PROJECT:

PANEL LP-EX
CIRCUIT: 1
Voltage volt 380
Cable Size mm2 10 CU/XLPE/PVC
Power Factor 0.8
Resistance at 85 0C ohm/m 0.0023
Reactance ohm/m 0.000109

Pole ID Number DISTANCE Power 0f each Ampere of Total VD in VD at end of Percentag


between Lighting pole each Amps in each each section e voltage
poles POLE each section (accumulative) drop
section (%VD)

m VA A A VOLT VOLT % 1
1 50.00 2,500.00 3.80 11.40 2.17 2.17 0.57
2 25.00 2,500.00 3.80 7.60 0.72 2.89 0.76 2
3 25.00 2,500.00 3.80 3.80 0.36 3.26 0.86
Maximum ampere of circuit Ampere 11.40
Maximum voltage drop % 0.86
Selected Cable mm2 10.00
NOTES:
Calculation for VD of 1phase, is using this formula √ 3× L×I ( R×cosϕ+X ×sin ϕ )
2xLxI(Rxcos(phi)+XxSin(Phi))

703429333.xls/SLP1-Z03-1 3PH 11/08/2023