MVM-1-X

Multi-Variable Monitor Sheet 1 of 4

270116
Product Submittal Rev. F
2019/09/10

7in. (178mm) SCREEN SIZE (S7)

MVM SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 50⁰F to 105⁰F (10⁰C to 40⁰C), 10% to 90% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 10%, 50/60 Hz, 14 VA, CLASS 2
DISPLAY TYPE CAPACITIVE TOUCH, 7in. (178mm), DIMMABLE
RESOLUTION 800px x 480px, 262144 COLORS
FACE GLASS, IP54
COMMUNICATION PROTOCOL BACNET MS/TP, BACNET IP

.11 (3)
DIMENSIONS:

3.75 (95)
7.0 (178) 3.61 (92)
6.25 (159)
1.3 (33)
2.11 (54)
6.0 (152) 1.4 (36)
8.75 (222)
8.11 (206)

2.50 (63)

2.4 (60) 5.63 (143)

MONITOR
O0.18 (5)
7.68 (195) WALL CUTOUT

MOUNTING FRAME
TERMINATION:

P OWER + INP UT P OWER, HOT

P OWER - INP UT P OWER, GROUND

IP CONNECTION FOR B A CNET IP OR


ETHERNET
TO LA P TOP FOR CONFIGURA TION

GND NET COM


GND

+ NET +
+

+
--

--

ETHERNET
POWER RS-485
24VAC - NET -

NOTE: PLEASE REFER TO MVM MANUAL FOR INSTALLATION, SETUP INSTRUCTIONS AND ADDITIONAL INFORMATION.
Solid Edge

SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.


ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2019


MVM-1-X
Multi-Variable Monitor Sheet 2 of 4

270116
Product Submittal Rev. F
2019/09/10

15in. (381mm) SCREEN SIZE (S15)

MVM SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 50⁰F to 105⁰F (10⁰C to 40⁰C), 10% to 90% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 10%, 50/60 Hz, 25 VA, CLASS 2
DISPLAY TYPE CAPACITIVE TOUCH, 15in. (381mm), DIMMABLE
RESOLUTION 1024px x 768px, 262144 COLORS
FACE GLASS, IP54
COMMUNICATION PROTOCOL BACNET MS/TP, BACNET IP

.16 (4)
DIMENSIONS:

11.6 (294)
15.0 (381) 9.0 (228)
12.5 (318)

1.8 (45)

12.0 (304) 1.8 (45) 2.6 (65)


15.5 (394)

2.50 (63) 14.37 (365)

MOUNTING FRAME

2.4 (60) 11.61 (295)


MONITOR

O0.18 (5)
13.98 (355) WALL CUTOUT
TERMINATION:

P OWER + INP UT P OWER, HOT

P OWER - INP UT P OWER, GROUND


IP CONNECTION FOR B A CNET IP OR
ETHERNET
TO LA P TOP FOR CONFIGURA TION

GND NET COM


GND
+

+ NET +
--

+
--

ETHERNET
POWER RS-485
24VAC - NET -

NOTE: PLEASE REFER TO MVM MANUAL FOR INSTALLATION, SETUP INSTRUCTIONS AND ADDITIONAL INFORMATION.
Solid Edge

SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.


ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2019


MVM-1-X
Multi-Variable Monitor Sheet 3 of 4

270116
Product Submittal Rev. F
2019/09/10

CONFIGURATIONS:
SINGLE ROOM CONFIGURATIONS (1RM)

CONFIGURATION TYPE: (1) CONFIGURATION TYPE: (2)


DISPLAY POINTS: (RMP-RMT-RMRH) DISPLAY POINTS: (RMP-RMT-ACH)
•Room Pressure •Status •Room Pressure •Status
•Room Temperature •Alarm/Caution Reason •Room Temperature •Alarm/Caution Reason
•Relative Humidity •Room Pressure Mode •Air Changes per Hour •Room Pressure Mode
•Room Mode Override •Room Mode Override

CONFIGURATION TYPE: (3) CONFIGURATION TYPE: (4)


DISPLAY POINTS: (RMT-RMRH-CO2) DISPLAY POINTS: (RMT-RMRH-ACH)
•Room Temperature • Status •Room Temperature •Status
•Relative Humidity •Alarm/Caution Reason •Relative Humidity •Alarm/Caution Reason
•CO2 •Room Pressure Mode •Air Changes per Hour •Room Pressure Mode
•Room Mode Override •Room Mode Override

TWO ROOM CONFIGURATIONS (2RM)

CONFIGURATION TYPE: (5) CONFIGURATION TYPE: (6)


DISPLAY POINTS FOR EACH ROOM: (RMP-RMRH) DISPLAY POINTS FOR EACH ROOM: (RMP-ACH)
•Room Pressure •Status •Room Pressure •Status
•Relative Humidity •Alarm/Caution Reason •Air Changes per Hour •Alarm/Caution Reason
•Room Mode Override •Room Mode Override

CONFIGURATION TYPE: (7) CONFIGURATION TYPE: (8)


DISPLAY POINTS FOR EACH ROOM: (RMT-RMRH) DISPLAY POINTS FOR EACH ROOM: (RMT-ACH)
•Room Temperature •Status •Room Temperature •Status
•Relative Humidity •Alarm/Caution Reason •Air Changes per Hour •Alarm/Caution Reason
•Room Mode Override •Room Mode Override

THREE ROOM CONFIGURATIONS (3RM)

CONFIGURATION TYPE: (9) CONFIGURATION TYPE: (10)


DISPLAY POINTS FOR EACH ROOM: (RMP-RMT) DISPLAY POINTS FOR EACH ROOM: (RMP-ACH)
•Room Pressure •Status •Room Pressure •Status
•Room Temperature •Alarm/Caution Reason •Air Changes per Hour •Alarm/Caution Reason
•Room Mode Override •Room Mode Override

CONFIGURATION TYPE: (11) CONFIGURATION TYPE: (12)


DISPLAY POINTS FOR EACH ROOM: (RMT-RMRH) DISPLAY POINTS FOR EACH ROOM: (RMT-ACH)
•Room Temperature •Status •Room Temperature •Status
•Relative Humidity •Alarm/Caution Reason •Air Changes per Hour •Alarm/Caution Reason
•Room Mode Override •Room Mode Override

NOTE: PLEASE REFER TO MVM MANUAL FOR INSTALLATION, SETUP INSTRUCTIONS AND ADDITIONAL INFORMATION.
Solid Edge

SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2019


MVM-1-X
Multi-Variable Monitor Sheet 4 of 4

270116
Product Submittal Rev. F
2019/09/10

CONFIGURATIONS (CONTINUED):
FOUR ROOM CONFIGURATIONS (4RM)

CONFIGURATION TYPE: (13) CONFIGURATION TYPE: (14)


DISPLAY POINTS FOR EACH ROOM: (RMP) DISPLAY POINTS FOR EACH ROOM: (RMT)

•Room Pressure •Status •Room Temperature •Status


•Alarm/Caution Reason •Alarm/Caution Reason
•Room Mode Override •Room Mode Override

CONFIGURATION TYPE: (15)


DISPLAY POINTS FOR EACH ROOM: (ACH)

•Air Changes per Hour •Status


•Alarm/Caution Reason
•Room Mode Override

SIX ROOM CONFIGURATIONS (6RM)

CONFIGURATION TYPE: (16) CONFIGURATION TYPE: (17)


DISPLAY POINTS FOR EACH ROOM: (RMP) DISPLAY POINTS FOR EACH ROOM: (RMT)

•Room Pressure •Status •Room Temperature •Status


•Alarm/Caution Reason •Alarm/Caution Reason
•Room Mode Override •Room Mode Override

CONFIGURATION TYPE: (18)


DISPLAY POINTS FOR EACH ROOM: (ACH)

•Air Changes per Hour •Status


•Alarm/Caution Reason
•Room Mode Override

EIGHT ROOM CONFIGURATIONS (8RM)

CONFIGURATION TYPE: (19) CONFIGURATION TYPE: (20)


DISPLAY POINTS FOR EACH ROOM: (RMP) DISPLAY POINTS FOR EACH ROOM: (RMT)

•Room Pressure •Status •Room Temperature •Status


•Alarm/Caution Reason •Alarm/Caution Reason
•Room Mode Override •Room Mode Override

CONFIGURATION TYPE: (21)


DISPLAY POINTS FOR EACH ROOM: (ACH)

•Air Changes per Hour •Status


•Alarm/Caution Reason
•Room Mode Override

NOTE: PLEASE REFER TO MVM MANUAL FOR INSTALLATION, SETUP INSTRUCTIONS AND ADDITIONAL INFORMATION.
SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Solid Edge

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2019