4.29 Earthquake Protection. 4.29.3.4.1* Where seismically protecting smaller diameter trim
lines, restraint shall be sufficient.
4.29.1 General. Where water-based fire protection systems to
be protected against damage from earthquakes, 4.29.2 and 4.30 Packaged Fire Pump Assemblies.
4.29.3 shall apply.
4.30.1 A packaged fire pump assembly, with or without an
4.29.2* Seismic Loads. Horizontal seismic loads shall be deter‐ enclosure, shall meet all of the following requirements:
mined in accordance with NFPA 13; SEI/ASCE 7, Minimum (1) The components shall be assembled and affixed onto a
Design Loads for Buildings and Other Structures; local, state, or steel framing structure.
international codes; or other sources acceptable to the author‐ (2) Welders shall be qualified in accordance with the
ity having jurisdiction. Section 9 of ASME Boiler and Pressure Vessel Code or with
4.29.3 Components. the American Welding Society AWS D1.1, Structural Weld‐
ing Code — Steel.
4.29.3.1 Pump Driver and Controller. The fire pump, driver, (3) The assembly shall be listed for fire pump service.
and fire pump controller shall be attached to their foundations (4) The total assembly shall be engineered and designed by a
with materials capable of resisting applicable seismic loads. system designer as referenced in 4.3.2.
4.29.3.2* High Center of Gravity. Pumps with high centers of (5) All plans and data sheets shall be submitted and reviewed
gravity, such as vertical in-line pumps, shall be mounted at their by the authority having jurisdiction, with copies of the
base and braced above their center of gravity. stamped approved submittals used in the assembly and
for record keeping.
4.29.3.3* Pipe and Fittings. Pipe and fittings shall be protec‐
ted in accordance with NFPA 13. 4.30.2 All electrical components, clearances, and wiring shall
meet the minimum requirements of the applicable NFPA 70
4.29.3.4 Appurtenances. Seismic protection of appurtenances, articles.
including trim pieces, shall be required where they are essen‐
tial for post-earthquake operation of the fire pump.
2016 Edition