The document contains calculations of short circuit currents (IF) at faults F4 through F8 on a system. For each fault: 1) The total per-unit impedance (Zpu) from source to fault is calculated including line and transformer impedances. 2) The short circuit current (IF) is then calculated as the source power rating divided by the voltage and Zpu. The results show short circuit currents of 3.01 kA, 7.7 kA, 8.06 kA, 6.9 kA, and 4.28 kA for faults F4 through F8 respectively.
The document contains calculations of short circuit currents (IF) at faults F4 through F8 on a system. For each fault: 1) The total per-unit impedance (Zpu) from source to fault is calculated including line and transformer impedances. 2) The short circuit current (IF) is then calculated as the source power rating divided by the voltage and Zpu. The results show short circuit currents of 3.01 kA, 7.7 kA, 8.06 kA, 6.9 kA, and 4.28 kA for faults F4 through F8 respectively.
The document contains calculations of short circuit currents (IF) at faults F4 through F8 on a system. For each fault: 1) The total per-unit impedance (Zpu) from source to fault is calculated including line and transformer impedances. 2) The short circuit current (IF) is then calculated as the source power rating divided by the voltage and Zpu. The results show short circuit currents of 3.01 kA, 7.7 kA, 8.06 kA, 6.9 kA, and 4.28 kA for faults F4 through F8 respectively.
The document contains calculations of short circuit currents (IF) at faults F4 through F8 on a system. For each fault: 1) The total per-unit impedance (Zpu) from source to fault is calculated including line and transformer impedances. 2) The short circuit current (IF) is then calculated as the source power rating divided by the voltage and Zpu. The results show short circuit currents of 3.01 kA, 7.7 kA, 8.06 kA, 6.9 kA, and 4.28 kA for faults F4 through F8 respectively.
Zpu = ZU + ZTR + ZC101 + ZC102 + ZC112 Zpu = 77.22233+31.52258j pu = 83.4084 ∟22.21° pu 2. SHORT CIRCUIT CURRENT AT FAULT F4 IF4 = [(100 MVA)/(0.23 kV)] x [(1 ∟0° pu)/(83.4084 ∟22.21° pu)] IF4 = 3.01 kA
FOR SHORT CIRCUIT AT FAULT F5
1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 + ZC102 + ZC113 Zpu = 17.84646+27.29562j pu = 32.61207 ∟56.82° pu 2. SHORT CIRCUIT CURRENT AT FAULT F5 IF5 = [(100 MVA)/(0.23 kV)] x [(1 ∟0° pu)/(32.61207 ∟56.82° pu)] IF5 = 7.7 kA
FOR SHORT CIRCUIT AT FAULT F6
1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 + ZC102 + ZC114 Zpu = 15.18136+27.17166j pu = 31.12512 ∟60.81° pu 2. SHORT CIRCUIT CURRENT AT FAULT F6 IF6 = [(100 MVA)/(0.23 kV)] x [(1 ∟0° pu)/(31.12512 ∟60.81° pu)] IF6 = 8.06 kA
FOR SHORT CIRCUIT AT FAULT F7
1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 + ZC102 + ZC115 Zpu = 18.78854+31.1755j pu = 36.39946 ∟58.92° pu 2. SHORT CIRCUIT CURRENT AT FAULT F7 IF7 = [(100 MVA)/(0.23 kV)] x [(1 ∟0° pu)/(36.39946 ∟58.92° pu)] IF7 = 6.9 kA
FOR SHORT CIRCUIT AT FAULT F8
1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 + ZC102 + ZC116 Zpu = 48.09221+33.49351j pu = 58.60611 ∟34.86° pu 2. SHORT CIRCUIT CURRENT AT FAULT F8 IF8 = [(100 MVA)/(0.23 kV)] x [(1 ∟0° pu)/(58.60611 ∟34.86° pu)] IF8 = 4.28 kA