Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 6

INSPECTION TEST PLAN FOR ELECTRICAL AND

BLACK & VEATCH


INSTRUMENT INSTALLATION WORK PT TIGA PILAR ENERGI

Form: Rev.:
BVI-TPE-ITR-0052
Page:
CONTINUITY / ATTENUATION / OTDR TEST REPORT OF FIBER OPTIC CABLES AFTER
INSTALLATION Report No.:
INSPECTION DATE:
CABLE NO.:
CWA NO.: SUB-SYSTEM NO:
DWG NO.: DWG REV. NO.:

Test Equipment Used (Type/Model) : Serial No.:


Test Equip. Cert. No.: Cal. Date: Cal. Exp. Date:
Test Equipment Used (Type/Model) : Serial No.:
Test Equip. Cert. No.: Cal. Date: Cal. Exp. Date:

Fiber Type: □ MM □ SM
Wave Length: nm Reference Index:

Test Criteria a) Reference document: Manufacturer's manual


b) Acceptance criteria / value: Manufacturer's manual

FIBER
FIBER TUBE OPTICAL LENGTH (km) ATTENUATION (Db/km) REMARKS
COLOUR
NO. COLOUR.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Prepared By: Witnessed By: Approved By :


INVOLVEMENT PARTY
TPE QC Inspector BVI QC Inspector PTFI (Owner)
Name

Signature

Date
Form: Rev.:
BVI-TPE-ITR-0053
INSPECTION TEST PLAN FOR ELECTRICAL AND
BLACK & VEATCH
INSTRUMENT INSTALLATION WORK PT TIGA PILAR ENERGI

Page:
INSPECTION OF CABLE GLANDING FOR FIBER OPTIC CABLES
Report No.:
INSPECTION DATE:
CABLE NO.:
CWA NO.: SUB-SYSTEM NO:
DWG NO.: DWG REV. NO.:

Cable Glanding Location: FO Panel No./ Smart JB No.

ITEMS TO BE CHECKED CHECKED REMARKS


1 Cable Tag No.
2 Connection drawing is the latest one.
3 Cable tails good.
4 Correct gland/MCT block type and size.
Ohms
5 Gland/MCT(EMC)block to Earth. (Note-1)

6 Armor / Cable clamped.


7 Gland/MCT block tight.
8 Gland sealed.
9 Cable marker & wire maker of cores/wires shield installation correct.

Note-1: Record resistance of Gland body / MCT (EMC) block to earth (Acceptance: Max1.0 ohm). NOTE:

Fill all check items under RESULT:"ACC" if satisfactory; "N/A" - Not applicable; "REJ" - reject.

Prepared By: Witnessed By: Approved By :


INVOLVEMENT PARTY
TPE QC Inspector BVI QC Insoector PTFI (Owner)
Name

Signature

Date

Form: Rev.:
BVI-TPE-ITR-0055
Page:
END TO END TEST OF FIBER OPTIC CABLE
Report No.:
INSPECTION TEST PLAN FOR ELECTRICAL AND
BLACK & VEATCH
INSTRUMENT INSTALLATION WORK PT TIGA PILAR ENERGI

INSPECTION DATE:
CABLE NO.:
CWA NO.: SUB-SYSTEM NO:
DWG NO.: DWG REV. NO.:

1. BI-DIRECTIONAL END-TO-END ATTENUATION INSERTION LOSS


Test Equipment Used (Type/Model) : Optical Power Meter / . Serial No.:

Test Equip. Cert. No.: Cal. Date: Cal. Exp. Date:

Test Equipment Used (Type/Model) : Optical Light Source / . Serial No.:

Test Equip. Cert. No.: Cal. Date: Cal. Exp. Date:

Total Optical Cable Length (L): km Total Number of Splices (N): nos Total Number of Connectors (T): nos

Fiber □ MM Wavelength 850 nm Wavelength 1300 nm


Type
□ SM Wavelength 1310 nm Wavelength 1550 nm
A-B B-A (dB) AVE (dB) A-B (dB) B-A (dB) AVE (dB)
FIBER NO
(dB)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
Form: Rev.:
BVI-TPE-ITR-0055
Page:

END TO END TEST OF FIBER OPTIC CABLE


Report No.:
INSPECTION TEST PLAN FOR ELECTRICAL AND
BLACK & VEATCH
INSTRUMENT INSTALLATION WORK PT TIGA PILAR ENERGI

CABLE NO.:

FIBER NO A-B B-A (dB) AVE (dB) A-B (dB) B-A (dB) AVE (dB)
(dB)
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
INSPECTION TEST PLAN FOR ELECTRICAL AND
BLACK & VEATCH
INSTRUMENT INSTALLATION WORK PT TIGA PILAR ENERGI

76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96

Loss Budget Ave. Reading Remarks (Failed


Loss Budget Calculation (Estimation) Pass or Failed
Estimate (dB) Max. (dB) Core)

Single-mode (1310nm) Loss (dB)


= L x 0.4 + N x 0.3 + T x 0.75

Single-mode (1550nm) Loss (dB)


= L x 0.3 + N x 0.3 + T x 0.75
Multi-mode (850nm) Loss (dB)
= L x 3.5 + N x 0.3 + T x 0.75
Multi-mode (1300nm) Loss (dB)
= L x 1.5 + N x 0.3 + T x 0.75

Prepared By: Witnessed By: Approved By :


INVOLVEMENT PARTY
TPE QC Inspector BVI QC Insoector PTFI (Owner)
Name

Signature

Date

Form: Rev.:
BVI-TPE-ITR-0055
Page:

END TO END TEST OF FIBER OPTIC CABLE


Report No.:
CABLE NO.:
INSPECTION TEST PLAN FOR ELECTRICAL AND
BLACK & VEATCH
INSTRUMENT INSTALLATION WORK PT TIGA PILAR ENERGI

2. BI-DIRECTIONAL OTDR END-TO-END FAULT DETECTION


Test Equipment Used (Type/Model) : OTDR / . Serial No.:
Test Equip. Cert. No.: Cal. Date: Cal. Exp. Date:

Single-Mode

Acceptance Remarks
Single-mode (1310nm) Reading Max. Pass or Failed
Losses (Typical) (Failed Core/Point)

Cable Attenuation ≦ 0.4 dB/km 0.4 dB/km


Splice Loss ≦ 0.3 dB 0.3 dB
Connector Loss ≦ 0.75 dB 0.75 dB

Acceptance Remarks
Single-mode (1550nm) Reading Max. Pass or Failed
(Failed Core/Point)
Losses (Typical)
Cable Attenuation ≦ 0.3 dB/km 0.3 dB/km
Splice Loss ≦ 0.3 dB 0.3 dB
Connector Loss ≦ 0.75 dB 0.75 dB

Multi-Mode

Acceptance Remarks
Single-mode ( 850nm) Reading Max. Pass or Failed
(Failed Core/Point)
Losses (Typical)

Cable Attenuation ≦ 3.5 dB/km 3.5 dB/km


Splice Loss ≦ 0.3 dB 0.3 dB
Connector Loss ≦ 0.75 dB 0.75 dB

Acceptance Remarks
Single-mode (1300nm) Reading Max. Pass or Failed
(Failed Core/Point)
Losses (Typical)
Cable Attenuation ≦ 1.5 dB/km 1.5 dB/km
Splice Loss ≦ 0.3 dB 0.3 dB
Connector Loss ≦ 0.75 dB 0.75 dB
OTDR test results shall be printed out and attached.

Prepared By: Witnessed By: Approved By :


INVOLVEMENT PARTY
TPE QC Inspector BVI QC Insoector PTFI (Owner)
Name

Signature

Date

You might also like