ADDITIONAL BRACKETS AND ANCHORAGE

CALCULATIONS FOR AWQAF PROJECT

1
NAME TYPE L (M) W(SPAN)M WIND LOAD, TRIBUTARY AREA (M2) REMARKS TYPE OF CONNECTION
GL 01 C.C.W 7.95 1.7 13.515 FOLLOW CALCULATION OF GL 01 FIX
GL 01 A C.C.W 7.95 1.7 13.515 FOLLOW CALCULATION OF GL 01 FIX
GL 02 STRIP 3 1.246 3.738 FOLLOW CALCULATION OF GL 08 PINNED
GL 03 STRIP 3 1.254 3.762 FOLLOW CALCULATION OF GL 08 PINNED
GL 05 STRIP 3 1.31 3.93 FOLLOW CALCULATION OF GL 42 PINNED
GL 06 STRIP 3.45 1.31 4.5195 FOLLOW CALCULATION OF GL 42 PINNED
GL 07 STRIP 3.45 1.238 4.2711 FOLLOW CALCULATION OF GL 42 PINNED
GL 08 STRIP 3 1.255 3.765 FOLLOW CALCULATION OF GL 08 PINNED
GL 09 STRIP 4.3 1.33 5.719 FOLLOW CALCULATION OF GL 30 FIX
GL 10 STRIP 4.25 1.095 4.65375 FOLLOW CALCULATION OF GL 42 PINNED
GL 11 STRIP 3.58 1.55 5.549 FOLLOW CALCULATION OF GL 30 FIX
GL 12 STRIP 3.75 1.2 4.5 FOLLOW CALCULATION OF GL 42 PINNED
GL 13 STRIP 3 1.38 4.14 FOLLOW CALCULATION OF GL 42 PINNED
GL 14 STRIP 3 1.2 3.6 FOLLOW CALCULATION OF GL 08 PINNED
GL 14 A STRIP 3 1.2 3.6 FOLLOW CALCULATION OF GL 08 PINNED
GL 14 B STRIP 3 1.2 3.6 FOLLOW CALCULATION OF GL 08 PINNED
GL 15 A STRIP 3.45 1.2 4.14 FOLLOW CALCULATION OF GL 42 PINNED
GL 15 B STRIP 3.6 1.2 4.32 FOLLOW CALCULATION OF GL 42 PINNED
GL 15 C STRIP 3.45 1.2 4.14 FOLLOW CALCULATION OF GL 42 PINNED
GL 15 D STRIP 3.45 1.2 4.14 FOLLOW CALCULATION OF GL 42 PINNED
GL 16 STRIP 4.15 1.1 4.565 FOLLOW CALCULATION OF GL 42 PINNED
GL 17 STRIP 3.05 1.12 3.416 FOLLOW CALCULATION OF GL 08 PINNED
GL 18 STRIP 2.96 1.125 3.33 FOLLOW CALCULATION OF GL 08 PINNED
GL 19 STRIP 1.2 0.975 1.17 FOLLOW CALCULATION OF GL 34 PINNED
GL 20 STRIP 1.2 0.975 1.17 FOLLOW CALCULATION OF GL 34 PINNED
GL 21 STRIP 1.2 0.95 1.14 FOLLOW CALCULATION OF GL 34 PINNED
GL 22 STRIP 1.2 0.95 1.14 FOLLOW CALCULATION OF GL 34 PINNED
GL 23 A STRIP 3 1.37 4.11 FOLLOW CALCULATION OF GL 42 PINNED
GL 23 B STRIP 3 1.255 3.765 FOLLOW CALCULATION OF GL 08 PINNED
GL 23 C STRIP 3 1.325 3.975 FOLLOW CALCULATION OF GL 42 PINNED
GL 24 A STRIP 3 1.365 4.095 FOLLOW CALCULATION OF GL 42 PINNED
GL 24 B STRIP 3 1.255 3.765 FOLLOW CALCULATION OF GL 08 PINNED

2
GL 24 C STRIP 3 1.255 3.765 FOLLOW CALCULATION OF GL 08 PINNED
GL 25 STRIP 3.45 1.255 4.32975 FOLLOW CALCULATION OF GL 42 PINNED
GL 26 STRIP 3.45 0.785 2.70825 FOLLOW CALCULATION OF GL 34 PINNED
GL 27 STRIP 3.45 1.255 4.32975 FOLLOW CALCULATION OF GL 42 PINNED
GL 28 STRIP 3.45 1.255 4.32975 FOLLOW CALCULATION OF GL 42 PINNED
GL 29 STRIP 3.45 1.255 4.32975 FOLLOW CALCULATION OF GL 42 PINNED
GL 30 STRIP 4.5 1.185 5.3325 FOLLOW CALCULATION OF GL 30 FIX
GL 31 STRIP 3.15 1.055 3.32325 FOLLOW CALCULATION OF GL 08 PINNED
GL 32 STRIP 3 0.995 2.985 FOLLOW CALCULATION OF GL 08 PINNED
GL 33 STRIP 3.2 1.095 3.504 FOLLOW CALCULATION OF GL 08 PINNED
GL 34 STRIP 2.85 0.7475 2.130375 FOLLOW CALCULATION OF GL 34 PINNED
GL 35 STRIP 2.85 0.7475 2.130375 FOLLOW CALCULATION OF GL 34 PINNED
GL 36 STRIP 2.85 0.695 1.98075 FOLLOW CALCULATION OF GL 34 PINNED
GL 37 STRIP 2.85 0.7475 2.130375 FOLLOW CALCULATION OF GL 34 PINNED
GL 38 STRIP 2.85 0.7475 2.130375 FOLLOW CALCULATION OF GL 34 PINNED
GL 39 STRIP 2.85 0.6975 1.987875 FOLLOW CALCULATION OF GL 34 PINNED
GL 40 STRIP 3.6 1.485 5.346 FOLLOW CALCULATION OF GL 30 FIX
GL 41 STRIP 3.55 1.43 5.0765 FOLLOW CALCULATION OF GL 30 FIX
GL 42 STRIP 3.7 1.29 4.773 FOLLOW CALCULATION OF GL 42 PINNED
GL 43 STRIP 3.5 1.055 3.6925 FOLLOW CALCULATION OF GL 08 PINNED
GL 44 A STRIP 3 1.2 3.6 FOLLOW CALCULATION OF GL 08 PINNED
GL 44 B STRIP 3 1.2 3.6 FOLLOW CALCULATION OF GL 08 PINNED
GL 44 C STRIP 3.025 1.2 3.63 FOLLOW CALCULATION OF GL 08 PINNED
GL 45 STRIP 3.955 1.307 5.169185 FOLLOW CALCULATION OF GL 30 FIX
GL 46 STRIP 3 1.307 3.921 FOLLOW CALCULATION OF GL 42 PINNED

3
www.hilti-me.com
GL 08 BOTTOM , BP THK 6MM Profis Anchor 2.9.1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HST2 M10 hmin1
Return period (service life in years): 50
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef = 60 mm, hnom = 69 mm
Material:
Evaluation Service Report: ETA-15/0435
Issued I Valid: 12/21/2017 | -
Proof: SOFA design method + fib (07/2011) - after ETAG testing
Stand-off installation: eb = 0 mm (no stand-off); t = 2 mm
Anchor plate: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm2; gMs = 1.000
lx x ly x t = 150 mm x 130 mm x 2 mm; (Recommended plate thickness: calculated (2 mm))
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm
Base material: uncracked concrete, C40/50, fc,cyl = 40.00 N/mm2; h = 250 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 4
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

2 Load case/Resulting anchor forces y

Load case: Design loads


3 4

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.536 1.283 1.283 0.000
x
2 0.536 1.283 1.283 0.000
3 0.536 1.283 1.283 0.000 Tension
4 0.536 1.283 1.283 0.000

max. concrete compressive strain: - [‰]


max. concrete compressive stress: - [N/mm2] 1 2
resulting tension force in (x/y)=(0/0): 2.145 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load SOFA (fib (07/2011), section 10.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 0.536 22.429 3 OK
Pullout Strength* 0.536 15.085 4 OK
Concrete Breakout Strength** 2.145 38.933 6 OK
Splitting failure** 2.145 49.589 5 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
31.400 1.400 22.429 0.536

3.2 Pullout Strength


NRk,p [kN] yc gM,p NRd,p [kN] NSd [kN]
16.000 1.414 1.500 15.085 0.536

3.3 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm]
61,600 32,400 1.901 90 180
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 0.950 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
11.000 32.333 1.500 38.933 2.145
Group anchor ID
1-4

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 5
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

3.4 Splitting failure


Ac,N [mm2] A0c,N [mm2] y A,N ccr,sp [mm] scr,sp [mm] y h,sp
61,600 32,400 1.901 90 180 1.274
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1
0 1.000 0 1.000 0.950 1.000 11.000
N0Rk,c [kN] gM,sp NRd,sp [kN] NSd [kN]
32.333 1.500 49.589 2.145
Group anchor ID
1-4

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 6
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

4 Shear load SOFA (fib (07/2011), section 10.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.283 17.280 8 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 5.130 77.866 7 OK
Concrete edge failure in direction x+** 2.565 15.336 17 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
21.600 1.250 17.280 1.283

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm] k4
61,600 32,400 1.901 90 180 2.000
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 0.950 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
32.333 1.500 77.866 5.130
Group anchor ID
1-4

4.3 Concrete edge failure in direction x+


lf [mm] dnom [mm] kV a b
60 10.0 2.400 0.089 0.067
c1 [mm] Ac,V [mm2] A0c,V [mm2] y A,V
75 36,563 25,313 1.444
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V y 90°,V
1.000 1.000 1.000 0 1.000 1.000 2.000
V0Rk,c [kN] gM,c VRd,c [kN] VSd [kN]
15.926 1.500 15.336 2.565

5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.024 0.074 2.000 1 OK
concrete 0.055 0.167 1.500 9 OK

baN + baV <= 1

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 7
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 0.397 [kN] dN = 0.005 [mm]
VSk = 0.950 [kN] dV = 0.178 [mm]
dNV = 0.178 [mm]
Long term loading:
NSk = 0.397 [kN] dN = 0.057 [mm]
VSk = 0.950 [kN] dV = 0.263 [mm]
dNV = 0.269 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are valid
without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in this
calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This means load
re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in
order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate thickness with FEM to
limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by
PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be followed
to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling the gap
with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 8
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

8 Installation data
Anchor plate, steel: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm Anchor type and diameter: HST2 M10 hmin1
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm Installation torque: 0.045 kNm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 10 mm
Plate thickness (input): 2 mm Hole depth in the base material: 85 mm
Recommended plate thickness: calculated (2 mm) Minimum thickness of the base material: 120 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use
is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Seismic/Filling set
• Properly sized drill bit • Torque wrench
• Hammer
y

75 75

15
3 4

65
100

x
65

1 2
15

40 70 40

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -35 -50 75 145 - -
2 35 -50 145 75 - -
3 -35 50 75 145 - -
4 35 50 145 75 - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 9
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the
relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you
bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole
responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms
and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to
the absence of errors, the correctness and the relevance of the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the
AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by
carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs,
arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 10
GL 08 TOP , BASEPLATE THICKNESS 6 MM
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HST2 M8 hmin1
Return period (service life in years): 50
Effective embedment depth: hef = 47 mm, hnom = 55 mm
Material:
Evaluation Service Report: ETA-15/0435
Issued I Valid: 12/21/2017 | -
Proof: Design method EN 1992-4, Mechanical
Stand-off installation: eb = 0 mm (no stand-off); t = 2 mm
Anchor plate: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm2; gMs = 1.000
lx x ly x t = 140 mm x 120 mm x 2 mm; (Recommended plate thickness: calculated (2 mm))
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm
Base material: uncracked concrete, C40/50, fc,cyl = 40.00 N/mm2; h = 250 mm, partial material safety factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 11
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

2 Load case/Resulting anchor forces y

Load case: Design loads


2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 2.565 2.565 0.000
x
2 0.000 2.565 2.565 0.000

max. concrete compressive strain: - [‰]


max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 0.000 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN] 1

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 12
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* N/A N/A N/A N/A
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Strength** N/A N/A N/A N/A
Splitting failure** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 13
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 2.565 9.120 29 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 5.130 48.689 11 OK
Concrete edge failure in direction x+** 5.130 12.884 40 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


V0Rk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
11.400 1.000 11.400 1.250 9.120 2.565

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm] fc,cyl [N/mm2] k8
32,456 19,881 71 141 40.00 2.000
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N
0 1.000 0 1.000 0.998 1.000 1.000
k1 N0Rk,c [kN] gM,c,p VRd,cp [kN] VEd [kN]
11.000 22.417 1.500 48.689 5.130
Group anchor ID
1, 2

4.3 Concrete edge failure in direction x+


lf [mm] dnom [mm] k9 a b fc,cyl [N/mm2]
47 8.0 2.400 0.082 0.065 40.00
c1 [mm] Ac,V [mm2] A0c,V [mm2]
70 31,500 22,050
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V
1.000 1.000 1.000 0 1.000 1.000
V0Rk,c [kN] kT gM,c VRd,c [kN] VEd [kN]
13.528 1.0 1.500 12.884 5.130

5 Displacements (highest loaded anchor)


Short term loading:
NSk = 0.000 [kN] dN = 0.000 [mm]
VSk = 1.900 [kN] dV = 0.585 [mm]
dNV = 0.585 [mm]
Long term loading:
NSk = 0.000 [kN] dN = 0.000 [mm]
VSk = 1.900 [kN] dV = 0.906 [mm]
dNV = 0.906 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are valid
without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in this
calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 14
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This means load
re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in
order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate thickness with FEM to
limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by
PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters of the
clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be followed
to ensure a proper installation.
• For the determination of the Psi_re,v (concrete edge failure) a concrete cover of the edge reinforcement c = 30 mm is assumed
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 15
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

7 Installation data
Anchor plate, steel: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm Anchor type and diameter: HST2 M8 hmin1
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 9 mm Hole diameter in the base material: 8 mm
Plate thickness (input): 2 mm Hole depth in the base material: 70 mm
Recommended plate thickness: calculated (2 mm) Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use
is required.

7.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Torque wrench
• Properly sized drill bit • Hammer
y

70 70

15
2

60
90

x
60

1
15

70 70

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 0 -45 - 70 - -
2 0 45 - 70 - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 16
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the
relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you
bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole
responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms
and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to
the absence of errors, the correctness and the relevance of the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the
AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by
carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs,
arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 17
GL 34 , BP THK 6 MM
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HST2 M12 hmin1
Return period (service life in years): 50
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef = 70 mm, hnom = 80 mm
Material:
Evaluation Service Report: ETA-15/0435
Issued I Valid: 12/21/2017 | -
Proof: SOFA design method + fib (07/2011) - after ETAG testing
Stand-off installation: eb = 0 mm (no stand-off); t = 3 mm
Anchor plate: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm2; gMs = 1.000
lx x ly x t = 150 mm x 130 mm x 3 mm; (Recommended plate thickness: calculated (3 mm))
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm
Base material: uncracked concrete, C40/50, fc,cyl = 40.00 N/mm2; h = 250 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 18
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

2 Load case/Resulting anchor forces y

Load case: Design loads


2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 1.234 1.857 1.857 0.000
x
2 1.234 1.857 1.857 0.000
Tension
max. concrete compressive strain: - [‰]
max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 2.467 [kN]
1
resulting compression force in (x/y)=(0/0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load SOFA (fib (07/2011), section 10.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 1.234 32.000 4 OK
Pullout Strength* 1.234 18.856 7 OK
Concrete Breakout Strength** 2.467 36.429 7 OK
Splitting failure** 2.467 49.239 6 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
44.800 1.400 32.000 1.234

3.2 Pullout Strength


NRk,p [kN] yc gM,p NRd,p [kN] NSd [kN]
20.000 1.414 1.500 18.856 1.234

3.3 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm]
60,000 44,100 1.361 105 210
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 0.986 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
11.000 40.745 1.500 36.429 2.467
Group anchor ID
1, 2

3.4 Splitting failure


Ac,N [mm2] A0c,N [mm2] y A,N ccr,sp [mm] scr,sp [mm] y h,sp
60,000 44,100 1.361 105 210 1.352
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1
0 1.000 0 1.000 0.986 1.000 11.000
N0Rk,c [kN] gM,sp NRd,sp [kN] NSd [kN]
40.745 1.500 49.239 2.467
Group anchor ID
1, 2

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 19
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

4 Shear load SOFA (fib (07/2011), section 10.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.857 25.120 8 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 3.713 80.143 5 OK
Concrete edge failure in direction x+** 3.713 21.386 18 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
31.400 1.250 25.120 1.857

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm] k4
60,000 44,100 1.361 105 210 2.200
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 0.986 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
40.745 1.500 80.143 3.713
Group anchor ID
1, 2

4.3 Concrete edge failure in direction x+


lf [mm] dnom [mm] kV a b
70 12.0 2.400 0.084 0.065
c1 [mm] Ac,V [mm2] A0c,V [mm2] y A,V
100 58,500 45,000 1.300
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V y 90°,V
1.000 1.000 1.000 0 1.000 1.000 2.000
V0Rk,c [kN] gM,c VRd,c [kN] VSd [kN]
24.676 1.500 21.386 3.713

5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.039 0.074 2.000 1 OK
concrete 0.068 0.174 1.500 9 OK

baN + baV <= 1

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 20
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 0.914 [kN] dN = 0.010 [mm]
VSk = 1.375 [kN] dV = 0.254 [mm]
dNV = 0.254 [mm]
Long term loading:
NSk = 0.914 [kN] dN = 0.106 [mm]
VSk = 1.375 [kN] dV = 0.376 [mm]
dNV = 0.391 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are valid
without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in this
calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This means load
re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in
order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate thickness with FEM to
limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by
PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be followed
to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling the gap
with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 21
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

8 Installation data
Anchor plate, steel: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm Anchor type and diameter: HST2 M12 hmin1
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm Installation torque: 0.060 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 3 mm Hole depth in the base material: 97 mm
Recommended plate thickness: calculated (3 mm) Minimum thickness of the base material: 140 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use
is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Seismic/Filling set
• Properly sized drill bit • Torque wrench
• Hammer
y

75 75

20
2

65
90

x
65

1
20

75 75

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 0 -45 100 100 - -
2 0 45 100 100 - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 22
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the
relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you
bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole
responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms
and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to
the absence of errors, the correctness and the relevance of the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the
AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by
carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs,
arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 23
www.hilti-me.com
GL 34 , TOP BP,THK 6 MM Profis Anchor 2.9.1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HST2 M8 hmin1
Return period (service life in years): 50
Effective embedment depth: hef = 47 mm, hnom = 55 mm
Material:
Evaluation Service Report: ETA-15/0435
Issued I Valid: 12/21/2017 | -
Proof: Design method EN 1992-4, Mechanical
Stand-off installation: eb = 0 mm (no stand-off); t = 1 mm
Anchor plate: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm2; gMs = 1.000
lx x ly x t = 140 mm x 120 mm x 1 mm; (Recommended plate thickness: calculated (1 mm))
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm
Base material: uncracked concrete, C40/50, fc,cyl = 40.00 N/mm2; h = 250 mm, partial material safety factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 24
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

2 Load case/Resulting anchor forces y

Load case: Design loads


2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 1.857 1.857 0.000
x
2 0.000 1.857 1.857 0.000

max. concrete compressive strain: - [‰]


max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 0.000 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN] 1

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 25
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* N/A N/A N/A N/A
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Strength** N/A N/A N/A N/A
Splitting failure** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 26
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.857 9.120 21 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 3.713 48.689 8 OK
Concrete edge failure in direction x+** 3.713 12.884 29 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


V0Rk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
11.400 1.000 11.400 1.250 9.120 1.857

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm] fc,cyl [N/mm2] k8
32,456 19,881 71 141 40.00 2.000
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N
0 1.000 0 1.000 0.998 1.000 1.000
k1 N0Rk,c [kN] gM,c,p VRd,cp [kN] VEd [kN]
11.000 22.417 1.500 48.689 3.713
Group anchor ID
1, 2

4.3 Concrete edge failure in direction x+


lf [mm] dnom [mm] k9 a b fc,cyl [N/mm2]
47 8.0 2.400 0.082 0.065 40.00
c1 [mm] Ac,V [mm2] A0c,V [mm2]
70 31,500 22,050
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V
1.000 1.000 1.000 0 1.000 1.000
V0Rk,c [kN] kT gM,c VRd,c [kN] VEd [kN]
13.528 1.0 1.500 12.884 3.713

5 Displacements (highest loaded anchor)


Short term loading:
NSk = 0.000 [kN] dN = 0.000 [mm]
VSk = 1.375 [kN] dV = 0.423 [mm]
dNV = 0.423 [mm]
Long term loading:
NSk = 0.000 [kN] dN = 0.000 [mm]
VSk = 1.375 [kN] dV = 0.656 [mm]
dNV = 0.656 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are valid
without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in this
calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 27
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This means load
re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in
order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate thickness with FEM to
limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by
PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters of the
clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be followed
to ensure a proper installation.
• For the determination of the Psi_re,v (concrete edge failure) a concrete cover of the edge reinforcement c = 30 mm is assumed
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 28
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

7 Installation data
Anchor plate, steel: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm Anchor type and diameter: HST2 M8 hmin1
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 9 mm Hole diameter in the base material: 8 mm
Plate thickness (input): 1 mm Hole depth in the base material: 70 mm
Recommended plate thickness: calculated (1 mm) Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use
is required.

7.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Torque wrench
• Properly sized drill bit • Hammer
y

70 70

15
2

60
90

x
60

1
15

70 70

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 0 -45 - 70 - -
2 0 45 - 70 - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 29
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the
relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you
bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole
responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms
and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to
the absence of errors, the correctness and the relevance of the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the
AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by
carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs,
arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 30
www.hilti-me.com
GL 42 BOTTOM , BP THK 6 MM Profis Anchor 2.9.1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HST2 M12 hmin1
Return period (service life in years): 50
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef = 70 mm, hnom = 80 mm
Material:
Evaluation Service Report: ETA-15/0435
Issued I Valid: 12/21/2017 | -
Proof: SOFA design method + fib (07/2011) - after ETAG testing
Stand-off installation: eb = 0 mm (no stand-off); t = 3 mm
Anchor plate: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm2; gMs = 1.000
lx x ly x t = 180 mm x 150 mm x 3 mm; (Recommended plate thickness: calculated (3 mm))
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm
Base material: uncracked concrete, C40/50, fc,cyl = 40.00 N/mm2; h = 250 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 31
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

2 Load case/Resulting anchor forces y

Load case: Design loads


3 4
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.662 1.637 1.637 0.000
x
2 0.662 1.637 1.637 0.000
3 0.662 1.637 1.637 0.000 Tension
4 0.662 1.637 1.637 0.000

max. concrete compressive strain: - [‰] 1 2


max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 2.646 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load SOFA (fib (07/2011), section 10.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 0.662 32.000 3 OK
Pullout Strength* 0.662 18.856 4 OK
Concrete Breakout Strength** 2.646 50.740 6 OK
Splitting failure** 2.646 67.014 4 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
44.800 1.400 32.000 0.662

3.2 Pullout Strength


NRk,p [kN] yc gM,p NRd,p [kN] NSd [kN]
20.000 1.414 1.500 18.856 0.662

3.3 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm]
84,800 44,100 1.923 105 210
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 0.971 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
11.000 40.745 1.500 50.740 2.646
Group anchor ID
1-4

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 32
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

3.4 Splitting failure


Ac,N [mm2] A0c,N [mm2] y A,N ccr,sp [mm] scr,sp [mm] y h,sp
84,800 44,100 1.923 105 210 1.321
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1
0 1.000 0 1.000 0.971 1.000 11.000
N0Rk,c [kN] gM,sp NRd,sp [kN] NSd [kN]
40.745 1.500 67.014 2.646
Group anchor ID
1-4

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 33
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

4 Shear load SOFA (fib (07/2011), section 10.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.637 25.120 7 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 6.549 111.627 6 OK
Concrete edge failure in direction x+** 3.275 20.331 17 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
31.400 1.250 25.120 1.637

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm] k4
84,800 44,100 1.923 105 210 2.200
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 0.971 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
40.745 1.500 111.627 6.549
Group anchor ID
1-4

4.3 Concrete edge failure in direction x+


lf [mm] dnom [mm] kV a b
70 12.0 2.400 0.064 0.059
c1 [mm] Ac,V [mm2] A0c,V [mm2] y A,V
170 155,000 130,050 1.192
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V y 90°,V
1.000 1.010 1.000 0 1.000 1.000 2.000
V0Rk,c [kN] n1 gM,c VRd,c [kN] VSd [kN]
50.670 2 1.500 20.331 3.275
Note: Resistance limit acc. to fib (07/2011) Eq. (10.2-6) is governing

5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.021 0.065 2.000 1 OK
concrete 0.052 0.161 1.500 8 OK

baN + baV <= 1

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 34
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 0.490 [kN] dN = 0.005 [mm]
VSk = 1.213 [kN] dV = 0.224 [mm]
dNV = 0.224 [mm]
Long term loading:
NSk = 0.490 [kN] dN = 0.057 [mm]
VSk = 1.213 [kN] dV = 0.332 [mm]
dNV = 0.337 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are valid
without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in this
calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This means load
re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in
order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate thickness with FEM to
limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by
PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be followed
to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling the gap
with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 35
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

8 Installation data
Anchor plate, steel: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm Anchor type and diameter: HST2 M12 hmin1
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm Installation torque: 0.060 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 3 mm Hole depth in the base material: 97 mm
Recommended plate thickness: calculated (3 mm) Minimum thickness of the base material: 140 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use
is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Seismic/Filling set
• Properly sized drill bit • Torque wrench
• Hammer
y

90 90

20
3 4

75
110

x
75

1 2
20

55 70 55

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -35 -55 95 170 - -
2 35 -55 165 100 - -
3 -35 55 95 170 - -
4 35 55 165 100 - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 36
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the
relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you
bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole
responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms
and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to
the absence of errors, the correctness and the relevance of the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the
AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by
carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs,
arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 37
www.hilti-me.com
GL 42 , TOP , BP THK 6 MM Profis Anchor 2.9.1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HST2 M8 hmin1
Return period (service life in years): 50
Effective embedment depth: hef = 47 mm, hnom = 55 mm
Material:
Evaluation Service Report: ETA-15/0435
Issued I Valid: 12/21/2017 | -
Proof: Design method EN 1992-4, Mechanical
Stand-off installation: eb = 0 mm (no stand-off); t = 2 mm
Anchor plate: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm2; gMs = 1.000
lx x ly x t = 140 mm x 120 mm x 2 mm; (Recommended plate thickness: calculated (2 mm))
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm
Base material: uncracked concrete, C40/50, fc,cyl = 40.00 N/mm2; h = 250 mm, partial material safety factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 38
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

2 Load case/Resulting anchor forces y

Load case: Design loads


2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 3.275 3.275 0.000
x
2 0.000 3.275 3.275 0.000

max. concrete compressive strain: - [‰]


max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 0.000 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN] 1

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 39
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* N/A N/A N/A N/A
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Strength** N/A N/A N/A N/A
Splitting failure** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 40
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 3.275 9.120 36 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 6.549 48.689 14 OK
Concrete edge failure in direction x+** 6.549 12.884 51 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


V0Rk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
11.400 1.000 11.400 1.250 9.120 3.275

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm] fc,cyl [N/mm2] k8
32,456 19,881 71 141 40.00 2.000
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N
0 1.000 0 1.000 0.998 1.000 1.000
k1 N0Rk,c [kN] gM,c,p VRd,cp [kN] VEd [kN]
11.000 22.417 1.500 48.689 6.549
Group anchor ID
1, 2

4.3 Concrete edge failure in direction x+


lf [mm] dnom [mm] k9 a b fc,cyl [N/mm2]
47 8.0 2.400 0.082 0.065 40.00
c1 [mm] Ac,V [mm2] A0c,V [mm2]
70 31,500 22,050
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V
1.000 1.000 1.000 0 1.000 1.000
V0Rk,c [kN] kT gM,c VRd,c [kN] VEd [kN]
13.528 1.0 1.500 12.884 6.549

5 Displacements (highest loaded anchor)


Short term loading:
NSk = 0.000 [kN] dN = 0.000 [mm]
VSk = 2.426 [kN] dV = 0.746 [mm]
dNV = 0.746 [mm]
Long term loading:
NSk = 0.000 [kN] dN = 0.000 [mm]
VSk = 2.426 [kN] dV = 1.157 [mm]
dNV = 1.157 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are valid
without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in this
calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 41
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This means load
re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in
order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate thickness with FEM to
limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by
PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters of the
clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be followed
to ensure a proper installation.
• For the determination of the Psi_re,v (concrete edge failure) a concrete cover of the edge reinforcement c = 30 mm is assumed
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 42
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

7 Installation data
Anchor plate, steel: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm Anchor type and diameter: HST2 M8 hmin1
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 9 mm Hole diameter in the base material: 8 mm
Plate thickness (input): 2 mm Hole depth in the base material: 70 mm
Recommended plate thickness: calculated (2 mm) Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use
is required.

7.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Torque wrench
• Properly sized drill bit • Hammer
y

70 70

15
2

60
90

x
60

1
15

70 70

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 0 -45 - 70 - -
2 0 45 - 70 - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 43
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the
relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you
bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole
responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms
and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to
the absence of errors, the correctness and the relevance of the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the
AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by
carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs,
arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 44