TEST REPORT FOR SIEVE / GRADING ANALYSIS OF FINE AGGREGATE

Project : Integrated Hospitality & Sports Complex, Shillong


Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/SIA
EPC contractor : Badri Rai & Co Date :

ISO 14001:2004 Date of sample : Sample source :


ISO 9001:2008 Sample Location: Wt. of Sample : 1000 g
TEST OBSERVATION

Fineness Modulus Grading Required % as per IS 383


IS Sieve size
Sl. No. Wt. in g Remarks
in mm Cumm. %
% Retained Wt. passed in g % passed Zone I Zone II Zone III
retained
1 10 100 100 100

2 4.75 90 - 100 90 - 100 90 - 100

3 2.36 60 - 95 75 - 100 85 - 100

4 1.18 30 - 70 55 - 90 75 - 100

5 0.6 15 - 34 35 - 59 60 - 70

6 0.3 5 - 20 8 - 30 12 - 40

7 0.15 0 - 10 0 - 10 0 - 10

8 PAN N.A N.A N.A

Reference:

(i) IS: 2386-1963 (Part I): Methods of test for aggregates for concrete
(ii) IS: 383-1970 : Specification for Fine and Coarse aggregates from natural sources for concrete

BRC CSC SSCM

Sign

Name

Date
TEST REPORT FOR SIEVE / GRADING ANALYSIS OF COARSE AGGREGATE
(12.5 mm Single size)
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/SIA12.5
EPC contractor : Badri Rai & Co Date :

ISO 14001:2004 Date of sample : Sample source :


ISO 9001:2008 Sample Location : Wt. of Sample :
TEST OBSERVATION

Fineness Modulus Grading


IS Sieve size Required % as per IS
Sl. No. Wt. in g Remarks
in mm 383
% Retained Cumm. % retained Wt. passed in g % passed

1 16 100

2 12.5 85-100

3 10 0 - 45

4 4.75 0-10

5 2.36 -

6 PAN -

Reference:

(i) IS: 2386-1963 (Part I): Methods of test for aggregates for concrete
(ii) IS: 383-1970 : Specification for Fine and Coarse aggregates from natural sources for concrete

BRC CSC SSCM

Sign

Name

Date
TEST REPORT FOR SIEVE / GRADING ANALYSIS OF COARSE AGGREGATE (
20mm Single Size )
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/SIA20
EPC contractor : Badri Rai & Co Date :

ISO 14001:2004 Date of sample : Sample source :


ISO 9001:2008 Sample Location : Wt. of Sample :
TEST OBSERVATION

Fineness Modulus Grading


IS Sieve size Required % as per IS
Sl. No. Wt. in g Remarks
in mm 383
% Retained Cumm. % retained Wt. passed in g % passed

1 40 100

2 20 85-100

3 10 0 - 20

4 4.75 0-5

Reference:

(i) IS: 2386-1963 (Part I)- Methods of test for aggregates for concrete
(ii) IS: 383-1970 : Specification for Fine and Coarse aggregates from natural sources for concrete

BRC CSC SSCM

Sign

Name

Date
TEST REPORT FOR SILT CONTENT IN FINE AGGREGATE
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/SC
EPC contractor : Badri Rai & Co Date :

ISO 14001:2004 Date of sample : Sample source :


ISO 9001:2008 Sample Location : Wt. of Sample :
TEST OBSERVATION

Volume in (ml)
Sl. No. Particulars Remarks
Trial I Trial II

1 Volume of Sand in Jar V1 (ml)

2 Volume of Silt in Jar V2 (ml)

3 Silt Content % = (V2 / V1) X 100 =

Average(%)=

SILT CONTENT : As per IS 383 allowed max upto 3% by weight.

Reference:
(i) IS:383-1970: Specification for Coarse and Fine Aggregates from natural sources of concrete

(ii) IS:2386-1963:(Part II)- Method of test for aggregates for concrete

BRC CSC SSCM

Sign

Name

Date
TEST REPORT FOR FLAKINESS INDEX COARSE AGGREGATE(12.5 mm)
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/FLI12.5
EPC contractor : Badri Rai & Co Date :

ISO 14001:2004 Date of sample : Sample source :


ISO 9001:2008 Sample Location : Wt. of Sample :
TEST OBSERVATION

IS sieves
Weight retained on sieves(A) Weight retained on Flakiness scale (B) Weight passed on Flakiness scale (C)
sizes in Remarks
Gms Gms Gms
mm

16-12.5

12.5-10

10-6.3

Total

Flakiness Index = C/Ax100=

Reference:

(i)IS: 2386-1963(Part I):Methods of test for aggregates for concrete

BRC CSC SSCM

Sign

Name

Date
TEST REPORT FOR FLAKINESS INDEX COARSE AGGREGATE(20 mm)
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/FLI20
EPC contractor : Badri Rai & Co Date :

ISO 14001:2004 Date of sample : Sample source :


ISO 9001:2008 Sample Location : Wt. of Sample :
TEST OBSERVATION

IS sieves
weight retained on sieves(A) Weight retained on Flakiness scale (B) Weight passed on Flakiness scale (C)
sizes in Remarks
Gms Gms Gms
mm

25 - 20

20 - 16

16 - 12.5

12.5 - 10

10 - 6.3

Total

Flakiness Index = C/Ax100=

Reference:

(i)IS: 2386-1963 (Part I): Methods of test for aggregates for concrete

BRC CSC SSCM

Sign

Name

Date
TEST REPORT FOR ELONGATION INDEX COARSE AGGREGATE (12.5 mm)
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/ELI12.5
EPC contractor : Badri Rai & Co Date :

ISO 14001:2004 Date of sample : Sample source :


ISO 9001:2008 Sample Location : Wt. of Sample :
TEST OBSERVATION

IS sieves
weight retained on sieves(A) Weight retained on Elongation scale (B) Weight passed on Elongation scale (C)
sizes in Remarks
Gms Gms Gms
mm

16-12.5

12.5-10

10-6.3

Total

Elongation Index = B/Ax100=

Reference:

(i)IS: 2386 - 1963 (Part I): Methods of test for aggregates for concrete

BRC CSC SSCM

Sign

Name

Date
TEST REPORT FOR ELONGATION INDEX COARSE AGGREGATE (20 mm)
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/ELI20
EPC contractor : Badri Rai & Co Date :

ISO 14001:2004 Date of sample : Sample source :


ISO 9001:2008 Sample Location : Wt. of Sample :

TEST OBSERVATION

IS sieves
weight retained on sieves(A) Weight retained on Elongation scale (B) Weight passed on Elongation scale (C)
sizes in Remarks
Gms Gms Gms
mm

25 - 20

20 - 16

16 - 12.5

12.5 - 10

10 - 6.3

Total

Elongation Index = B/Ax100=

Reference:
(i)IS: 2386 - 1963(Part I):Methods of test for aggregates for concrete

BRC CSC SSCM

Sign

Name

Date
TEST REPORT FOR BULK DENSITY OF AGGREGATE
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/BKD
EPC contractor : Badri Rai & Co Date :

ISO 14001:2004 Date of sample : Sample source :


ISO 9001:2008 Sample Location: Wt. of Sample :
TEST OBSERVATION Type of Aggregate:

Sl. No. Description Trail No. 1 Trail No. 2 Trail No. 3 Remarks

1 Volume of the container (V) lt

2 Weight of the container (W1) kg

3 Weight of the container + Aggregate(W2) kg

4 Weight of Aggregate (W2-W1) kg

5 Loose Bulk Density (W2-W1)/V kg/lt

Average

Reference :
(i)IS 2386-1963 (Part-III): Method for testing aggregates for concrete

BRC CSC SSCM

Sign

Name

Date
TEST REPORT FOR SPECIFIC GRAVITY
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/CSC/SPG-
EPC contractor : Badri Rai & Co Date :

ISO 14001:2004 Date of sample : Sample source :


ISO 9001:2008 Sample Location: Wt. of Sample :
TEST OBSERVATION Type of Aggregate:

Sl. No. Description Trail No. 1 Trail No. 2 Remarks

1 Weight of SSD Aggregate (W1) g

2 Weight of the Pycnometer + SSD Aggregate + Water (W2) g

3 Weight of the Pycnometer + Water (W3) g

4 Weight of Oven dried sample (W4) g

5 Specific Gravity = (W4)/(W1-(W2-W3))

Average:

Reference :
(i)IS 2386-1963 (Part-III): Method for testing aggregates for concrete
BRC CSC SSCM

Sign

Name

Date
TEST REPORT FOR WATER ABSORPTION
TEST
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No.: BRC/PQP/IHSC/WA
EPC contractor : Badri Rai & Co Sample Date :

Type of sample : Sample source :


ISO 14001:2004
ISO 9001:2008 Sample Location : Wt. of Sample :

Coarse Aggregate 20 mm Date of testing:

Sl.no Description Trial I Trial II Remarks

1 Weight of Aggregate in SSD condition (Gms)

2 Weight of oven dry sample (Gms)

3 Water Absorption (%)

Average (%)

Coarse Aggregate 10 mm/12.5 mm

Sl.no Description Trial I Trial II Remarks

1 Weight of Aggregate in SSD condition (Gms)

2 Weight of oven dry sample (Gms)

3 Water Absorption (%)

Average (%)

Fine Aggregate

Sl.no Description Trial I Trial II Remarks

1 Weight of Aggregate in SSD condition (Gms)

2 Weight of oven dry sample (Gms)

3 Water Absorption (%)

Average (%)

Reference :

(i)IS 2386-1963 (Part-III): Method for testing aggregates for concrete

BRC CSC SSCM

Sign

Name

Date
TEST REPORT FOR REBAR
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC)
EPC contractor : Badri Rai & Co

ISO 14001:2004 Report No. BRC/PQP/IHSC/RF


ISO 9001:2008 Date
Tensile Elongatio
Certificate Wt.per mtr Yield stress Rebend
Sl. No. Grade Size mm Manufacturer Quantity Arrival date strength n Bend test
No. Kg/m N/mm2 test
N/mm2 %

REMARKS:
REQUIREMENTS AS PER IS: 1786:2008

Grade 0.2% proof stress,(N/mm2 U T S(N/mm2) (Min) Elongation(%) min

485 or 10 % more than the actual proof stress


Fe 415 415 14.5
whichever is higher

545 or 8 % more than the actual proof stress


Fe 500 500 12
whichever is higher

565 or 10 % more than the actual proof stress


Fe 500 D 500 16
whichever is higher

BRC CSC SSCM

Sign

Name

Date
TEST ON BRICKS FOR WATER ABSORPTION
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC)
EPC contractor : Badri Rai & Co

ISO 14001:2004 Area: Date of Testing:


ISO 9001:2008 Location: Report No.: BRC/PQP/IHSC/BWB
Sampling Date : Report Date:
TEST OBSERVATION

Weight of water absorbed % of water absorpyion


Weight of overdried Weight of wet bricks Ww
Sl. No. Sample No. Frog Mark (Ww-Wd) in Gms {(Ww-Wd) / Wd} X 100 Remarks
bricks Wd in Gms in Gms

Requirement as per IS:1077-1992:


The water absorption shall not be more than 20 percent by weight up to class 12.5 and 15 percent by weight for higher classes.
Reference
(i) IS : 1077-1992 : Specification for common burnt clay building bricks
(ii) IS : 3495 - 1992(Part-2): Methods of tests of burnt clay building bricks
(iii) IS : 5454 -1978: Method of sampling of clay building bricks

BRC CSC SSCM

Sign

Name

Date
TEST ON BRICKS FOR COMPRESSIVE STRENGTH
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC)
EPC contractor : Badri Rai & Co Date of Testing:

ISO 14001:2004 Area: Report No.: BRC/PQP/IHSC/BCS


ISO 9001:2008 Location: Report Date:
TEST OBSERVATION

Average crushing
No. of Size of brick LxWxH Crushing surface area Crushing load in Crushing strength in
Sl. No. Frog Mark strength of the Remarks
Samples in Cm in Cm2 Kg/Cm2 N/mm2
sample in N/mm2

Reference

(i) IS : 1077-1992: Specification for common burnt clay building bricks


(ii) IS : 3495-1992 (Part 1) - Methods of tests of burnt clay building bricks

BRC CSC SSCM

Sign

Name

Date
CEMENT TEST REPORT - FINENESS
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/FIN
EPC contractor : Badri Rai & Co Date of Testing:

ISO 14001:2004 Manufacture: Grade:


ISO 9001:2008 Type of Cement: Batch / Week No:
TEST OBSERVATION

Sl. No. Description Trail No. 1 Trail No. 2 Trail No. 3 Average Remarks

1 Weight of Cement (gms), A

Weight of Cement retained on


2
90 micron sieve (gms), B

Fineness value (%), (B/A) X


3
100

Reference:

(i) IS: 4031-1988 (Part I)- Methods of Physical test for Hydraulic cement
(ii)Shall be not more than 10% as per IS 1489-1991 (Part 1)

BRC CSC SSCM

Sign

Name

Date
CEMENT TEST REPORT - COMPRESSIVE STRENGTH
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/CCS
EPC contractor : Badri Rai & Co Date of Testing:

ISO 14001:2004 Manufacture: Grade:


ISO 9001:2008 Type of Cement: Batch / Week No:
TEST OBSERVATION
Average
Compressive
Weight of Cubes compressive Requirments as per IS 1489-
Sl. No. Age of Cube Cube ID Date of Casting Date of Testing Load in KN strength in
in Kg strength in 1991(Part1)
N/mm2
N/mm2

1 3 Days 16 Mpa, min

2 7 Days 22 Mpa, min

3 28 Days 33 Mpa, min

Remarks:

Reference:

(i) IS: 4031-1988 (Part 6): Methods of Physical test for Hydraulic cement

BRC CSC SSCM

Sign

Name

Date
CEMENT TEST REPORT - SETTING TIME & CONSISTENCY
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/STC
EPC contractor : Badri Rai & Co Date of Testing:

ISO 14001:2004 Manufacture: Grade:


ISO 9001:2008 Type of Cement: Batch / Week No:
TEST OBSERVATION

Requirements as per IS 1489-


Sl. No. Description Observation Remarks
1991 (Part 1)

1 Normal Consistency (%) --

2 Initial Setting Time (Min.) > 30 min

3 Final Setting Time (Min.) < 600 min

Reference:

(i) IS: 4031-1988 (Part 6): Methods of Physical test for Hydraulic cement

BRC CSC SSCM

Sign

Name

Date
CEMENT TEST REPORT - SOUNDNESS
Project : Integrated Hospitality & Sports Complex, Shillong

Client : State Sports Council Meghalaya

Owner's Engineer : Shah Technical Consultant (STC) Report No. BRC/PQP/IHSC/SOU

EPC contractor : Badri Rai & Co Date of Testing:

Manufacture: Grade:
ISO 14001:2004
ISO 9001:2008 Type of Cement: Batch / Week No:
TEST OBSERVATION
Distance between the
Distance between the
Qty of Water added (0.78 points of Indicator
points of Indicator
times the water required for after 24 hours in Diff. between the
Sl. No. Wt. of Sample (gms) after keeping the Remarks
standard consistency to be Water at a indicator readings.
water boiling for
added) temperature of 27º -
3hours
32 ºC

Reference: Average:
(i) IS: 4031 (Part-3) Test Report for Soundness Cement Average:

(ii) As per IS the distance between the two indicators should not exceed 10mm.

BRC CSC SSCM

Sign

Name

Date
CONCRETE BATCHING - CORRECTION FOR MOISTURE CONTENT &
WATER ABSORPTION
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC)
EPC contractor : Badri Rai & Co Report No.: BRC/PQP/IHSC/MC

ISO 14001:2004 Grade of Concrete : Date : `


ISO 9001:2008 Mix Ratio : Cement content : kg/m3
WATER CORRECTION TABLE W/C Ratio :

MOISTURE WATER EFF.WATER CORRECTION ON QTY AFTER CORRECTION


MATERIALS IN KGS QTY PER CUM UNIT
CONTENT ABSORPTION CORRECTION QTY Per Cu.m

CEMENT Kgs

WATER Kgs

SAND Kgs

CA - 20 mm Kgs

CA-12.5 mm Kgs

ADMIXTURE Kgs

Remarks

BRC CSC SSCM

Sign

Name

Date
CONCRETE POUR CARD

Project : Integrated Hospitality & Sports Complex, Shillong

Client : State Sports Council Meghalaya


Owner's Engineer : Shah Technical Consultant (STC)
DOC NO:
EPC contractor : Badri Rai & Co
DATE
Drawing No:
ISO 14001:2004 page 1 of1
ISO 9001:2008 Structure Name:

CONCRETE GRADE : LOCATION: QUANTITY: RCC/PCC

A.CHECKS BEFORE CONCRETING

DETAILS OF CHECK REQUIRED CHECKED REMARKS

DIMENSION

CENTER LINE

ELEVATION

SHUTTERING

REINFORCEMENT

LOCATION & NO OF POCKETS

ELECTRICAL CONDUITS. PILE LINESS ETC.

EMBEDMENTS

COVER BLOCKS PROVIDED PROPERLY

EXTRA REINFORCEMENT / DEVIATIONS :

REMARKS :

BRC CSC QC SSCM


Quality check card for Brick works
Construction/Installation Inspection Record

Project : Integrated Hospitality & Sports Complex, Shillong


Client : State Sports Council Meghalaya
DOC NO:

EPC contractor : Badri Rai & Co


DATE

Drawing No:
PAGE 01 OF 01
ISO 14001:2004
ISO 9001:2008 Structure Name:

LOCATION: QUANTITY:

DETAILS OF CHECK REQUIRED CHECKED REMARKS

The joints shall be filled with mortar of more


than 80%
≥80%

Axis displacement
≤10mm

Verticality
≤10mm

the horizontal and vertical joints gap


8~12mm

standard deviation between height and width for


pcc and pipe and anchor
±5mm

performed hole Centre displacement ≤10mm

Deviation for inside


section size

Elevation deviation
±15mm
REMARKS :

BRC CSC QC SSCM


TEST REPORT FOR FIELD COMPACTION TEST
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC)
EPC contractor : Badri Rai & Co Report No.:

ISO 14001:2004 Area: Date of Testing: `


ISO 9001:2008 Location: Report Date:
MDD: OMC:
TEST OBSERVATION
Weight of
Weight of Weight of Weight of Water Content Dry density Degree of
Wet soil Volume of Bulk Density
Sl. No. Core Identification empty core core with soil Dry Soil % (W)= (W2- (D)= compaction % Remarks
(WS)= (W2- Core (V) (B)=(WS/V)
(W1) (W2) (WD) WD)/WD)*100 (B/1+W/100) (D/MDD*100)
W1)

Reference

(i) IS : 2720 - 1983(Part-29): Methods of test for soils.


(ii) IS : 2720-1983 (Part 2): Methods of tests for soils.

BRC CSC SSCM

Sign

Name

Date
CUBE TEST REPORT
Project : Integrated Hospitality & Sports Complex, Shillong
Client : State Sports Council Meghalaya
Owner's Engineer : Shah Technical Consultant (STC)
EPC contractor : Badri Rai & Co
ISO
Tested at :Site lab Report No.: BRC/PQP/IHSC/CTR
14001:2004
ISO 9001:2008 Grade of concrete :
7 days Result 28 days Result Signature
No.of
Date of Structure / Identifica Average Average
Sl.No cubes Compressive Compressive
casting Location tion No. Date of Weight of Load in compressive Date of Weight of Load in compressive
Taken strength in strength in BRC CSC SSCM Remarks
testing cube Kg KN strength in testing cube Kg KN strength in
N/mm2 2 N / mm2 2
N / mm N / mm

Reference:
(i) IS: 516 -1959: Methods of tests for strength of concrete
(ii) IS:456 -2009: Plain and reinforced concrete-Code of practice

BRC CSC SSCM

Sign

Name

Date