Plate No.2 Gannaban Lizardo Villodres 2

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 13

ADAMSON UNIVERSITY

COLLEGE OF
ENGINEERING
DEPARTMENT OF CIVIL ENGINEERING

PLATE NO: CE322AL-02

COMPUTATION OF
GRAVITY LOADS

ZAIRA SAMANTHA P. GANNABAN


BSCE 3-2 201814665

PORTIA MAE C. LIZARDO


BSCE 3-2 201814113

NEIL PHILIP A. VILLODRES


BSCE 3-2 201813179

PROF. NOLAN C. CONCHA, Ph.D.


Professor
COMPUTATION OF GRAVITY LOADS

1. DEAD LOAD

2ND FLOOR PLAN LOAD DISTRIBUTION PLAN

𝐿
Two-way Slab = ≤ 2.0 L
𝑆

S SLAB PANEL

Equivalent Rectangular Load


For Trapezoid: For Triangle:

[ ] ()
2
S
3− PS
W= PS L W= 3
3 2

COMPUTATION OF GRAVITY LOADS


DEAD LOAD:

DESIGN PARAMETER:

A. LOCATION
MARAGONDON, CAVITE
B. PRELIMINARY SIZE OF MEMBER

Column: 400mm x 400mm

Slab: 200mm

Beam: 300mm x 400mm


C. MATERIALS

Concrete Strength: f’c=28MPa


Steel yielding strength (Main): 415MPa
Steel yielding strength (Secondary): 276MPa
Floor finishes: 1.0 kPa
Weight of concrete: 23.6kN/m
Weight of internal wall: 3.17kN/m
Weight of external wall: 3.45Kn/m
Parapet wall: 2.40kPa
Ceiling: 0.5kPa
COMPUTATION OF GRAVITY LOADS
DEAD LOAD: INTERIOR LONGITUDINAL ( 2ND FLOOR )

Slab = thickness x concrete unit weight


= .2 x 23.6 = 4.72 kPa
Electromechanical = 0.1kPa
Floor Finish = 1.0kPa
Ceiling = 0.5kPa

P = 4.72 + 0.10 + 1.0 + 0.5 = 6.32kPa

FOR BEAM AC-2 2ND FLOOR:

[ ] () [ ] ()
2 2
S 2
3− 3−
W1 = PS L = 6.32(2) 3 = 5.384kN/m
3 2 3 2

PS 6.32(5)
W2 = 3 = = 10.53kN/m
3

[ ( )] [ ( ) ]
2 2
S 1.95
3− 3−
W3 = PS L = 6.32(1.95) 6 = 5.945kN/m
3 2 3 2

Wall = pressure x height = 3.17kPa x 2.5m = 7.925kN/m


Beam = b x h x concrete unit weight = .3 x .4 x 23.6 = 2.832kN/m

W = 5.384 + 5.945 + 10.53+ 7.925+ 2.832 = 32.616kN/m

FOR BEAM CD-2 2ND FLOOR:

[ ( )] [ ( ) ]
2 2
S 2.925
3− 3−
W1 = PS L = 6.32(2.925) 6 = 8.511kN/m
3 2 3 2

[ ( )] [ ( ) ]
2 2
S 1.95
3− 3−
W2 = PS L = 6.32(1.95) 3 = 5.294kN/m
3 2 3 2
PS 6.32(1.95)
W3 = 3 = = 4.108kN/m
3

Wall = pressure x height = 3.17kPa x 2.5m = 7.925kN/m


Beam = b x h x concrete unit weight = .3 x .4 x 23.6 = 2.832kN/m

W = 8.511 + 5.294 +4.108 + 7.925 + 2.832 = 28.67kN/m


COMPUTATION OF GRAVITY LOADS

DEAD LOAD: INTERIOR TRANSVERSE ( 2ND FLOOR )

FOR BEAM 12-C 2ND FLOOR:

[ ( )] [ ( )]
2 2
S 3
3− 3−
W1 = PS L = 6.32(3) 5 = 8.342kN/m
3 2 3 2

PS 6.32(2.075)
W2 = 3 = = 4.371kN/m
3

PS 6.32(2.925)
W3 = = 3 = = 6.162kN/m
3

Wall = pressure x height = 3.17kPa x 2.5m = 7.925kN/m


Beam = b x h x concrete unit weight = .3 x .4 x 23.6 = 2.832kN/m

W = 8.342 + 4.371 + 6.162 + 7.925 + 2.832= 31.217kN/m

FOR BEAM 23-C 2ND FLOOR

PS 6.32(6)
W1 = 3 = 3
= 12.64kN/m
PS 6.32(3)
W2 = 3 = 3 = 6.32kN/m

Wall = pressure x height = 3.17kPa x 2.5m = 7.925kN/m


Beam = b x h x concrete unit weight = .3 x .4 x 23.6 = 2.832kN/m

W = 12.64 + 6.32 + 7.925 + 2.832 = 29.717kN/m

FOR BEAM 34-C 2ND FLOOR

PS6.32(6)
W1 = 3 = 3
= 12.64kN/m
PS 6.32(6)
W2 = 3 = 3 = 12.64kN/m

Wall = pressure x height = 3.17kPa x 2.5m = 7.925kN/m


Beam = b x h x concrete unit weight = .3 x .4 x 23.6 = 2.832kN/m

W = 12.64 + 12.64 + 7.925 + 2.832 = 36.037kN/m


COMPUTATION OF GRAVITY LOADS
DEAD LOAD: INTERIOR LONGITUDINAL (3RD FLOOR )

Slab = thickness x concrete unit weight


= .2 x 23.6 = 4.72 kPa
Electromechanical = 0.1kPa
Floor Finish = 1.0kPa
Ceiling = 0.5kPa

P = 4.72 + 0.10 + 1.0 + 0.5 = 6.32kPa

FOR BEAM AC-2 3RD FLOOR:

PS 6.32(5)
W1 = 3 = = 10.533kN/m
3

[ ( )] [ ( ) ]
S 2 2 . 525 2
3− 3−
W2 = PS L = 6.32(2 .525) 3 =6.095kN/m
3 2 3 2

[ ( )] [ ( ) ]
2 2
S 1.95
3− 3−
W3 = PS L = 6.32(1.95) 3 = 5.945kN/m
3 2 3 2

[ ( )] [ ( )]
2 2
S 1.95
3− 3−
W3 = PS L = 6.32(1.95) 3 = 5.945kN/m
3 2 3 2

W = 10.533 + 6.095 + 5.945 + 5.945 + 7.925 + 2.832 = 36.443kN/m

FOR BEAM CD-2 3RD FLOOR:

[ ( )] [ ( ) ]
2 2
S 1.500
3− 3−
W1 = PS L = 6.32(2.925) 6 3.0941kN/m
3 2 3 2

[ ( )] [ ( ) ]
2 2
S 1.95
3− 3−
W2 = PS L = 6.32(1.95) 3 = 5.294kN/m
3 2 3 2

PS 6.32(1.95)
W3 = 3 = = 4.108kN/m
3

W = 3.094 + 5.294 +4.108 + 7.925 + 2.832 = 23.253kN/m


COMPUTATION OF GRAVITY LOADS

DEAD LOAD: INTERIOR TRANSVERSE (3RD FLOOR )

FOR BEAM 12-C 2ND FLOOR:


PS 6.32(3)
W1= 3 = = 6.32kN/m
3

PS 6.32(3)
W2 = = 3 = = 6.32kN/m
3

[ ( )] [ ( ) ]
S 2 3 2
3− 3−
W3 = PS L = 6.32(3) 3 .5 =7.158kN/m
3 2 3 2
PS 6.32(6)
W4 = = 3 = = 12.64kN/m
3

W = 6.32 + 6.32 + 7.158 + 12.64 + 7.925 + 2.832= 43.187kN/m

FOR BEAM 23-C 2ND FLOOR


PS6.32(3)
W1 = 3 = 3
= 6.32kN/m
PS 6.32(3)
W2 = 3 = 3 = 6.32kN/m

W = 6.32 + 6.32 + 7.925 + 2.832 = 23.397kN/m

FOR BEAM 34-C 2ND FLOOR

PS 6.32(3)
W1 = 3 = 3
= 6.32kN/m

W = 6.32 + 7.925 + 2.832 = 17.077kN/m


COMPUTATION OF GRAVITY LOADS

LIVE LOAD: INTERIOR LONGITUDINAL

DESIGN CRITERIA:

1. Basic floor area 1.90kPa


2. Restrooms 1.90kPa
3. Stairs 4.80kPa
4. Corridors above ground floor 3.80kPa
5. Roof deck 1.90kPa

P1 = 1.90kPa P2=3.80kPa

For Beam AC-2 2ND FLOOR:

[ ( )] [ ( )]
2 2
S 2
3− 3−
W1 = PS L = 1.90(2) 3 =1.619kN/m
3 2 3 2

PS 1.90 (5)
W2 = = = 3.167kN/m
3 3

[ ( )] [ ( ) ]
2 2
S 1.950
3− 3−
W3 = PS L = 3.80(1.950) 6 = 3.575kN/m
3 2 3 2

W = 1.619 + 3.167 + 3.575 = 8.361kN/m

FOR BEAM CD-2 2ND FLOOR:

[ ( )] [ ( ) ]
2 2
S 2.925
3− 3−
W1 = PS L = 1.90(2.925) 6 = 2.559kN/m
3 2 3 2

[ ( )] [ ( ) ]
2 2
S 1.95
3− 3−
W2 = PS L = 3.80(1.95) 3 = 3.183kN/m
3 2 3 2
PS 3.80(1.95)
W3 = 3 = = 2.47kN/m
3

W = 2.559 + 3.183 + 2.47 = 28.67kN/m


COMPUTATION OF GRAVITY LOADS

LIVE LOAD: INTERIOR TRANSVERSE (2ND FLOOR)

FOR BEAM 12-C 2ND FLOOR:

[ ( )] [ ( )]
2 2
S 3
3− 3−
W1 = PS L = 1.90(3) 5 = 2.508kN/m
3 2 3 2

PS 3.80(2.075)
W2 = 3 = = 2.628kN/m
3

PS 3.80(2.925)
W3 = = 3 = = 3.705kN/m
3

W = 2.508 + 2.628 + 3.705= 8.841kN/m

FOR BEAM 23-C 2ND FLOOR

PS 1.90(6)
W1 = 3 = 3
= 3.8kN/m
PS 3.80(3)
W2 = 3 = 3 = 3.8kN/m

W = 3.8 + 3.8 = 7.6kN/m

FOR BEAM 34-C 2ND FLOOR

PS 1.90(6)
W1 = 3 = 3
= 3.8kN/m
PS 3.80(6)
W2 = 3 = 3 = 7.6kN/m

W = 3.8 + 7.6 = 11.4kN/m


COMPUTATION OF GRAVITY LOADS

LIVE LOAD: INTERIOR LONGITUDINAL (3RD FLOOR)

FOR BEAM AC-2 3RD FLOOR:

PS 1.90(5)
W1 = 3 = = 3.167kN/m
3

[ ] () [ ( ) ]
S 2 2.525 2
3− 3−
W2 = PS L = 1.90(2.525) 3 =1.832kN/m
3 2 3 2

[ ( )] [ ( ) ]
2 2
S 1.95
3− 3−
W3 = PS L = 3.80(1.95) 3 = 3.183kN/m
3 2 3 2

[ ( )] [ ( )]
2 2
S 1.95
3− 3−
W3 = PS L = 3.80(1.95) 3 = 3.183kN/m
3 2 3 2

W = 3.167 + 1.832 + 3.183 + 3.183 = 11.365kN/m

FOR BEAM CD-2 3RD FLOOR:

[ ( )] [ ( ) ]
2 2
S 1.500
3− 3−
W1 = PS L = 1.90(2.925) 6 = 2.721kN/m
3 2 3 2

[ ( )] [ ( ) ]
2 2
S 1.95
3− 3−
W2 = PS L = 3.80(1.95) 3 = 3.183kN/m
3 2 3 2

PS 3.80(1.95)
W3 = 3 = = 2.47kN/m
3

W = 2.721 + 3.183 + 2.47 = 8.374kN/m


COMPUTATION OF GRAVITY LOADS

LIVE LOAD: INTERIOR TRANSVERSE (3RD FLOOR )

FOR BEAM 12-C 2ND FLOOR:


PS 1.90(3)
W1= 3 = = 6.32kN/m
3

PS 1.90(3)
W2 = = 3 = = 6.32kN/m
3

[ ( )] [ ( )]
S 2 3 2
3− 3−
W3 = PS L = 3.80(3) 3.5 =7.158kN/m
3 2 3 2
PS 3.80(6)
W4 = = 3 = = 12.64kN/m
3

W = 6.32 + 6.32 + 7.158 + 12.64 + 7.925 + 2.832= 43.187kN/m

FOR BEAM 23-C 2ND FLOOR


PS 1.90(3)
W1 = 3 = 3
= 6.32kN/m
PS 3.80(3)
W2 = 3 = 3 = 6.32kN/m

W = 6.32 + 6.32 + 7.925 + 2.832 = 23.397kN/m

.0
00 FOR BEAM 34-C 2ND FLOOR

PS 1.90(3)
W1 = 3 = 3
= 1.9kN/m

W= 1.9kN/m
SUMMARY OF DEADLOADS
ALONG GRID 1

SUMMARY OF DEADLOADS
ALONG GRIDS
SUMMARY OF LIVELOADS
ALONG GRID 1 ALONG GRID 1