Professional Documents
Culture Documents
E560 Bcu02 DB
E560 Bcu02 DB
Application Characteristics
The bus connection 560BCU02 may only be used in
The bus connection unit 560BCU02 is designed to
the 23TP21. The board is mounted to the plug-in
make the RTU560 System Bus Signals accessible to
terminal strips at slot address / board address 69/4
the outside.
and 77/2. This gives the chance to use two RTU560
boards at this slots.
ALARM (ALR) and WARNING (WRN) are signalled to
the outside with relay contacts. The power comes from the RTU560 boards and a
24 V cable.
An external minute impulse may be connected via an
The signals ALARM and WARNING are distributed
optocoupler. The filtered internal minute impulse is
with relay contacts. On signalling ALARM the signal
outputted as 24 V impulse.
WARNING is activated also.
The 560BCU02 may only be used in the 23TP21. ALARM and WARNING are supervised from a
With this board two RTU560 communication boards watchdog. They are activated if the communication
560SLI01 and/or 560ETH01 are usable within the modules do not respond within 30 seconds.
23TP21.
At the isolated minute impulse input TSI an external
minute impulse may connected to the RTU560
boards. This minute impulse is evaluated from the
SBK 1
SBK 2
Alarm 1
+24 V
ALR ∫1
RTU system bus
Alarm 2
Warning 1
WRN ∫1
Warning 2
+24 V
TSO TSO +
Explanation:
SBK1 = plug-in terminal strip 1
SBK2 = plug-in terminal strip 2
Technical Data
In addition to the general technical data of the RTU560, the following applies:
Minute impulse input Power supply
TSI: plug-in terminal strip 2-pole Supply: 5 V / app. 80 mA
isolated, 24 V input 24 V / app. 60 mA
Mechanics
Minute impulse output PCB: 100 x 55 mm
TSO: plug-in terminal strip 2-pole Weight: app. 0,2 kg
24 V output.
Connection Type
Signal outputs Connectors: 2 plug-in terminal strips
18 pole each
Alarm-/Warning: plug-in terminal strip
Output: 2-pole each Environmental Conditions
Relay contact: active closed
Warning set also with Alarm Temperature: 0 ... 70 C
1 A / 60 V DC / 30 W Relative humidity: 5 ... 95 %
(non condensing)