Safety Cautions

Read the entire "Instruction Manual" carefully for important information about safety, handling,
installation, operation, maintenance, and parts replacements.
This equipment is designed and built in accordance with applicable safety standard in effect on
the date of manufacture. Unauthorized modifications will void warranty and can result in severe
injury, death and property damage. Do not make any modifications to the equipment.
Only qualified persons are to install, operate or service this equipment according to all applicable
codes and established safety practices.
Use only genuine Toshiba replacement parts and accessories. Improper components could cause
the equipment malfunction.
Do not install this equipment in areas where unusual service conditions exist. Using this
equipment in other than usual service conditions can result in equipment failure.
Do not exceed the ratings specified on the equipment nameplate or system accessories.
Underrated equipment can fail during operation causing fire, explosion, severe injury, death, and
property damage.

TRANSMISSION DISTRIBUTION & INDUSTRIAL SYSTEMS COMPANY


1-1, SHIBAURA 1-CHOME, MINATO-KU, TOKYO 105-8001, JAPAN

http://www3.toshiba.co.jp/sic/english/swgr/products.htm

The data given in this catalog are subject to change without notice.

CMO23 AD
2010-8 Printed in Japan
Having successfully supply the vacuum switches to practical use in 1965
for the first products in Japan, Toshiba has been producing various
types of vacuum apparatus which are now widely used as a result of their
outstanding performance.
Excellent Breaking Performance
Currently producing vacuum circuit breakers, vacuum contactors, and Since the arc in vacuum disperses at high speed and
extinguishes almost at the first current zero, Toshiba vacuum
pole mounted vacuum switches, Toshiba has become a leader of
circuit breakers are appropriate for high-speed breaking and
manufacturers of vacuum interrupters and vacuum technology for such rapid reclosing. The vacuum enclosure is sealed so that it's
breaking performance is not changed by the effect of external
devices by following items: atmosphere.
(1) By using axial magnetic field type electrode for VCB,
following features can be obtained. High Reliability
Toshiba vacuum circuit breakers are produced under an
(a) Contact erosion by arc can be reduced integrated quality control system ranging from design through
production. Especially the vacuum interrupters (the ÒHEARTÓ
(b) High Interrupting current can be applied of vacuum circuit breakers) are produced to ensure high
(c) Compact size reliability by assembling them in a modern Òclean roomÓ and by
using a high vacuum degassing furnaces.
(2) Brazed in Vacuum furnace
The vacuum interrupters are assembled in vacuum furnace, Safety for Personnel and Operating Safety
the exhaust pipe is deleted and the reliable vacuum is realized. The vacuum circuit breaker dose not require any other media for
arc extinction, hence there is no emission product which could
(3) Long experiences in manufacturing give rise to explosion or the hazard.
Since the introduction of the first vacuum interrupter in 1962,
Toshiba has been continuously improving and developing Minimized Maintenance/Inspection
Since the main contacts are sealed in a vacuum envelope, and
vacuum technology. Over 3.2 million Toshiba vacuum having low contact wear characteristics, the inspection and/or
maintenance will be minimized. Further the operating mechanism
interrupters have been manufactured and are providing reliable
offers easy maintenance and long-life thanks to the special
service in a wide variety of applications worldwide. mechanism involving less energy. Also the operating
mechanism is mounted on the front and control circuit
Processing superb features in that maintenance/inspection component are arranged on a printed board,
maintenance/inspections will be performed easily. Replacement
service is reduced and safety is secured without using any media, parts such as tripping coil, closing coil in mechanism and
the vacuum circuit breaker has become a leading product vacuum interrupter, are easily inspected and replaced.

among circuit breakers of 36kV


Compact and Light
and below. The reliable insulation material/structure and efficient mechanism
Toshiba Vacuum Circuit make the vacuum circuit breaker compact and light weight.
Toshiba vacuum circuit breakers offer simplified installation and
Breakers enjoy popularity operation, and realize lightweight and compact switchgear and
multi tiers construction of cubicle.
for their excellent quality
proved by the longest
operation period.

1 2
Refer to Table 1 for selecting the Type-Form of TOSHIBA Vacuum Circuit Breaker.
Then refer to Table 2 for more detailed information. Table 1 Selection Table
Interrupting
current 12.5kA 16kA 20kA 25kA 31.5kA 40kA 50kA
Voltage

3.6kV

VHA-6J13S (630A)
VZ-6M40 (1250A)
V6A- (600A) VHA-6 J 20S ( 630A) VZ-6 J 25 ( 630A)
VZ-6J16 (630A) VZ-6M32 (1250A) VZ-6P40 (2000A)
7.2kV V6AS- (600A) VHA-6M20S (1250A) VZ-6M25 (1250A)
VZ-6P32 (2000A) VZ-6Q40 (3150A)
VZ-6P25 (2000A)
VZ-6R40 (4000A)

VZ-10M40 (1250A) VZ-10M50 (1250A)


12kV (630A) VZ-10J25 ( 630A) VZ-10P40 (2000A) VZ-10P50 (2000A)
VZ-10J16
VZ-10M25 (1250A) VZ-10Q40 (3150A) VZ-10Q50 (3150A)
VZ-10P25 (2000A) VZ-10R40 (4000A) VZ-10R50 (4000A)

VZ-2 0 J 25 ( 630A) VZ-20M40 (1250A)


VZ-2 0 J 16 ( 630A) VZ-20M25 (1250A) VZ-20P40 (2000A)
24kV
VZ-20M16 (1250A) VZ-20P25 (2000A) VZ-20Q40 (3150A)

36kV VY-30M25A (1250A)


VY-30P25A (2000A)

3 4
Table 2 Rating and specifications

Type V6A, V6AS * VHA VZ VZ VZ VY

Type-Form MU 6M40 10M40 10M50


U 6J25 10J25 20J25 20M40
Form L ML 6M32 6P40 10P40 10P50 20J16 30M25A
6J13S 6J20S 6M20S 6J16 6M25 10J16 10M25 20M25 20P40
T MT 6P32 6Q40 10Q40 10Q50 20M16 30P25A
6P25 10P25 20P25 20Q40
MLD 6R40 10R40 10R50

Voltage (kV) 7.2 3.6/7.2 7.2 12 24 36

M : 1250 M : 1250 M : 1250


J : 630 J : 630 J : 630 M :1250
M : 1250 P : 2000 P : 2000 P : 2000 J : 630 M : 1250
Current (A) 600 600 630 630 1250 630 M : 1250 630 M : 1250 M : 1250 P : 2000
P : 2000 Q : 3150 Q : 3150 Q : 3150 M : 1250 P : 2000
P : 2000 P : 2000 P : 2000 Q : 3150
R : 4000 R : 4000 R : 4000

Frequency (Hz) 50/60 50/60 50/60


Rated

Interrupting current (kA) 12.5 12.5 16/12.5 25/20 25/20 16 25 31.5 40 16 25 40 50 16 25 40 25

Making current (kA) 31.5 31.5 40/31.5 63/50 63/50 40 63 80 100 42 65 104 130 40 63 100 63

Short-time current (kA) 12.5-2s 12.5-2s 16-3s 25-3s 25-3s 16-3s 25-3s 31.5-3s 40-3s 16-3s 25-3s 40-3s 50-3s 16-3s 25-3s 40-3s 25-3s

Interrupting time (cycle) 3 3 3 3 3 3

Opening time (ms) 30 20 30 30 40 40 30 40 25

No-load closing time (ms) ---- 300 50 40 40 40 50 40 50 55

Impulse (kV) 60 60 60 75 125 170


Insulation
level
Power Freq. (kV) 22 20 20 28 50 70

Operating duty O - 1min. - CO - 3min. - CO O - 3min. - CO - 3min. - CO O - 3min. - CO - 3min. - CO O - 3min. - CO - 3min. - CO

Closing system Manual Op. Motor Op. Motor Spring Operation Motor spring operation Motor spring operation

Voltage (V) ---- 100AC/100DC DC110 DC110 DC110 DC110 DC110 DC110 DC110
Closing
Current (A) ---- 1.0/1.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

Voltage (V) DC110 DC110 DC110 DC110 DC110 DC110 DC110 DC110
Tripping
Current (A) 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

Mechanical switching life (times) 10,000 10,000 10,000 10,000

Load switching life (times) 10,000 10,000 10,000 10,000

Numbers of auxiliary switch-contacts 2NO-2NC 4NO-4NC 4NO-4NC 4NO-4NC

MU : 23 M : 105 M : 105 M : 160


U : 21 J : 80 J : 80 J : 160 M : 290
ML : 26 M : 105 P : 125 P : 125 P : 175 J : 160 M : 270
Weight (kg) L : 24 43 50 78 80 M : 95 80 M : 105 M : 180 P : 325
MT : 26 P : 125 Q : 240 Q : 240 Q : 295 M : 180 P : 300
T : 24 P : 125 P : 125 P : 220 Q : 340
MLD : 37 R : 315 R : 315 R : 360

M : UKP-6MS3 M : UKP-10MS2
J : UKP-6JS J : UKP-10JS M : UKP-10MS3 J : UZP-20JS M : UZP-20MS1
Applicable draw-out unit M : UKP-6MS3 P : UKP-6PS2 P : UKP-10PS2 J : UZP-20JS M : UYP-30MS
---- U6A-HLS UHA-6JPS UHA-6MPS J : UKP-6JS M : UKP-6MS J : UKP-10JS M : UKP-10MS P : UKP-10PS3 M : UZP-20MS P : UZP-20PS1
P : UKP-6PS2 Q : UKP-10QS Q : UKP-10QS M : UZP-20MS P : UYP-30PS
P : UKP-6PS P : UKP-10PS Q : UKP-10QS P : UZP-20PS Q : UZP-20QS1
R : UZP-6RS R : UZP-10RS

* indicated breakers are comformed to JIS, JEC (Japanese standards) only

5 6
V 6 A S M L D 1. FIXED TYPE (MANUAL OPERATION)
Vacuum circuit breaker
Ratings
6 : 7.2/3.6kV-600A-12.5kA 188
Center line of front cover
162 206 185 120 120 143
Series 150 150
136 136 3.2 30 123
Vacuum interrupter 50 11 12
No symbol : General type 9 8
13 1 5 14 9 10
S : Low surge type

20
Closing system

343
6

288

255
255

250
243
No symbol : Manual operation

204
2

174
M : Motor spring operation 7
Main terminal position

12
3
U : Right and left on the top 152 138 114 375.5
3 8 8 Center line
73 500
L : Upper and lower at the rear of front cover
T : Front and back on the top 4
Installation Fig. 1 Types V6A(S)-U Vacuum circuit breakers
No symbol : Fixed type
D : Draw-out type
Center line of front cover
173 266
150 205
120 120
148 150
136 136 3.2 20 60.5
50
11
5 30
Table 3 List of specifications for V6A series 14 10 13 12
13 1 5 6

8
Motor spring operation type Manual operation type 9
Applicable standards JIS C 4603, JEC-2300 JIS C 4603

143
Control circuit connection Plug connection Terminal connection

310

9
243

204
Closing voltage and method 1. 100/110VDC Manual operation

174
2 7

129
2. 48/50VDC
3. 100/110VAC
silicon rectifier

3
3
3

12
88.5 114 230 8
4. 200/220VAC 8 Center line of front cover
silicon rectifier 304.5 (Rear side) 354
4
114.5 73 442
Tripping voltage 1. 100/110VDC 1. CT trip
2. 48/50VDC 2. CT trip and shunt trip 355.5 (Front side)
3. 100/110VAC (100/110VADC)
capacitor tripping 3. 100/110VDC Fig. 2 Types V6A(S)-L Vacuum circuit breakers
4. 200/220VAC 4. 100/110VAC
capacitor tripping capacitor tripping
Auxiliary contacts arrange Center line of front cover
2NO, 2NC (STD) 2NO, 2NC (STD)
281 39
5NO, 5NC (MAX) 5NO, 5NC (MAX)
150 205
Silicon rectifier and capacitor tripping device shall be installed 148 150 228 143 120 120
NO. Description
in the switchgear and may be ordered as accessories.
136 136 1 Panel installation bolt (4 - M8)
3.2 9 8 30 86
50
12 11 2 Tripping lever
1 5 6 9 14 10 3 Front cover

5
4 Operation counter
5 OPEN-CLOSE indicator

20
343
6 Closing handle

292
255

255
204
2 7 Auxiliary contact
174

13 13 8 Floor mounting ( 9 - 4 Holes)


9 Mounting panel

3
12
3

109 290 Center line of front cover 10 Terminal board


3 4 8 7
73 409
11 Main terminal ( 14 Hole)
105 270.5
12 Insulation tube
13 Auxiliary switch (Option)
Fig. 3 Types V6A(S)-T Vacuum circuit breakers 14 Earthing terminal

7 8
Operating circuit (Open and discharged condition)
2. DRAW-OUT TYPE (MOTOR SPRING OPERATION)

A B C P
16 15 14 13 12 11
K a2 a1 b2 b1
Center line of VCB
247 No. Description b6 b5 b4 a6 a5 a4
396 a3 a2 a1 b2 b1
233 1 OPEN-CLOSE indicator
230 230
34 104
11 7
35 Center line
2 Opening lever
VCB TC3
of VCB
1 3 Front cover
26 25 24 23 22 21
5 6 4 Operation counter N2 a02 a01 b02 b01
12 N

144
Interlock Lever

Secondary Disconnects 5 Handle


10 Option
371

10 6 Interlock release lever


13 8 7 Primary disconnector OCR I> I> OCR

185
2 8 Secondary disconnector Internal of VCB
9 9 Aux. disconnector (Option) 2 X CT
438
61
3 20 330 120 120 10 Auxiliary switch (Option)
11 Symbol Description
490 11 Earthing terminal E
4 12 Shaft for closing handle K N2 a1 a01 a2 a02 b1 b01 b2 b02 VCB Vacuum circuit breaker
13 Spring indicator A, B, C Phase
Terminal arrangement
Fig. 4 Types V6A(S)-MLD Vacuum circuit breakers CT Current transformer
E Ground
TC3 Voltage trip coil
a1 - a6 Auxiliary contact (N.O.)
b1, b2, b4 - b6 Auxiliary contact (N.C.)
3. DRAW-OUT UNIT Overload relay
OCR
Fig. 6 Connection diagram for manual operation with shunt trip
4 5

PR3 P2 PR4
150

130
120

A E ON E OFF
513

464

550

a1 b1 b6 b5 b4 a6 a5 a4
A PR3 H K a2 b2
15
130
150

IL

NR RF
"B" D
a3 a2 a1 b2 b1 b6 b5 b4 a6 a5 a4
X-a

No. Description Y-b


Y-a LS1
2 5 24 1 Primary terminal LS2 X-a
Symbol Description
12 - 6 holes 2 Mounting hole Charging motor
80 260 250 R4 M
3 Earthing terminal (M8 Screw) M R2 Y-b TC TC Trip coil
X-b
4 Guide for lifter a02 b02
a1 - a6 Auxiliary contact (N.O.)
80 546 X-a R3 a01 b01 b06 b05 b04 a06 a05 a04
5 Bolt for preventing full draw-out b1, b2, b4 - b6 Auxiliary contact (N.C.)
R1
Disconnected position
Connected position

172 180 6 Shutter C


LS3 X Y OPTION X Control relay
70 10 7 Lifting hole (2 Holes) RL GL X-a Control relay N.O. contact
7 X-b Control relay N.C. contact
R7 NT3 N2
15

7 1 14
Y Auxiliary relay
NT3 N2 NT4
70

Y-a Auxiliary relay N.O. contact


30

17 16 15 14 13 12 11 10
8

Y-b Auxiliary relay N.C. contact


PR3 NT3 H a1 a2 b1 b2 LS1 - LS3 Limit switch
VCB 20 Green
144

K N2 a01 a02 b01 b02 IL Interlock switch


450
8

9 8 7 6 5 4 3 2 1 R1 - R4 Resistor
6 Detail of "B" Rectifier
17 16 15 14 13 12 11 10 RF
VCB Internal connection
183

a4 a5 a6 b4 b5 b6 D Diode
Printed circuit board White Option
100

a04 a05 a06 b04 b05 b06 C Capacitor


9 8 7 6 5 4 3 2 1 NR Surge suppressor
43

10 90 RL, GL Lamp
3 Arrangement of secondary disconnectors
650

Section A-A
Fig. 7 Connection diagram of motor operation
Fig. 5 Type U6A-HLS Draw-out unit

9 10
V H A 6 J 13 S
Vacuum circuit breaker
Series symbol
HA : series

Voltage class 423


6 : 7.2/3.6kV 410 28 30 307 125 125
Rated current 2
J : 630A, M : 1250A
VACUUM CIRCUIT BREAKER

Rated interrupting current 8 7


13 : 12.5A, 20 : 20/25kA OPERATION COUNTER

Vacuum interrupter
CLOSING OPERATION TRIPPING OPERATION
5
S : Low surge type CLOSING BUTTON

240
1

462

25
10 TRIP BUTTON
4
VCB DRAWING IN/OUT OPERATION
DRAWING IN OPERATION

9 VACUUM CIRCUIT BREAKER DRAWING OUT OPERATION

178

152
15
10
Table 4 List of specifications for VHA series 6 11
Items Standard type Changeable scope of spec 450
Applicable standard IEC 62271-100 JEC 23008
Installation method Draw-out Fixed with wheel
Control circuit connection Plug with Interlock Plug connection Fig. 8 Types VHA-6J13S, 6J20S Vacuum circuit breakers
(SC connector)
Closing voltage and method 100/110VDC 1. 48/50VDC
Motor spring 2. 100/110VAC
silicon rectifier
3. 200/220VAC
silicon rectifier 39 458
467 44 338 165 165
Tripping voltage 100/110VDC 1. 48/50VDC 2
2. 100/110VAC 10 12
capacitor tripping
3. 200/220VAC VACUUM CIRCUIT BREAKER

9
capacitor tripping
Auxiliary contacts arrange. 4NO,4NC VCB DRAWING VCB DRAWING
IN/OUT INTERLOCK LEVER 7

298
IN/OUT INTERLOCK LEVER

130
OPERATION COUNTER

CLOSING OPERATION TRIPPING OPERATION CHARGING OPERATION


OF THE CLOSING SPRING
5
Silicon rectifier and capacitor tripping device shall be installed in
switchgear and may be ordered as accessories. CLOSING BUTTON

625
3
1 TRIP BUTTON

4
6

348

291
VCB DRAWING IN/OUT OPERATION
DRAWING IN OPERATION DRAWING OUT OPERATION
VACUUM CIRCUIT BREAKER

15
CONNECTED /DISCONNECTED POSITION

24
13 11

Fig. 9 Type VHA-6M20S Vacuum circuit breaker No. Description


1 Secondary disconnector
2 Primary disconnector
3 Closing button
4 Opening button
5 Opening for charging handle
6 OPEN-CLOSE indicator
7 Spring charge indicator
8 Operation counter
9 Interlock release lever
10 Handle
11 Earthing terminal
12 Hook for lift
13 Opening for draw-out handle

11 12
Dimensions (Draw-out unit) Operating circuit (Open and discharged condition)

15 3 12 - 6 Holes
M8 X 45 - 2 Bolts 7 43
4 1 7 5
M8 Nut P1 Printed P3 P2

25
150 Circuit
120 CLOSE Board OPEN
A2 A3 A4 A5 B2 B3 B4 B5

36
H P3 K
150

M12 Screws Depth 18 9 6


Detail of primary terminal
7 14
115 225 200

85 100 480 IL
510
30 450
25 130 130 LS3 C1 R1 LS1
16 - 2 Holes 5
VCB 10
M8 - 2 Screws
Disconnected position

Secondary disconnector for partition


Connected position

6 C2 Y-b Y LS2-a
40
25

350
500
12
1 a2 a3 a4 a5 b2 b3 b4 b5
LS2-b
300
233

Handle b1 Y-b R2
181

Mounting surface
100

4 a1
74

108 (Blank portion) 2


16 - 2 Holes 5 11 R3 R4 M
600

CC D2 TC
Fig. 10 Type UHA-6JPS Draw-out unit
13 16
15
4 17 - H8 3 12 - 4 Holes
D1 D4
D3

5
40
165
120

N3 N2
550
340

600

A02 A03 A04 A05 B02 B03 B04 B05


60
80
165

40

N3 N2

2
M12 - 4 Screws Depth 20
8 60 450 1 2 3 4 5 6 7 8 9 10 11 12
Detail of primary terminal P3 H K a2 a3 a4 a5 b2 b3 b4 b5
150 514 20 N3 N2 a02 a03 a04 a05 b02 b03 b04 b05
5 16 - 2 Holes
39 420 510 Symbol Description 13 14 15 16 17 18 19 20 21 22 23 24
1 CC Closing coil
85
TC Tripping coil SC connector
85

M Charging motor
170
Disconnected position

Secondary IL Interlock switch


Connected position

10 - 2 Holes
disconnector LS1 - LS3 Limit switch
6 for partition
298

a1 - a5 Auxiliary contact (N.O.) P3 N3 a2 a3 a4 a5


160

11 12 13 14 15 16 17
700

b1 - b5 Auxiliary contact (N.C.)


a02 a03 a04 a05
57

D1 - D4 Diode 21 22 23 24 25 26 27
7 R1 - R4 Resistor H b2 b3 b4 b5
Mounting
294
263

surface C1, C2 Capacitor 31 32 33 34 35 36 37


K N2 b02 b03 b04 b05
41 42 43 44 45 46 47
12
2 Plug interlock connector
77

706 (100)
No. Description
16 - 2 Holes 5 806 1 Primary terminal Arrangement of secondary disconnector
2 Earthing terminal (38mm2) (Front view )
3 Mounting hole
Fig. 11 Type UHA-6MPS Draw-out unit 4 Guide for lifter
5 Lifting hole
6 Shutter
7 Pin (Bolt) for preventing full draw-out
8 Support for draw-out handle (6MPS only) Fig. 12 Connection diagram 100/110VDC for VHA- breaker

13 14
V Z 6 M 25
Vacuum circuit breaker
Series symbol
Z : series
7
Voltage class 40 535
6 : 3.6/7.2kV 10 : 12kV 20 : 24kV 466 380 9 165 165
8
Rated current
6 10
J : 630 (600)A, M : 1250 (1200)A 1
P : 2000A, Q : 3150 (3000)A
R : 4000A 2

B
12
Rated interrupting current 4

625
16 : 16kA, 25 : 25kA, 5
32 : 31.5kA, 40 : 40kA 11
3

A
497 390
508

Type A B
Table 5 List of specifications for VZ series VZ-6J16, VZ-6J25
VZ-10J16, VZ-10J25 289 302
Items Standard type Changeable scope of spec
Applicable standards VZ-6M25 291 298
IEC 62271-100 JEC 2300
Installation method Draw-out Fixed with wheel
Control circuit connection Plug with Interlock Plug connection
Fig. 13 Types VZ-6J16, 6J25, 6M25, 10J16, 10J25 Vacuum circuit breakers
(MIC connector)

Closing voltage and method 100/110VDC 1. 48/50VDC


Motor spring 2. 100/110VAC
silicon rectifier 7
40 535
3. 200/220VAC
silicon rectifier 566 380 9 200 200
8
Tripping voltage 100/110VDC 1. 48/50VDC
6 10
2. 100/110VAC 1
capacitor tripping
3. 200/220VAC 2

B
capacitor tripping 12
4

625
Auxiliary contacts arrange 4NO, 4NC 1. 5NO, 5NC(MAX) 5 11
for Plug interlock
3

A
Silicon rectifier and capacitor tripping device shall be installed in
switchgear and may be ordered as accessories.

597 390
606

Type A B
VZ-10M25 291 298
VZ-6P25 295 290 No. Description
VZ-10P25
1 Handle
2 Opening for charging handle
3 Secondary disconnector
Fig. 14 Types VZ-6P25, 10M25, 10P25 Vacuum circuit breakers 4 Operation counter
5 OPEN-CLOSE indicator
6 Spring charge indicator
7 Opening button
8 Interlock release levers
9 Primary disconnector
10 Vacuum interrupter
11 Driving rollers for shutter
12 Hole for closing operation

15 16
7
40 535
9 7 725 40 699
566
8
380 200 200 X X 9

10
1
VZ 6 12
VZ 8 230 230
1 6 85 85 85

B
2

390
4 14 4
625 13

837
5 11 10
3
2 14

335
12 3
5 11
597 390
13 700 583
606
713
Type A B
VZ-6M32, VZ-6M40 VIEW X-X
291 298
VZ-10M40
VZ-6P32, VZ-6P40
VZ-10P40
295 290 Fig. 17 VZ-6R40, VZ-10R40 Vacuum circuit breakers

Fig. 15 Types VZ-6M32, 6M40, 10M40, 6P32, 6P40, 10P40 Vacuum circuit breakers

40 680
7 670 560 230 230
X 670 X 40 670 9
543 7
9
VZ 6 10

1 VZ 8 230 230
1
8

368
2 6 76 76 76
340

14 2 13

835
4
720

10
5 4
3
3

376
295

12
11 5 11

700 550 13 697 526


711 750

VIEW X-X Fig. 18 Types VZ-20J16, VZ-20J25 Vacuum circuit breakers


Fig. 16 Types VZ-6Q40, VZ-10Q40 Vacuum circuit breakers

No. Description
No. Description
1 Handle
1 Handle
2 Opening for charging handle
2 Openning for charging handle
3 Secondary disconnector 3 Secondary disconnector
4 Operation counter 4 Operation counter
5 OPEN-CLOSE indicator 5 OPEN-CLOSE indicator
6 Spring charge indicator 6 Spring charge indicator
7 Opening button 7 Opening button
8 Interlock release lever 8 Interlock release lever
9 Primary disconnector 9 Primary disconnector
10 Vacuum interrupter 10 Vacuum interrupter
11 Driving rollers for shutter 11 Driving roller for shutter
12 Opening for driving handle 12 Driving roller for draw-out/in
13 Driving screw 13 Hole for closing operation
14 Hole for closing operation 14 Interlock pin

17 18
Dimensions Dimensions (Draw-out unit)

5 100
1 6
40 680 17.3 15 580 45
11 - 5 Holes
670 560 230 230
14
7 9 15 10 M12 - 4 Screws Depth 20

251
3

190
6 11

165
150
120
552

60

80

40
1

150

165
190
368
8

251
2 40

2 13
838

55 25 Detail of primary terminals

45
4 769
6
3

376
14 - 4 Holes 345 182 8 510
30 30 - 2 Holes
5 12

90

85
170
Disconnected position
2
697 526

Connected position
750 77 392

298

710
4
Fig. 19 Types VZ-20M16, VZ-20M25, VZ-20P25 Vacuum circuit breakers

295.5
20 40

150

100

35
38 140 75 7
926 39 771
870 541 300 300 869

10 Fig. 21 Types UKP-6JS, UKP-6MS Draw-out units

14 11 15 580 100
7 9 5 6
17.3 45
11 - 5 Holes
1 6 8 1
442

9
1010

301
M12 - 4 Screws Depth 20

240

200
13 3
4

120

60

80
652
3

40
400

200
240

301
2 40
5
12
Detail of primary terminal
891 546
55 25

45
910 15 769
6
345 182 8 600
14 - 4 Holes 30 - 2 Holes
30
Fig. 20 Types VZ-20M40, VZ-20P40, VZ-20Q40 Vacuum circuit breakers A B

90

100
UKP-6MS3 298

200
295.5
2

Disconnected position

Connected position
UKP-6PS, 6PS2 299.5 290
No. Description 77 390

B
1 Handle

710
2 Opening for charging handle
4
3 Secondary disconnector
4 Operation counter
5 OPEN-CLOSE indicator

A
20 40 No. Description
6 Spring charge indicator

150
1 Primary terminal

100
7 Opening button
8 Interlock release lever 2 Shutter device (Insulation)

35
9 Driving cam 38 140 100 7 3 Earthing plate
869 4 Guide rail
10 Primary disconnector
11 Vacuum interrupter 5 Connecting boss for lifter
12 Driving roller for shutter 6 Mounting hole
13 Hole for closing operation Fig. 22 Types UKP-6MS3, UKP-6PS, UKP6PS2 Draw-out units 7 Hole for earthing wire
Opening for driving handle 8 Lifting hole
14
15 Hole for lift 9 Opening for driving screw

19 20
45 11 - 7 Holes
15 580 120 25 6 1
5
17.3 6 14 - 6 Holes

25
15 715 120 11 - 7 Holes

299
M12 - 4 Screws Depth 20
6

230
190

3 60 1

165
150

100
130
120

5 6

50
60
80

40
552

657
17.3 11 - 6 Holes

150
165
190

230
2 40 50

299
3 M12 - 4 Screws Depth 20

420
340
Detail of primary terminal Detail of primary terminal

300

230
30 50 45

120
756

899
100 8 30 - 2 Holes
769
9 50 75
50

345 182 510 15 - 2 Holes

230
6 36

300

340
DISCONNECTED POSITION

420

10.5
90
CONNECTED POSITION

56
3
85

36
170

2
60
298

77 392 Detail of earthing terminal


30 50

60
710

110
4 904 8 30 - 2 Holes
710
400 150

50
20
295.5

40
150

DISCONNECTED POSITION
100

70
CONNECTED POSITION
35

75 7

115
38 140

230
869 2

340
Fig. 23 Type UKP-10JS, Draw-out unit 60

830
55 498
45 11 - 7 Holes

17.3
15 580 120 25 6 1 4 7

299.5
5 6 11 - 6 Holes
30 115

140
100
365

9
280

38 140
240

200

M12 - 4 Screws Depth 20


120

3 1004
652

789

60
80

40
200
240

280
365

2 40

Detail of primary terminal Fig. 25 Type UKP-10QS Draw-out unit


30 50
45

100
769 8 30 - 2 Holes A B
50

345 182 600


UKP-10MS, 10MS2 295.5 298
UKP-10PS, 10PS2 299.5 290
90

100
DISCONNECTED POSITION

200
CONNECTED POSITION

2
60
No. Description
B

77 392
1 Primary terminal
710

4 2 Shutter device (Insulation)


No. Description 3 Earthing plate
20 85 1 Primary terminal
A

7 40 4 Guide rail
35

2 Shutter device (Insulation)


150
100

5 Connecting boss for lifter


3 Earthing plate
38 140 4 Guide rail 6 Mounting hole
869 5 Connecting boss for lifter 7 Earthing terminal
6 Mounting hole 8 Lifting hole
7 Hole for earthing wire 9 Socket for driving screw
Fig. 24 Types UKP-10MS, UKP-10MS2, UKP-10PS, UKP-10PS2 Draw-out units
8 Lifting hole
9 Socket for driving screw

21 22
Dimension (Draw-out unit) Dimensions (Draw-out unit)

15 - 4 Holes 125
(Mounting) 139.5 0.5
40
2
M12 - 4 Screws
4 Depth 20
5 7 633.5 4 1
15 - 2 Holes

375

324
Center

150
230

60
80
93
Line

40
Center

968
Line 40
15

130
199
375
230
120 12 15

400
300
17.5

230
Detail of primary terminal (Section A-A)

124
8

850

869
M8

120

230
300
Detail of fixing pin for lifter 300 189

400
14 - 2 Holes (for lifting hook M12) 855 145
6 22
7 SECTION B-B 3
30 - 2 Holes (for lifting) 30 344 344 A A Detail of earthing plate
1

35
500 400 70

78
6 3

125
15 - 6 Holes

28
6

250
8
2 9.5 38 M10 - 2 Screws
8
1032

390

33 Detail of earthing terminal


300 2

63
11

125
250
13

Disconnected position
339.5

Connected position
B

M4 - 5 Screws

160
161
(for Partition)
+1

11

368
687 0 10 9 210 717 340 340 "B"

1000

1000
950 1015 350 350
Connected position
Disconnected position

382
M12 - 4 Screws Depth 20
50
690 20 115 115
140
170

PDS 1030 145


A
50

30
145 50 40
18 - 4 Holes
No. Description
140
170

PDS
B 1 Primary terminal
50

2 Shutter device (Insulation) Fig. 27 Types UZP-20JS, UZP-20MS, UZP-20PS Draw-out units
145 100 3 Earthing plate
Detail of primary terminal 4 Fixing pin for lifter
5 Stopper for dropout of VCB
6 Interlock grave (Disconnected pos.)
Fig. 26 Type UZP-10RS Draw-out unit 7 Wheel guide No. Description
8 Driving mechanism 1 Primary terminal
2 Insulation shutter
9 Driving shaft
3 Earthing plate
10 Lever for driving handle 4 Earthing terminal
11 Opening for driving handle 5 Connecting boss for lifter (M8 Nut)
6 Mounting holes (Floor plate)
12 Ventilation hole (Floor)
7 Mounting holes (Top plate)
13 Ventilation hole (Rear) 8 Lifting hole

23 24
Dimensions (Draw-out unit) Operating circuit (Open and discharged condition)

Control circuit board


15 - 6 Holes 5 3 8 2

1
4
525

15
Square M12 - 4 Holes Depth 25

300
hole
1144

180
120

40
300
140 180
525

80
40

Detail of primary terminal


400 500 151
589
310 6 40 - 4 Holes
7
40
Disconnected position

Connected position

442
1054

1120
403

Symbol Description
Y Auxiliary relay
Y-b Y relay contact (N.C.)
50

300 746 62 9 X Control relay


150 X-a X relay contact (N.O.)
1105 244 M8 Nut
X-b X relay contact (N.C.)
CC Closing coil
TC Trip coil
a1 - a6 Auxiliary contact (N.O.)
No. Description
b1 - b6 Auxiliary contact (N.C.)
1 Primary terminal
M Charging motor
2 Insulation shutter
LS1 Limit switch
3 Earthing plate
IL Interlock switch
4 Fixing pin for lifter Arrangement of secondary disconnector
5 Mounting hole D1 - D5 Diode
6 Lifting hole C1 - C3 capacitor
7 Racking roller R1 - R5 Resistor
8 Ventilation hole F Fuse
9 Hole for earthing wire Ry Auxiliary relay
Ry - a Aux. Ry contact (N.O.)

Fig. 28 Type UZP-20MS1, -20PS1, -20QS1 Draw-out units


Fig. 29 Connection diagram of Type VZ vacuum circuit breakers
V Y 30 M 25 A
Vacuum circuit breaker
Series symbol
Y : series 820 980
300 300 930
Voltage class 10
30 : 36kV
Rated current
M : 1250 (1200)A, P : 2000A
Rated interrupting current 13 9
25 : 25kA
Modification symbol

1465

1370
1 5 No. Description
1 Opening for racking handle
11 Spring charge indicator
2 6 2
Operation counter

830
3
7 4 Rating plate
Table 6 List of specifications for VY series 3 5 OEN-CLOSE indicator
6 Closing button
Items Standard type Changeable scope of spec 8
7 Opening button
Applicable standards IEC 60056 JEC 2300 12 Opening for charging handle
8
9 Interrupter and molding
Installation method Draw-out Fixed with wheel 905 10 Primary disconnector
Control circuit connection Plug with Interlock Plug connection 11 Racking screw
(MIC connector) 12 Secondary disconnector
Self coupling Fig. 30 Types VY-30M25A, VY-30P25A Vacuum circuit breakers 13 Handle
Closing voltage and method 100/110VDC 1. 48/50VDC
Motor spring 2. 100/110VAC
silicon rectifier
3. 200/220VAC
silicon rectifier
Tripping voltage 100/110VDC 1. 48/50VDC
2. 100/110VAC
capacitor tripping
3. 200/220VAC
capacitor tripping 300 300 360 825
Auxiliary contacts arrange. 4NO,4NC 1. 5NO, 5NC(MAX)
(for Plug interlock)

100
60

40
Silicon rectifier and capacitor tripping device shall be installed in
switchgear and may be ordered as accessories.
2 40

540
Disconnected position

1700
Connected position

838
100
110 290 1250 46
940 1356 310
1000
1100

Fig. 31 Types UYP-30MS, UYP-30PS Draw-out units

27 28
Accessories Accessories

Warning Warning
Type-form or label 420 label
Name of parts Application
ordering code
Control wire with plug Supplied 1 set with Draw-out unit M12 Nut
Cramps

130

85
Manual charging handle Supplied 1 pc for V6A, VHA only, required for others for wire

(To base floor)


39
Racking handle Required for

24
4.5
478
VZ : 31.5kA or more (except 4000A) 502

3
VK : 40kA or more Section A-A Internal connection
VY : all ratings
140 140 B Section B-B detail for terminal
A without insulation cap
Rectifier unit 2N4BUL For closing operation with 100-200VAC class
Insulation
Capacitor tripping device LC-9 For tripping operation with 100/110VAC caps
LC-10 For tripping operation with 200/220VAC Insulators

(Maximum dimension)
B
For tripping operation with 100/200VAC class
CIT-10Q
Provide alarm contact 15 X 20
2 Holes

385
CR surge suppressor NV60K304T1 For 6.6kV, 3 phase type
Hooks
NV95K304T1 For 11kV, 3 phase type

200
A Rating
label
Earthing

110
terminal

38
(M8)
90 485
80 5.5 - 2 Holes 520
83

Legs for
mounting

Fig. 33 CR Surge suppressor

30
265 NV60K304T1

Manual charging handle M4 - 8 Screws


Warning Warning
label label
600

35
21

M12 Nut
Cramps

190

145
for wire

(To base floor)


147

39
Rectifier unit

24
670

4.5

3
510
(2N4BUL) 694
600 Internal connection
Section A-A
5 - 2 Holes or M4 Screws 200 200 B
A
Racking handle Section B-B detail for terminal
4.2 - 2 Holes Discharging switch Connecting terminal without insulation cap
Insulation
cap
Signal lamp Insulators
B

(Maximum dimension)
131.5
10

Fuse 25 - 2 Holes
110
130
142

116

118
130

510
15 X 20
2 Holes
Hooks
Closing operation rod A Rating

260
label
10 56 14 4 64
6
16

76 75
Earthing
130

Dimension of panel mounting holes terminal


38

2 (M8)
665
Capacitor tripping device 700
(LC-9 and LC-10) Legs for
mounting
Fig. 34 CR Surge suppressor
Fig. 32 Accessories NV95K304T1

29 30