System No.

WW-D-0021
August 03, 2001
Construction Joints

Assembly Rating – 2 Hr
L Rating At Ambient – 4 CFM/Lin Ft
L Rating At 400 F – 6 CFM/Lin Ft
Nominal Joint Width –1 in. Max
Class II Movement Capabilities –18.75% Compression or Extension
Wall to Wall

1. Wall Assembly – Min 7-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) structural concrete. Wall may also be
constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Joint System – Max width of joint (at time of installation of joint system) is 1 in. The joint system is designed to accommodate a max
18.75 percent compression or extension from its installed width. The joint system shall consist of the following:
A. Packing Material – Nom 1-1/4 in. diameter polyethylene backer rod compressed and installed into joint. Packing material to be
recessed from each surface of wall as required to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* – Min 1/2 in. thickness of fill material applied within the joint, flush with both surfaces of wall.
3M COMPANY – FireDam 150+
*Bearing the UL Classification Mark
WWD

This material was extracted and drawn by 3M Fire Protection Products from the 2007 edition of the UL Fire Resistance Directory.
3Fire Protection Products Product Support Line: 1-800-328-1687
128 www.3m.com/firestop WW-D-0021 • 1 of 1 Choose option 4 for FAX ON DEMAND