Professional Documents
Culture Documents
Ref N° 3 - LINE SIZING PHILOSOPHY
Ref N° 3 - LINE SIZING PHILOSOPHY
&
CONSTRUCTION
GLOSSARY 3
1. INTRODUCTION 5
1.1 Foreword 5
1.2 Objectives 5
1.3 Scope of Document 5
7. REFERENCES 16
The following terms are generic to each Project and may be referred to in this
document:
Definitions
The following definitions are generic to each Project and may be referred to in this
document:
Company SONATRACH
Contractor The contractor selected by the Company to carry out the
engineering, procurement, construction and commissioning
(EPC) of those elements of the project and includes the
Contractor's personal representative, successors and
permitted assignees.
Subcontractor The subcontractor assigned a portion of the EPC contract by
Contractor as allowable.
Terminology
1.1 Foreword
1.2 Objectives
The purpose of this document is to outline the methods and design criteria to be used
for sizing process and utility lines.. These guidelines should be used in conjunction
with other project process design philosophies.
Line sizing must satisfy both pressure drop and flow velocity requirements. In
general, the more onerous condition of the two will dictate the line size. Consideration
shall also be given to erosion, corrosion and noise criteria.
The line sizing criteria have also been developed with the aim of providing optimal
sizing (minimise lifecycle cost), thus preventing excessive cost, weight and space
requirements of installed piping.
The criteria should not to be applied as fixed rules without regard to sound
engineering judgement. In addition, deviations are acceptable where they can be
justified.
The following non-standard line sizes will not be used for in-plant pipework:
For pressure drop calculations, the following roughness values will be used for the
selected material:
Where detailed pressure drop calculations are performed, pipe fitting equivalent
lengths will be taken from refs. 1-3.
The design margins for piping rated capacity are listed in Process Basis of Design
other margin shall be applied for pressure drop calculations.
Inlet and discharge piping and valves shall be at a minimum the same size as the
machinery inlet nozzle. Larger pipe sizes than the machinery nozzle are acceptable.
3.1.1. Materials
The maximum allowable fluid velocities depend on the piping material and are
summarised below in Table 3.1. These criteria are for normally sand free liquids.
Maximum Velocity
Pipe Nominal (m/s)
Diameter
Carbon Steel and Stainless Steel /
GRP Duplex
<2” 2 2
2" 2 2
3" 2.5 2.5
4" 3 3
6" 4 4
8" 5 5
>8" 6 (5 For GRP) 7
When the service is intermittent the maximum velocities specified in Table 3.1 can be
increased, provided that water hammer is not a problem.
Where solids are expected, a minimum velocity of 0.8 m/s should be maintained to
avoid solids deposition. For erosional velocity limits refer to section 5.1.
Pressure drop criteria and additional velocity constraints for specific cases are
summarised in the following sections.
Centrifugal Pumps
The maximum allowable velocities and unit pressure drop for pump suction and
discharge lines are summarised in Table 3.2.
Reciprocating Pumps
Due to pulsation and acceleration effects, lower flowing velocities are required
(compared to centrifugal pumps). The acceleration head effect is proportional to pipe
length, velocity, pump speed and a factor depending on the number of plungers in the
pump (the acceleration effect decreases as the number of plungers is increased).
Installation of pulsation dampers on both the suction and the discharge lines is to be
considered and can potentially eliminate suction acceleration head losses. The data
in Table 3.3 is based on a single plunger pump, and should be used for estimating
purposes only.
Generally, these lines will be sized on the maximum velocity limits shown in Table
3.1. However, the actual pressure drop should not exceed 35% of the driving
pressure when the flow rate is controlled by a control valve. For liquids at, or close to
the bubble point, flashing upstream of control valves should be minimised and a
maximum velocity of 4.6 m/s is recommended.
To prevent solids deposition in sewage and open drain lines, the minimum flow
velocities listed in Table 3.4 are required.
Drain lines will in general be a minimum 2" and a minimum 4" for lines containing dirty
fluid and for drain headers.
For near horizontal piping, gas entrainment will be avoided by designing for partially
full pipes. The line capacity can be calculated from:
Q = VL A (3-1) [ref. 1]
where:
A = actual inner cross sectional area in the pipe (m2) x 0.5 (50% of
pipe is liquid full) or 0.8045 (75% of pipe is liquid full).
Q = Line Capacity (m3/s).
VL =Flow Velocity (m/s) calculated from:
0.22 *
VL 32 * g * rh * i * log10 (3-2) [ref. 6]
14.8 * rh
rh * g * rh * i
where:
g = gravity, m/s2
rh = hydraulic radius, m
i = inclination, m/m ( 1 : 100 i = 0.01 )
= pipe roughness, m (use 0.00025 m)
= kinematic viscosity of the flowing liquid, m²/s
For pipes larger than or equal to 8", design for 75% (in diameter) full of liquid:
For pipes less than 8", design for 50% full of liquid:
where:
½
v < 0.94 d (3-6)
where:
Fr = Froude no.
v = velocity, m/s
d = inside diameter, m
g = gravitational acceleration, m/s2
4.1. General
When sizing gas lines the sizing criteria will be a compromise between the maximum
velocity (Section 4.2) and allowable pressure drop (Section 4.3). Where pressure
drop is not critical the requirements in Section 4.2 should be used. Where the
pressure drop is critical, the recommendation in Section 4.3 should be used. The
pressure drop is considered critical when:
The cost increase due to additional power requirement is larger than the
potential cost savings due to reduced pipe diameter.
It results in unacceptable liquid drop out in suction lines e.g. between KO
drum and compressor suction, inlet lines to turbo-expanders and upstream
glycol contactors.
Piping with gas at the dewpoint and/or with some droplets shall be designed as gas
lines.
In lines where pressure drop is not critical (See Section 4.1), gas velocity shall not
exceed limits which may create noise or vibration problems (for erosional velocity
criteria for 2 phase lines refer to section 5.1). As a rule of thumb, the velocity should
be kept below:
where;
Vmax = velocity m/s.
= density of gas kg/m3
To avoid excessive noise, the valve manufacturer should be consulted for line sizing
and arrangement upstream and downstream pressure control valves
For compressor anti-surge lines the constant 175 in the formula above may be
replaced with 200 during process upsets, if the noise level is acceptable. However,
during normal compressor recycle, the velocity shall be limited to the velocity as given
by the equation above.
Special attention shall be given to particle erosion if solid particles are present.
Where pressure drop is critical (see Section 4.1) the guidelines in Table 4.1 [ref.13]
should be used. The pressure drop should be pro-rated between the operating
pressures given.
Table 4.1 - Maximum Pressure Drop for Single Phase Gas Process Lines
For plant air, instrument air and inert gas distribution, the maximum pressure drop to
be used is 0.1 bar / 100 m. The maximum flowing velocity is as given in Section 4.1,
but also giving consideration to the noise criteria for the line.
Lines, which exhibit two-phase flow, are designed in accordance with API RP 14E.
This design approach assumes fluids are sand free.
Va,max < ve
ve = C / a (5-1) [ref. 3]
where:
But consider 25% higher value of C for lines in intermittent or temporary service.
A factor of 0.8 is to be applied to de-rate for sand production, and should be applied
as appropriate. For critical process lines, the actual pressure drop shall be calculated
to check with available pressure drop.
The sizing of all individual relief lines must be fully analysed in Detailed Engineering
to provide an optimum system design of header sizing and back pressures.
Reference should be made to API RP 520 [ref. 8] and API RP 521 [ref. 7].
The flowing velocity in flare headers will be a nominal maximum of 0.5 mach.
The flowing velocity in sub-headers and tail pipes will be normally less than 0.7 Mach.
105 * k * P
Sonic velocity: C (6-1)
where:
Calculations should consider maximum rated flow based on relief valve installed area
and not just the design relieving rate.
The maximum PSV back pressure should be less than 10% of the set pressure for a
conventional (spring loaded) valve, and 30-50% for a balanced or pilot operated
valve.
The flowing velocity in the line from the PSV to the downstream header should be a
maximum of 0.7 mach. Sonic velocity must be avoided by stepwise increasing the
pipe size. The actual back pressure at the PSV outlet must be checked to be
consistent with back pressure limitations.
Acoustic induced vibration fatigue must be considered for large relief flow rates.
Acoustic induced vibration fatigue must be considered for large controlled flaring
lines.
Design of the lines upstream of the restriction orifice shall be based on a flow velocity
that gives v2 < 200,000 kg/m.s2. The blowdown line size and orifice shall be sized
based on the peak depressurisation flowrate from the blowdown analysis..
The flow velocity downstream the restriction device shall be maximum 0.7 mach.
If the line is in frequent use (maintenance) a lower maximum flow rate to reduce the
noise level should be considered. The same applies to pipeline blowdown system.
The design (size, velocity and material) should be consistent with ref. 15
1. Flow of Fluids through Valves, Fittings and Pipe, Crane Technical Paper 410.
2. Gas Processors Suppliers Association (GPSA) - Engineering Data Book, 1980.
3. API RP14E, Recommended Practice for Design and Installation of Offshore
Production Platform Piping Systems, Fifth Edition, October 1, 1991.
4. Pressure Drop for Flow of Fluids in Round Pipe, L. Friend & L. Samiloff.
5. Chemical Engineering Series - "Practical Piping Design"
6. Designing Piping for Gravity Flow, P. D. Hills, Chemical Engineering, 5 September
1983.
7. Guide for Pressure Relieving and Depressuring Systems, API RP 521, 5th Edition
- January 2007
8. API RP 520, Sizing, Selection, and Installation of Pressure-Relieving Devices in
Refineries, Part II, Fifth Edition, August 2003.
9. Evaluation of API RP 14E, Erosional Velocity Limitation for Offshore Gas Wells,
OTS paper 4485, 1993.
10. API RP 2000, Venting Atmospheric and Low Pressure Storage Tanks, Non-
Refrigerated and Refrigerated, Fifth Edition, April 1998
11. NFPA Appendix A
12. "Alternate to Standard Friction Factor Equation", Oil & Gas Journal April 1 1985.
13. NORSOK Standard, Process Design, Document No. P-001, Rev. 4, Oct. 1999.
14. Salama, M.M., and Venktash, E.S., "Evaluation of API RP 14E Erosional Velocity
Limitations for Offshore Gas Wells," Paper no. OTC 4485, 15th Offshore
Technology Conference, Houston 1983
15. Sonatrach Operational Philosophy: Relief, Blowdown and Venting, A-014-01-2005
Relief