Troubleshooting
SMCS - 4450-035
View Image
g00555151
Illustration 1
(CR7) Varistor
Visual Checks
A visual inspection of the generator set can detect possible causes of a malfunction. Inspect all wiring for
worn insulation or missing insulation. Ensure that all wire terminal connections are tight. Also ensure that
Page 1 of 2
Caterpillar China Power System
all wire terminal connections are not corroded. Discolored electrical components indicate that the item has
been greatly stressed.
A large percentage of electrical problems are caused by mechanical defects. Carefully inspect the total
installation. Keep the mechanical defects separate from the electrical defects.
Problem List
Table 1
All Phase Voltages Are Too Low. Damaged diodes (CR1 through "Rotating Rectifier -
CR6) Test"
The Phase Voltages Are Not Equally Damaged main armature (Stator "Winding - Test"
Balanced. - L4)
The Phase Voltages Do Not Change With Damaged diodes (CR1 through "Rotating Rectifier -
Engine Speed. CR6) Test"