminal open (see table 13) were:
A-l
2
1" -40
E/e Li ,2 ; W1 + W2 + W3
Although one test load in the E/e unit produced an instantaneous peak suction
of 40 mm, the greatest trap-seal reduction shown for this load was only 10 mm.
In other studies, it has been found that with a repeated application of suction
to an idle trap-seal, a 25 mm cumulative trap-seal reduction may be expected
from a fluctuating, transient suction level of about 40 mm WG [1,3,10].
Therefore, the data with the vent terminal open show entirely satisfactory
trap-seal performance, with a safety factor of at least 2.5. Although two
loadings produced vent suction levels somewhat exceeding the generally accepted
level of 25 mm WG, this is not considered significant since no corresponding
excessive trap-seal reductions occurred.
Tests with the vent terminal closed were described briefly in section 3.3.3.
The data on trap-seal reductions and vent pressures with closed terminal are
presented in tables A. 2.1, A. 2. 2, A. 2. 3, and A. 2. 4.
Analysis of the pattern of trap-seal failure associated with data presented for
the D/a unit with vent terminal closed (see table A. 2. 3) has been aided by the
construction of figure A.2.1. Twelve replicate tests were made, each test
consisting of four runs without replenishment of water in the idle trap-seals
between runs. From figure A.2.1 it is apparent that some traps were more
subject to failure than others, that there was a variance in results from test
to test, and that the cumulative number of failed traps increased with the
number of runs made. In considering these data, it should be remembered that
the vent terminal was completely closed, and the load was a severe one. In
addition, the likelihood of four successive replicate runs with the same loading
seems very remote under service conditions. Therefore, it seems that if under
service conditions the vent terminal should become fully closed, most of the
traps would be replenished after the first "run" of a particular loading,
because of the probable random composition of successive loadings. Therefore,
it might be expected that representative results would more nearly resemble
those after run 1 than after run 4. Under this condition, there was only one
A-
3
trap failure, L2. This occurred only once in 12 replicate tests (see table
and the failure was very marginal (27 mm vs 25 mm).
A. 2. 3), The average trap-
seal reduction (in 12 tests) for trap L2 after the first run was 17.5 mm, a
value appreciably less than the generally accepted 25 mm.
A-
4 l < 4
cn g o o Q o < C < < < < < < < < < <
3 B
04 g CM *3- < < < o CM < < < < < < < < < <
3 B
GO
c
3 «=H 2 o o < c »=*4 *-=<
< < < < < < < < < <
M 3 s
U
3
O o o m m m o o o o o O o o m o •
m•
2 • • . . • • • • • . . . • •
Open
14-4 VsO
§ o o 04 CM CM o o 1
o m m o m m CM m CM
u
<D
u
U-t o o o O• m• m m m• o o o o o o O o O•
fH 2 • • « • • • • • • . • • •
03 g o m m m o* CM 04 p* M3 m m cn m m m f— cn
a
Terminal
c
o
•H (3
4-1 2 c < •< < m -S' CM iO ao vO M3 m o r»*
O j g —4
3
~a
Vent
0)
a 04 g • •
m
.
m
•
m
•
m
• • • . •
m
•
m
• •
m m
ca
u
H B o CM o o
H r*. o o
1—4
4-4
Reduction
a)
i—t o < Ol CM < cn cn cn -3- m cn -3- cn CM sf >3 cn
M3
"O |
(discharging)
Trap-Seal
3 |
sr
fa
g
1
o o CM cn m cn cn o <3- m >3" < m -3- M3 m <
active
1.1 H H
fa fa
Q Q
an
A. + +
m m m m <r
Table
CJ o fa u u fa
+ + + + + +
cn 0) indicates
W cn cn cn cn cn cn cn cn cn cn
<u
u u 3 3 3 3 3 3 3 3 3 3 3
3
JZ
4-> + + + + + + + + + + + +
X O
t4 CD CM CM CM
a CM Ol CM CM 04 CM CM CM CM Ol A
fa -H
/"S
i
3 3 3 3 3 3 3 3 3 3 3 3 3
+ + + + + + + + + + + + + + +
symbol
cn cn •—4 *— •H •-H
-J 3 3 3 3 3 3 3 3 3 3 3 3 3 3
The
Test
No.
f-M CM cn >3- m M3 o* 00 cr> O CM CO m M3
i \ 1
O O O O O O O I I
o
4-1
>4-1
•o
I I I -• < 4-1
o
<u
TO
£3
3
x> as
I
0)
M
0)
S
CD
a
C0
u
H I
co CO N N N a. 4J
CO Wi
H o
4-> a
o>
Vent
*o u
c
CO
0)
m m -o- m CO < «4- 1 1 <u
4-i a>
3> CO CO M »n
CJ CO
With
01
I
Oj •H 4
CO T3 C0
w u
4-1
o o < CM CO CM 1 1 C
•H
4-1
CO
• "O
0) a) CU
i— u si SI
Reduction T3 m .
m.
tn
•
m.
m •
o •
3
4-1
4-1U
H
CM CM CM CM CM m < 1 1 X
•H
u ss
o *
<4-1 <4-1
u
•a o
CM m CO CM CM CM CM 1 1 bo CU
c
C4-4
•H CO
Trap-Seal bO CO Q.
M 4-1 CO
CO S2 U
-C o u
o
co cm co -a- co co -S’ CM CO 0 ) 0)
1.1
t-l
0)
X4J
5
e
<u CO CO
A. co <5 p>* so p«» <o > 4-> SI
•H CO 4-1
4-1 •a
o CD
Table CO o c
c o
a> M-l c •H
s-/ co 4-1 4-1
'0- m 3 3 CD X
CO CO
3
U <U 4-1 4-1
+ + 4-1 o
CO
T3
<U
+ + s
CO
O
<u
4-1
3
i—4
00 CO CO CO CM
a>
u u 3 3 3 a H
>4-1 >4-1 T-l
T3
CO
o
<4-1
3 CO co CO C •H ai
4J sz
X o
+ + + + + 3 3 "3
C 3
u.
1-4 CO CNI CO
3
CM CM CM CM CM + + < t4 CD
Cb —-1
Q 3 3 3 3 3 3 —
> r— CO
CD
a>
+ + + + + + + (U <u
V-/
O
Xl Ul
u
a.
co CO a CO
3 3 3 3 3 3 3 3 < >s
CO
a u
(U
SI T3
V CD H
4-1 J= CO
CO
(U o
• H o a
H z CM CO -O’ m sO r-- ao as co x>
\ •
| | | | | | |
dash
OOGO<<<<<<<<QO<<< by
(continued)
OOOO<<<<<<O<<<<<< indicated
as
Open
OOOOmmominmininOinoO
••••••••••••••• 17,
OOOONNONNNNNONOO<l
•
Terminal
<D
14
3 11
u
Vent
hnChCChO c<o-<oo — oo X
c
O tests
with
oooomooinmininmoinoino 00
c
OOOONOONNNNNONiflNm H00
for
CO
Reduction
o oooomcninininm<-<-i<n4<:— 4=
o
CO trap
CO
C(nfO<!N^<!<!<!<o-<00^00 (U
> K4(a)
tH
4-1
Trap-Seal
o
CO the
c
CO
in mm of
1.1
U o O oo
<u
CO
•3
<U
+ + + 4-1
c0
made
A.
<D
U
00
t-l
mm
uu
sr 'O'
24 24 04 24
St
JN
H J
H
H
CJ
•H
3 CO 13
V z + + + + + + + + + C
4-J not
u
Table •H CO + CM CM CM CM CM CM CM CM -H CM CM CM
Pt4 T-l
Q “N /—
3 3 3 3 3 3 3 3 j 3 3 3 3
JQ
V—/ V
c0
t
CO
v—/
+ + + + + + + + + + + + + o
<r -<r m <r •HH cm NNHHH
24 CJ * 3 3 3 3 3 3 J 3 J J 3 3 3: a Observations
>>
00
rks.
cu
oo • 4= ma
0) o
N n N H
H Z vt in vO i— 00 CX> O CM CO <f lO
,
LI 12 13 SI K4 C5 F6
mm mm mm mm mm mm mm
21 20 20 25 16 15 8
LI 12 13 SI T2 K4 C5 F6
mm mm mm mm mm mm mm mm
45 39 29 24 25 38 28 24
Unit F/b: Trap--seal reductions^* after four runs with K4(a) + K4(b) discharged
W1 W2 U 12 T1 T2 C5 F6
mm mm mm mm mm mm mm mm
42 44 21 12 13 22 24 c
30 44 25 2 15 18 24 c
(0) d (0) (0) (0) (0) (0) (1) c
a 12 test average.
b The vent terminals of both the F/a and F/b units were closed.
A. D/a unit 3
13 W1 + W2 + W3 38 29 39 25 28 45 24 24.0 Ab A A
14 W1 + W2 + K4 A 10 39 25 16 31 25 7.0 A A 11
15 W1 + W2 + W3 + K4 A 23 42 25 22 41 25 6.0 A A A
16 W1 + W2 + W3 + C5 32 29 35 25 A 36 25 6.0 A A A
17 W1 + W2 + W3 23 25 27 23 25 30 22 17.5 A A A
18 W1 + W2 + K4 A 17 30 23 16 26 21 2.0 A A 12
19 W1 + W2 + W3 + K4 A 17 30 23 16 26 21 0.0 A A A
20 W1 + W2 4* W3 + C5 26 26 31 25 A 35 25 3.0 A A A
3 F6 vent closed.
b Symbol A indicates active (discharging) fixtures. Virtually zero seal reductions occurred
in the traps of such fixtures, due to refill provided by trailing flow at the end of the
discharge.
Table A. 2. 2 Trap-Seal Reduction with Vent Terminal Closed (continued)
B. F/b Unit
2 K4(a) 1 7 — 6 7 0.0 12 12 A
5 Wl + W2 + C5 +1 8 7.5 A 7 2.5 A A 4
6 W1 + W2 + C5 3 10 10.0 A 9 2.5 A A 4
7 Wl + W2 + K4 A 8 5.0 2 9 0.0 A A 4
8 Wl + W2 + K4 A 3 5.0 2 7 0.0 A A 3
9 Wl + W2 + K4 + C5 A 5 2.5 A 5 2.5 A A 2
10 Wl + W2 + K4 + C5 A 5 5.0 A 5 2.5 A A 0
11 L2 + W2 2 A 0.0 1 2 0.0 2 A -
12 W1 + W2 2 1 5.0 2 2 2.5 A A -
13 LI + W1 2 1 0.0 1 A 0.0 A 5 -
14 L2 + W1 1 A 0.0 1 0 0.0 A 3 -
15 W1 + W2 + LI 8 8 5.0 5 A 0.0 A A -
16 W1 + W2 + L2 2 A 2.5 2 4 2.5 A A -
17 W1 + W2 + T1 2 4 2.5 3 5 A A A -
A-
Table A. 2. 3 Effect on Idle Trap-Seal Reduction of Repeated
Loading without Refilling Trap6 between Runs,
with Vent Terminal Closed
A-10
/ / /
Table A. 2. 4 Vent Pressure Data for the D/a Unit with Vent Terminal Closed,
W1 + W2 + T2 Discharged (see also table A. 2. 3 and figure A. 2.1)
K4 SI W3
Test Time Time Time
Number/ Limit Peak Beyond Peak Beyond Peak Beyond
Run Switch Suction Suction Suction Suction Suction Suction
Number Setting Observed Limit Observed Limit Observed Limit
1/1 0.45£/ b/ cj b cj b/
2/ cj b 0.60 b cj b/
a This suction value was also observed for the clothes washer for this
run.
A-l 1
PATTERN OF TRAP FAILURES
RUN 1
RUN 2
FAILED TRAP THIS RUN
1 23456 7 8 9 10 11 12
RUN 3
RUN 4
B FAILED TRAP THIS RUN
1 2 345 67 89 10 11 12
Figure A. 2.1 Pattern of trap failures with repetitive, heavy loading and
closed vent terminal
A-12
•
It was expected that the data obtained by the method outlined here would be
useful in future analysis and updating of existing water supply pipe sizing
procedures that have been in use for over 40 years.
B-l
are essential to the rational updating of traditional procedures for the
design of water service and distribution piping, which are based on the
Hunter method.
B.2 RESULTS
Data were obtained intermittently and stored on magnetic tape, covering various
periods of time over a space of approximately 3 years. Sample analyses of the
data were made, from which it was concluded that vent pressure fluctuations
were negligible^ and trap-seal retention was adequate. Inspections of the roof
vents after a period of nearly 3 years showed no evidence of blockage. No
plumbing problems or complaints were reported to the Andrews Air Force Base
housing maintenance office that could be attributed to the existence of the
reduced-size vents. Any problems reported were for normal plumbing maintenance
or as a result of the presence of sensors installed for experimental purposes.
After about three years, the instrumented traps and the flow switches, as
well as exposed wiring and tubing, were removed to restore the wet piping
systems to an unaltered condition. Where appropriate, standard plumbing and
building materials were used to replace instrumented components and to repair
damaged elements. As had been expected, deterioration of the trap pins from
electrolytic corrosion ultimately resulted in some of the traps leaking.
Because of the great quantity of data that were recorded, and because of the
need to edit the records to remove spurious data, the resources available to
the program proved inadequate to complete the reduction, analysis, and
reporting of the data. The data are retained by NBS in anticipation of some
future opportunity to complete the analysis and report the detailed results.
Figures B.2.1 through B.2.8, and tables B.2.1 and B.2.2 show samples of data
extracted from the tapes, giving the distribution of hot and cold water flow
rates and consumption by fixture/outlet in two test units over a 5 day period.
reduced-size vents.
B-2
.
Tables B.2.1 and B.2.2 give the cumulative hot and cold (and combined hot and
cold) water consumption recorded over a period of 5 days for tests units D/a and
F/a. These data also show the distribution of the water consumption of fixture
and outlet.
Figures B.2.1 through B.2.8 show the distribution of hot and cold (and combined
hot and cold) water flow rates by fixture and proportion of flow occurrences
over a period of 5 days for test units D/a and F/a.
B-3
Outlet
and
Fixture
by
Distribution
and
D/a
Unit
period).
Test
day
Occupied 5
a
in
covering
Consumption
sample
(data
Water
B.2.1
Table
H
4-4
s m CO o rs pH pH CM pH
m o
o o
o O
m >a- m 9s?
Outlet
<u
o
nO
•
CM
•
nO
•
o•
NO
•
CM
•
oo
9
o 0 0 0 0 0
rs
0
o 9
O
O
(-1 on CO St CM CM oo ON pH O
pH
^H NO H
<u pH pH CM
Oh
and rH
CO
o
H OS
3 On rs rs o 00 rs oo
m
ON
o
cm o
o o
o
cm
m
CM NO nD
o
Fixture
O nO CO sf CM NO ON
0
St St
rH • • • • • • • 0 0 0 0 0 0 0
rH o CO H O CO pH oo ON rs ON ON m
CO on
H nO ON in St rs rs CM o CM pH rs
by
o CM CO pH CM pH ON
pH
3
4-1 4J
X
H c
3
00
nO
00
CM
m
m o
o
oo
m CO
ON
m
ON
o o
o o
o o
o O
o O
o
o
ON
S'?
o
Distribution
u* o • • • • • • • 0 0 0 0 0 0 0 o
M M oo CO rs CM CM rs CO <3- pH
0) 3 pH **H CM pH pH
-o 4-1 Oh
CO
<v
3 4-1
and CO o
3> EC CO
3 m pH O
m o CM N© O •3- o o
o o
o o o
o
NO St
F/a
u
3
O
iH
rs
•
CO
• •
o•
CO
•
rs
•
CM
•
ON
0
o0 0 0
o 0 0
st
0 0
4J
CO
rH
CO
on
st
nO
CM
o
NO
o
o
oo
p=H
pH
CM
'J’
o
ON
pH
pH
o
3 o pH pH CM pH pH 00
Unit
period).
4-4
Test
s ON NO o CO CM pH CO m
m o o 00 ON
m o a*
3
o
St
•
pH
•
NO
•
o•
rs
•
c—
•
00
•
CM
0 0
o0
o 0
NO
0 0
o 0
o
o
u M co CO CM CM CM CM NO CM NO pH
day
3 0) pH c=H pH co
4J Oh
Occupied 5 CO
3
a 33
rH
o 00
CJ 3 m rs o in pH 00 m CM o o CM
m
CM o CM
in
o
rH
ON
•
o•
ON
•
o• •
ON
•
CO
•
pH
0
ON
0
o0
o 0 0
St
0
o 0 0
covering rH o rs o ON St o
m CO ON r** ON CO
CO
o
CO CO St
pH
CM
H rs CM o
CM
CM
St pH
Consumption
sample
So >N
M M
o is O P In H U
4J at 4-4 0) 3 3 3
(data
CO 3 CO > •H rH r—i
Water > -Q o > -Q o 14-1 •H •H
CO
3 ^3
3
H
J=
CO
M
0)
CO
4-4 H
3 X
c/a
-X
o
•H
33
o
H
O
H
i-i -X J= o -X •H
3 3 JE JE -3 CO J3 -3 X o o a .3 -C
U u
rH
4-1 •H 4-4 4-4 4J CO 4-4 4-4 4-1 tH o 3 3
X CO CO CO CO 3 CO 3 3 rH o •x 3 3 3 4J
•H pa pa pa pa pa pa •H tH pa P3 JE o
B.2.2
3
3 c 3 s
CO
3 M M is
c/a •H
c/a
3
CJ 3 U
cn
3
H
je o O o -3 0) 04 3 4J 3 O 3 3
o s
Q
s s 4-4
o
4-1 u 4-1
3
3 M
3
3
u
g u £
4-1 0 0 CD CD O § cn CO
Table •H o o o rH eg eg 3 M <u 3 o 3 H
i4 CJ u C-> u S X X (H Pi o X Q
S^HSORS
RANGE
OVER
VENTS.
BACK-PRESSURE
FIXTURE
AND
SELECTED
SUCTION
IN
HERE.
INSTALLED
NOTSHOWN WERE
NOTE:
-©HI©
Figure B.1.1 Schematic of automatic monitoring instrumentation for
post-occupancy tests
B-6
Figure B.1.2 Schematic of post-occupancy field data acquisition system
B-7
1 « 1
1.0
.9
.8
.7
. 6
OCCURRENCES
.5
OF
.4-
PROPORTION
.3
. 2-
-
mimtn « i • «
• • 1 1 1 1 1 1 1 1 1 • • i i 1
. 1
mniMM
iinmiii
trill
*•1
i • 1
ft* ft
Mllllllll
1 1 1 V 1
flaw 1 1 1 1 1 mu1 1 1
o-
Figure B.2 1 Distribution of cold water flow rates in master bath shower.
D/a
unit (data sample covering a 5 day period)
B-8
1.0
.9
.8
.7
. 6
OCCURRENCES
.5 -
OF . 4-
PROPORTION
.3 -
1 1 1 < t
iiii*
- mi iimi
mu
•
iiim
i • 1 1 •
inn
tlfVf lllll
t immif iimi * 1 1 > i
- iiimiiimiti vim i
viimiiiimii vim 1 1 •
mtiiimiim inn • 1 1
Figure B.2.2 Distribution of hot water flow rates in master bath shower, D/a
unit (data sample covering a 5 day period)
B-9
1
1.0 -
-
.9
i
.8 .
.7 I
.6 -
i
OCCURRENCES
.5 .
I
OF 1„
.4- 1
i
I
PROPORTION
.3 -
i
I
i
i iimi
2 - i • I • t
mu
-
.
VMM
i
i
1 1 » 1
Mill
nm f
mu
» 9 1 1 1
i Mill till! • 1 M 1 1
* ’ 1 9 V t V « i f i « (till I 1 I 1
. 1
1 1 1 9 > flit* 9 1 1 1 1
'*
O'
Figure B.2 .3 Distribution of combined hot and cold water flow rates in master
bath shower, D/a unit (data sample covering a 5 day period)
B-10
1 1« )
« 1 1 1
1.0
UIM
* « I M
.9
t I I I (
t I t I t
HIM
.8 UIM
UIM
mu
.7 HIM
I 1 1 I I
HIM
HIM
HIM
. 6
I II If
Hill
OCCURRENCES
HIM
.5
HIM
I I I I I
OF II 1 1 I
.4- I 1 1 I
I I 1 I
PROPORTION
HIM
I I I I
.3
HIM
HIM
. 2- HIM
HIM
Hilt
I I I I I
-
I I I It
. 1 I I t I I
I I I I I
HIM
M
I I I
Figure B.2.4 Distribution of combined hot and cold water flow rates in common
bath shower head. D/a unit (data samples covering a 5 day period
B-Il
1
I
1.0 -
.9 -
.8 .
.7
OCCURRENCES
. 6
OF .5 -
PROPORTION
.4- -
.3
. 2-
1 1 1 1
I » I «
.r ;
*
0
Figure B.2.5 Distribution of cold water flow rates in master bath shower, F/a
unit (data sample covering a 5 day period)
B-12
1 1
1.0
.9
.8
.7
OCCURRENCES
.6
OF
.5
.4-
PROPORTION
2- - iimtiiii
1111111111
iiniiiiii 1 1 1 1
iiiiiiim 1 1 1
iiuivnti
• mu
« i » » r
nit
•
imniiif in
i>
iniMiiuiMit
• *
1 1
i
1
1 1
1 1 1 1 •
• iff* i * 1 1 1 1 « 1 1 1 1 1 1 1 1 1 I B 1
iiiiiMiiiiiiiiimiiiiii 1 1 1 1 1
Figure B.2.6 Distribution of hot water flow rates in master bath shower, F/a
unit (data sample covering a 5 day period)
B-13
1
1.0
8
.9 -
i
.7
. 6 -
OCCURRENCES
.5 -
OF
. 4 . :
PROPORTION
.3
iiiii
.2- -
i
mu
1 1 1 1
i
i 1 1 1
i iiiii
.1- • i 1 1
f v i v v IIIII
i
9 • V V « i i • i i
i iiiii f • I 9 V iiiii
0 i*---
Figure B.2.7 Distribution of combined hot and cold water flow rates in master
bath shower, F/a unit (data sample covering a 5 day period)
B-14
APPENDIX C. RECOMMENDED CRITERIA AND GUIDELINES FOR THE DESIGN AND INSTALLATION
OF REDUCED-SIZE VENTS FOR ONE- AND TWO-STORY HOUSING UNITS
C.l INTRODUCTION
The variables that determine safe, economic vent design and sizing are numerous,
difficult to define, and intricately related. Among these variables are the
time dependent air flow in the DWV pipe network. The interdependence of the
drains and vents for functional adequacy, the likelihood of random simultaneous
or concurrent (overlapping) discharge of two or more fixtures, the hydraulic
discharge characteristics of the drainage from the individual fixtures, the
heights of the drainage stacks, the geometry of the drainage fittings, drain
pipe sizes, and the specific configuration of the DWV system.
Various research programs to study the hydraulics and pneumatics of DWV systems
have been conducted; some have provided semi-scientific, more or less empirical,
bases for relaxing specification of some of the stringent requirements (e.g.,
unnecessarily large stack sizes and individual venting of each and every fix-
ture) in plumbing practice as regulated by the early plumbing codes in the
United States.
Among the mitigating effects of this research have been the gradual recognition
by codes of certain cost-saving practices such as wet venting, stack venting,
common venting, and the use of 3 inch diameter soil stacks and building drains
under many conditions. Based on a combination of research findings and empiri-
cal or practical judgments, codes have, from time-to-time updated the require-
,
ments for sizing and configuration of vent systems. Generally, this evolution-
ary process has resulted in requirements less restrictive than they were before
the research was conducted. However, many codes still require a considerable
amount of ventilation piping, undoubtedly more than necessary for many systems.
1. Traditional criteria for sizing main vents (stack vents and vent
stacks) were derived from research data obtained under hydraulic test
C-l
conditions which were more severe than those normally occuring in
actual service, especially in one- and two-story residential buildings.
2. The traditional criteria for sizing fixture vents and branch vents
were purely empirical and based on practical experience and collective
opinion.
3. Analysis indicated that air flow demands in the vents of the DWV
systems of one- and two-story buildings are substantially less than
those provided for by the prescriptive sizing requirements of
plumbing codes.
The results of the several RSV studies have confirmed the hypothesis that
reduced-size vents may perform adequately and have provided certain new design
criteria and installation guidelines to facilitate the utilization of reduced-
size venting as a viable technique.
Among the principal variables affecting the cost of any system are the
following:
(a) the fixtures and appliances should be grouped to limit the number
of fittings and the amount of horizontal piping.
(b) where possible, the design should provide for back-to-back
bathrooms.
(c) In two-story systems, an attempt should be made to place bathrooms
and plumbing walls one above the other ("stacked").
C-2
designs provide for simpler configurations and less piping than
individual venting.
3 . Field changes .
The nature and extent of field changes can affect overall costs
significantly. In general, field changes should be made only in
response to architectural or site constraints, to reduce complexity
and/or the amount of piping, or to avoid inadvertant violation of the
code.
This would limit RSV to systems or components with a maximum of three floors of
plumbing fixtures with connections distributed over a vertical distance not
exceeding 18 ft. This would generally include all one-story residences with
or without basements or crawl spaces, most split level designs, and two-story
Colonial designs conforming to the 18 ft distribution rule. This would pre-
clude RSV in two-story designs with full basement and sewer below basement in
which plumbing connections are made in each of the three branch intervals to
a stack running the full height of the building.
C-3
^
Reduced-size vents shall not be used for fixture and stack vents below an
elevation 6 inches above the flood rim of the highest fixture served by the
vent, nor for any portion of a vent subject to intermittent wetting; e.g., by
water rise due to a drain blockage or pressure that could be exerted by a
pumped discharge.
See Section C.5 for important installation guidelines for reduced-size venting.
C-4
geographical area. Weather records^, ASHRAE criteria^ and other
available data^ may be helpful in estimating the likelihood of
frost closure. Vent terminals should probably be enlarged in accor-
dance with the local plumbing code in localities having minimum winter
design temperatures of less than 0°F (97-1/2 percent Column of the
ASHRAE Criterion for the time during December, January, and February).
The critical areas in which frost closure is likely, according to
this criterion, are largely in some portions of the Northern Rocky
Mountains, upper Midwest and upper New England.
2 Evaluated Weather Data for Cooling Equipment Design, 1963 and Addendum No. 1
Summer and Winter Data Fluor Products Company, Santa Rosa, Calif., 1964.
,
Engineering Weather Data, Army, Navy, and Air Force Manual TM 5-785, 1963.
C-5
1. Obtain preliminary data on site and geographic conditions, piping
materials, and specific plans and specifications for a standard DWV
design acceptable to or approved by the Administrative Authority
(see section C.3). Based on these data, review the general limi-
tations applicable to RSV (see section C.2) before proceeding to
step 2.
a) Label each dry vent with a letter designation, and the fixture
unit load served according to table C.4.1. Then determine the
appropriate classification of each dry vent: (1) individual or
common fixture vent, or waste stack vent, (2) soil stack vent,
(3) branch vent or vent header, if any, and (4) vent stack, if
any.
Case 1 . Assume a two-story townhouse design, figure C.4.1, that has been
determined acceptable under the applicable plumbing code. Preliminary investi-
gation reveals that PVC plastic is acceptable for all DWV pipe and fittings,
and that sewer surcharging and frost closure is unlikely, based on site
conditions, geographical location, and local experience.
To apply the RSV sizing criteria, each dry vent is labeled with a letter
designation, and classified and sized as illustrated in table C.4.7. The loads
C-6
served and the RSV sizes are then transferred to the schematic (figure C.4.2).
Both standard and reduced-sizes may be shown here for comparison if desired.
Summarizing, table C.4.7 and figure C.4.2 show the results of the classification
and sizing of the dry vents according to the RSV criteria.
Table C.4.8 and figure C.4.4 show the results of the classification and sizing
of the dry vents according to the RSV criteria.
The system shown in figures C.4.3 and C.4.4 requires five roof penetrations for
the five vents. A vent header might provide some overall cost reduction and
certainly would improve the appearance of the roof line. Table C.4.9 and figure
C.4.5 show the results of the application of the RSV criteria (table C.4.3) to
the sizing of the vent header.
The plumbing designer should maintain close contact with the installing
contractor before and during installation of the DWV system. The designer
should explain the special requirements of the reduced-size venting method to
the installer, who may be unfamiliar with them. To facilitate understanding
by the installer, the designer should review the basic design drawings and
specifications with the installer and when necessary to describe the system
fully, should provide more detailed drawings. This can enhance the potential
economies and level of performance obtainable from RSV installations.
The designer should make regular field inspections to be sure that the design
conditions are met. This is particularly important in the event field changes
are introduced by the contractor (as is often done for legitimate reasons in
typical plumbing work). The designer's early cognizance and review of the
plans for field changes is essential to assure conformance of the field changes
with the RSV criteria, and to assure that any RSV design changes necessitated
by the field piping changes are made in a timely fashion.
The owner should be given copies of the plumbing drawings for permanent record
so that any future additions can be properly designed and sized, and that the
location of all piping elements and drain cleanouts can be readily determined
in the event future maintenance, repairs or remodeling should be required.
C-7
so that compliance will be assured in the field. The following detailed
guidelines should be reviewed by both designer and installer.
If single bowl kitchen sinks (or double bowl sinks with separate traps and waste
pipes) are equipped with food waste grinders, the shutoff head of the grinder
unit, in height of water column, should be ascertained. The sink vent serving
the compartment with the grinder should not be reduced in size below an eleva-
tion 6 inches (15 centimeters) above the level corresponding to the shutoff
head of the unit.
This limitation does not apply to a grinder in a double-bowl sink with a single
trap and waste. A similar precaution should be observed in relation to any
fixture with a pumped discharge not having a drain air gap or air break.
Because most dishwashers and clothes washers are installed with a drain air gap
or break, they do not usually pose a potential problem in this respect.
The DWV system design should be reviewed to evaluate the possibility of sewage
rising into any of the vents in case of a typical drain blockage occurring any-
where in the system followed by the discharge of fixtures. In most cases, it
will be apparent that the rise in a given vent will be limited to the flood rim
level of a particular fixture. No portion of a vent at an elevation up to
6 inches (15 cm) above the floor rim level or any higher elevation that could
be wetted from such occurrences should be reduced in size.
Since reduced-size vents may not be suitable for the entry of standard drain
cleaning tools, care should be taken to assure that drain cleanouts or clean-
out equivalents are adequate to assure compliance with the cleanout
requirements of the code.
In the selection of fittings for size reduction, the most economical available
fitting or combination of fittings should be used. Generally, the fewest
number of fittings should be used that will accomplish the necessary size
reductions.
Pipe and fittings customarily used in DWV work are not now manufactured in
sizes less than 1-1/4 inches. In sizes of 1 inch and less, therefore, it will
be necessary to use pipe and fittings manufactured for other applications,
such as water supply; for example, type M copper tube, or SDR PR or Schedule 40
PVC plastic pressure pipe. Probably DWV type fittings would be manufactured in
these small sizes if RSV design becomes more generally accepted In plumbing
codes and were more widely specified.
Requirements for pitch and support of reduced-size vent piping are identical
to those for standard venting, except that closer support spacing for horizon-
tal runs of the sizes smaller than 1 1/4 in may be required in accordance with
the pipe manufacturer's recommendations since standard venting does not
recognize nor specify support spacing for such smaller vent sizes.
C-8
.
Vent terminals of 1 inch size and less should be fitted with durable, corrosion
resistant, enlarged screen caps of 1/8 to 3/16 inch mesh having an open area
at least 150 percent of that of the terminal. Where approved by the Adminis-
trative Authority, vents may terminate through a wall or beneath an overhang,
provided that the end is turned down and that such terminals are located at
least 2 feet above any openable window, door, or ventilation opening within 10
feet horizontally, and are located at least 10 feet horizontally from the
property line except for adjacent townhouse units. No vent shall terminate in
a wall space, floor-ceiling cavity, or attic.
The designer should assemble and organize the information required by the
Administrative Authority, using an acceptable or agreed-upon format. The
designer should be available to review this information with the Administrative
Authority. Generally, this would include drawings and specifications relating
to the RSV design. Other data may be requested by the Administrative Authority
4. the designer should prepare such data as a part of the submittal.
and If this
supplemental data will be required, this fact should be ascertained from the
preliminary discussion with the Administrative Authority (section C.3).
C-9
5 . Laboratory Studies of the Hydraulic Performance of One-Story and
Split-Level Residential Plumbing Systems with Reduced-Size Venting .
National Bureau of Standards Building Science Series BSS 49, March 1974.
R. S. Wyly, et al.
10. All's Well that Vents Well — Pre-Occupancy Performance of Field Units
with Reduced-Size Vents . Yearbook of the American Society of Sanitary
Engineering, 1976. M. J. Orloski.
C-10
^
Table C.4.1 Drainage Fixture Unit Load Ratings For Various Plumbing Fixtures
Drainage Fixture
Fixture or Group Units (dfu)
Floor drain 2
Laundry tub 2
Lavatory 1
Show stall 2
Water closet 4
Bathroom group 6
Half-bath group 4
Laundry group 4
C-ll
Table C.4.2 Minimum Sizes for Individual and Common Fixture Vents and
for Stack Vents
4 3/4
over 8
through 18 6 and less 1
7 through 15 1-1/4
15 through 30 1-1/2
16 through 30 2
* The vertical distance the water from the highest fixture (served by the
vent) falls before being diverted by the first vented horizontal drain
in its path, i.e., a vented horizontal branch drain or the building drain.
2 Fixture unit loadings for the usual fixtures are given in table C.4.1.
3 Increase one pipe size over listed value if vent length exceeds 25 ft.
C-12
Table C.4.3 Minimum Sizes for Branch Vents *
Number of Fixture
Vents Served Rule for Sizing^
A B - Ski X /EAVS
^ A branch vent need not be larger than would be required by table C.4.6 for a
vent stack serving a DWV system with the same total fixture unit loading as
the system for which the branch vent is being sized.
C-13
.
Table C.4.4 Combinations of Three Fixture Vent Sizes Requiring a Branch Vent
Two Pipe Sizes Larger than Largest Fixture Vent Served by Branch
Vent 1
in in in in
1 1 1 1-1/2
1-1/4 1 3/4 2
1-1/4 1 1 2
1-1/4 1-1/4 1 2
^ All other likely combinations of three fixture vent sizes require a branch
vent one pipe size larger than the largest fixture vent served by branch
vent
2 A branch vent need not be larger than would be required by table C.4.6 for
a vent stack serving a similar DWV system with the same total fixture unit
C-14
.
in in2 in 2 in 2
1 .864 .874
2 3.355 3.272
3 7.393 7.235
a Areas for other piping materials and wall thicknesses may be obtained or
calculated from the respective ASTM Standards or the manufacturers'
specifications
C-l 5
Table C.4.6 Minimum Sizes and Maximum Lengths for Vent Stacks
1 Increase one pipe size if frequent flooded sewer conditions are anticipated.
C-16
.
Table C.4.7 Classification and Sizing of Dry Vents (Figure C.4.2, Example 1)
C-17
.
Table C.4.8 Classification and Sizing of Dry Vents (Figure C.4.4, Example 2)
C-18
Table C.4.9 Sizing of Vent Headers 3
(Figure C.4.5, Example 2)
Nominal
Diameter
Header Fixture Vents al SA V s aB Required
Element Served (in 2 ) (in 2 ) (in 2 ) (in)
C-19
Figure C.4.1 S
hoiw
showing a
s
Ste
i T
n P Ping fOC 2 ' St ° ry 8ln le
i DWV
standard
S famil y Chouse,
design conforming to the applicable
plumbing code (compare with figure
C.4.2 for RSv/
C-20
Figure C.4.2 Soil-waste-vent piping for 2-story single family townhouse,
showing reduced sizes of dry vents obtainable from RSV design
criteria (compare with figure C.4.1 for standard venting)
C-21
««
ft% y-jp-
^
C-22
Figure C.4.4 Soil-waste-vent piping for 1-story single family residence,
design
showing reduced sizes of dry vents obtainable from RSV
criteria (compare with figure C.4.3 for standard venting)
C-23
Figure C.4.5 Soil-waste-vent piping for 1-story single family residence,
roof
showing the use of a vent header to reduce the number of
penetrations (compare with figures C.4.3 and C.4.4 showing
five penetrations)
C-24
NBS-1 14A (REV. 2-BC)
U.S. DEPT. OF COMM. 1. PUBLICATION OR 2. Performing Organ. Report NoJ 3. Publication Date
REPORT NO.
BIBLIOGRAPHIC DATA
4.
SHEET (See instructions)
NBSIR 84-2860
TITLE AND SUBTITLE
AUTHOR(S)
Robert Wyly, Lawrence S. Galowin
9.
PERFORMING ORGANIZATION (If joint or other than NBS. see Instructions) 7. Contract/Grant No.
Tri Services
Department of Defense and
11. Department of Housing and Urban Development
SUPPLEMENTARY NOTES
| |
Document describes a computer program; SF-185, FIPS Software Summary, is attached.
ABSTRACT (A 200-word or less factual summary of most significant information. If document Includes a significant
bibliography or literature survey, mention it here)
KEY WORDS (Six to twelve entries ; alphabetical order; capitalize only proper names; and separate key words by semicolon v
(_3 Order From National Technical Information Service (NTIS), Springfield, VA. 22161 $ 13.00
jlCOuu OC 80 4 ) p i '
.
'