Professional Documents
Culture Documents
Reactive Power Management & Power Quality
Reactive Power Management & Power Quality
Types of Loads
∗ Resistive
∗ Inductive
∗ Capacitive
Resistive
Circuit
I V
• Resonance analogy
Reactive Power Flow Analogy
Voltage
I
Inductive Load
Current
+
V Pi
-
Inductive Load
Active power
Reactive power
Reactive Power Flow Analogy
Inductive Load
Inductive Load
Active power
Capacitor
Reactive power
Power Triangle Analogy
QC
S(kVA)
S(kVA)
Q(kVAr) φ1 φ2
φ1 P(kW)
-QC
P(kW)
Reactive Current I2
(inductive) IR(L)
I1
Resonance Analogy-1
Definition:-
Resonance is defined as a condition where
Capacitive Reactance becomes equal to Inductive
Reactance in magnitude.
The frequency at which this occurs is called the
Resonance Frequency.
| XL| = |XC |
Inductor
| XL| = |XC |
Inductor
|Z| = 0
|Z| =
Zeq = Z1 + Z2 Zeq = Z1Z2 / (Z1+ Z2)
Series Resonance Parallel Resonance
Resonance Analogy-2
Uncompensated load Compensated Load
Inductive Load
of Capacitor at Fundamental
Frequency, then the PF will be
Unity due to Parallel resonance
b/w capacitor & load inductor.
Inductor
Inductor
Resistor
Resistor
Resistor
Practical Example
40 W Fluorescent Tube Light
Choke
P N
P = 40W+10W = 50W
Power Factor = 0.6 230 Volts 50 Hz.
Calculation of PF correction based
on Power Triangle concept
Resistor
Resistor
Irms= I1
√ (
1+
THDI 2 V = V
100
) rms 1
√ (
1+
THDV 2
100
)
True Power factor = P/ (VrmsIrms)
P
=
√ (
V1I1 1 + THDI 2
100
) √ (
1+
THDV 2
100
)
True Power factor = Displacement PF x Distortion PF
1
Where Distortion PF =
√ ( ) √1 + (
THDI 2 THDV 2
1+
100 100
)
Effect of harmonics on PF
%THD(V) %THD(I) Distortion PF
0 0 1.00
1 20 0.98
2 40 0.93
3 60 0.86
4 80 0.78
5 100 0.71
Three dimensional
power triangle
kW
kdVA
kVA
kVA= √ kW2+kVAr2+kdVA2
kVAr kW
Displacement PF =
√ kW2+kVAr2
kW
True PF =
√ kW2+kVAr2+kdVA2
Electric Power
Apparent Power
kVA
r
we
w er
Po
Po
e
tiv
ive
ac
ct
Re
A
Power Triangle
Ap
Reactive Power
pa
r en
tP kVA = √kW2 + kVAr2
ow
er kW
P.F. =
kVA
Active Power
PF of various Industries
Floursent
Lamp
0.5 P.F.
Induction Welding
Furnace Transformer
Reduction in KVAR
Demand
Reduction in
Reduction in KVA Reduction in
Switchgear
Demand Transformer Rating
Rating
Reduction in
Reduction in Line Reduction in Line
Cable / Bus-bar
Current loss
size
REDUCTION IN KVA DEMAND
LOAD - 900 KW
KV
EXISTING P.F. (COS Ø 1) - 0.6 A
KVAR
KVA1 - 1500 kVA = √KW2 + KVAR2
Ø.
KVA2 - 978 KVAR1 = √KVA1 -
2 KW2
KW
= √1500 2 - 900 2 = 1200
Reduction in KVAR KVAR 2 =
√978 2 - 900 2 = 382
1200 - 382 = 818
REDUCTION IN LINE
KVA1 - 1500
CURRENT
KVA = √3 V I
KVA2 - 978 1000
I = KVA x 1000
√3 x 415
I1 = 1500 x 1000
√3 x 415
= 2087 Amp
Reduction in Current
I2 = 978 x 1000
2087 - 1361 = 726
√3 x 415
= 1361 Amp
Cable Losses
2
CosØ1
% of saving in losses = 1- X 100
CosØ2
2
0.6 X 100
1- 0.92
= 57.46
Transformer Losses
1 1
Saving in losses = Wr x K1 Cos Ø - Cos Ø
1 2
connected load in Kw
k1
KVA rating of the transformer
Transformer Losses
1 1
Saving in losses = Wr x K1 Cos Ø - Cos Ø
1 2
900 1 1
= 18000 x x
1500 0.6 0.92
= 6260 Watts
500
0
KVA X'MER CURRENT ACB
RATNG
AT 0.6 PF AT 0.92 PF
Evaluating PF from Electricity Bill
ELECTRICITY TARIFFS - I
In India, there are broadly 4 types of
Electricity Tariffs.
– Single part tariff
• Measurement of kWh only - Energy charges -
Generally applicable for LT installations only.
– Two part tariff
• kWh - Energy charges
• kVA or kW - Maximum demand charges
• PF Penalty/Incentives - vary from region to region
• Applicable for HT installations
ELECTRICITY TARIFFS – II
Resistive
M M M M Load 30kW
Lighting
30 HP, 75 HP, Other loads, 50 kVA, 75 HP, 20 HP,
415V, 415V, Load 10kW
415V, 3ph, 415V, total of 25 440V,
motor 3ph, kW 3ph, UPS 3ph, 3ph,
compressor compressor Pump,
PF =0.80
Lag
ESTIMATE kVAr REQUIRED for
New Electrical Installations - I
Fixed Compensation
– For Steady Loads
– No load compensation of Motors
– No load compensation of Transformers
Variable Compensation
For Varying Loads
Selection of Capacitor
1. Individual Compensation
2. Group Compensation
3. Central Compensation
Where to install Power
Factor correction Equipment
Individual Compensation
Group Compensation
Central Compensation
Transformer
Circuit Breaker
No 1
M M M M
Fig. 3.1
Central,Group and Individual Compensation
Providing compensation at
•main incomer bus – central compensation. (pos. No 1)
•At power distribution boards – group compensation (pos. No. 2).
•At individual load terminals – individual compensation. (pos. No. 3)
This is suitable for installations consisting of main receiving station,
substations, several load feeders and a wide variety of loads. (refer fig 3.3)
Supply Bus
Transformer
Circuit Breaker
No 1
No 2 No 2
No 3 M No 3 M No 3 M No 3 M
Fig. 3.3
Some basic formulae –
capacitance,capacitor currents
Capacitor Connection
B
Capacitor Rated Current
√3. VL IL
KVAR =
1000
KVAR .1000
IL =
√3 .VL
Change in Current Vs.
Change in Voltage
VOLTAGE KVAR CURRENT
6π f C∆ VL2 *
KVAR = CM
10 9
KVAR X 10 9
C∆ = µF C∆
6πf VL2
CM = 1.5. C∆
* C∆ in µF and VL in Volts
Peak inrush current of
capacitor
√2
√.
Ip = Ir MVA SC X 103
kVArc
Transformer = %Z x 10 x kV2
ACB impedance kVA
= 5 x 10 x 0.4152
1000
= 0.00861 Ohm
Short Circuit MVA of the System
√3 VL Isc
Short circuit MVA of the System =
10 6
Ip = Ir . √2
√.
MVA SC X 103
kVARc
Ip= 34.78.√2
√.
22.0 X 103
25
= 1459.1 Amp
Parallel Switching of Capacitor
√2 1
Ip = VL
√ X C XL
√3
V = Voltage Rise
V Q
=
V S
415 x 0.025
V =
22
= 0.47 volts
Discharge Time
C
Discharge Time
t
R<
K C log e
( Vn.√2
VR
)
R = Discharge Resistance in M Ohm
C = Capacitance in µF
C R K=1
K=3
R
C
R R
C C K=3
R
C
K=1
3. Calculation of Capacitor kVAr Required for Power-
Factor Improvement
lC
1 2
C C
V Vph CM
C = µF
C 1.5
2
CM
3 V = Vph
CM is the measured capacitance across any two terminals with the other terminal left open circuited.
C C C= 2CM
2
3
CM is the measured capacitance across any two terminals with the other terminal left
open circuited.
XC/Ph = 106
2πfc
Where XC = Capacitive Reactance per phase in ohms
3 Ph kVAr = 2πfcV x 3
2
V = Voltage (line to line) in volts
109
kVAr = Rated output of capacitor
3 ph kVAr X 103
IL = IL = Line current in Amps
√3 V
Measured verses cell capacitance
C1,C2,C3 are the capacitance
Ca Cc measured as indicated with the third
line open-circuited.
C1
Ca,Cb,Cc are the cell capacitance,
C2 internal to the three phase capacitor.
Using following formulae we can
Cb calculate cell capacitance, without
C3 opening and de-soldering/cutting the
capacitor units.
Ca =
1
( 1 1
+ -
1
C1 C3 C2 ) Cb =
1
( 1
+
1
-
C1 C2 C3
1
) Cc = 1 ( 1
+
1 - 1
C2 C3 C1 )
These are derived from the following
where basic relationships.
CaCb C cC a
( )
C1+C2+C3 C 1 = C c+ C + C C3 = Cb+
1 1 1 1 C c+ C a
= - + + a b
CbCc
C1C2C3 2 C12 C22 C32 C2 = Ca+
Cb+ Cc
Measured verses cell capacitance
1 1 1
Ca Cc Ca Cc Ca Cc
C2
2 2 2
Cb Cb Cb
C1 C3
3 3 3
C1,C2,C3 are measured capacitances across any line and other two lines
short circuited. Full line to line voltages are applied across the cells.
C1 = Ca+Cb C2 = Ca+Cc C3 = Cb+Cc
The individual cell capacitances can be computed as follows.
1 (C +C -C ) ; 1 (C +C -C ) ; 1 (C +C -C )
Ca = C = Cc = 2 3 1
2 1 2 3 b 2 1 3 2
2
Cost Based Selection
• MD Capacitors
Energy Consumed = (Loss per kVAr x Total kVAr x Operating time)/1000
= (1.5 x 1000 x 6000 x 15) / 1000
= 1,35,000 kWh
Consequently, the excess energy consumption due to the MD Capacitor shall be
= 1,35,000 – 45,000
= 90,000 kWh
This energy consumed can be converted into cost using a weighted average cost of Rs.5 per
kWh. Consequently, the extra cost shall be Rs.5 x 90,000 = Rs.4,50,000.
On a per kVAr base this can work out to Rs.450/-per kVAr. It is obvious that operating
cost must be evaluated carefully before taking the final decision on the type of capacitor to
be used. It is also self explanatory that lower the losses, lower will be the operating cost.
Automatic Power Factor Correction
(APFC)
NEED FOR AUTOMATIC POWER
FACTOR CORRECTION
Voltage Spike ,which can destroy electronic equipment and damage transformer
and motor insulation. They also cause failures in capacitors and indicators.
Notch in the Voltage Waveform
Liner Load Characteristics
Voltage
Waveform
Current
Waveform
Non-linear Load Characteristics
Voltage
Waveform
Current
Waveform
Power Quality Issues
Unbalanced loads
– Over & under voltage in the network.
– Increased energy consumption by motors
• Due to reduced efficiency.
– Failure of power electronic equipment
– Malfunction/failure of
• Protective relays
• Control & Automation equipment
PROBLEMS ! - V
R - phase.
Y - phase.
B - phase.
C o m p ensatin g
C u rren t
A ctiv e
F ilter
+ =
( T im e Do ma in )
+ =
( F requ en cy D oma in )
Benefits of POWER
QUALITY MANAGEMENT
• Improved reliability of installation
• Reduced energy consumption
• Reduced fuel consumption
• Better productivity
• Improved profitability
• Enhanced equipment life
Power factor improvement of DG sets
Capacitors with Generators
G
Diesel generator set
G
100 KVA
0.8 P.F.
80 kW
Connected load P.F. is 0.6
100 kVA
P.F. 0.8
80 kW
600
500
CURRENT IN AMPS
400
WITHOUT
COMPENSATION
300
WITH
COMPENSATION
200
100
0
1 2 3 4 5 6 7 8 9 10
TIME IN SECONDS
Alternator loss reduction due
to P.F improvement
The following example gives an approximate
calculation to show the impact of power factor
improvement on reduction of alternator losses and
accrued savings in Diesel consumption.
Consider a 3 phase, 415V, 50Hz, 500 kVA DG set
used in an industry for 6000 hours/year with an
average load of approximately 250kW at 0.65 PF.
What is the fuel saving if PF is improved to 0.93? The
full load copper loss of the alternator is 12kW and
average yield of the DG set is 3kWh/litre of fuel
(HSD).
Alternator loss reduction by
P.F. improvement
F .S .U
f 2
F 1 ......F n
Pow er
F a c to r
C o n tr o lle r C 1......C
K 1 .....K n
n
C 1......C n = N o . o f C a p a c it o r S te p s
K 1 ......K n = N o . o f C a p a c it o r S te p C o n ta c to r s
F 1......F n = C a p a c i to r S t e p P r o te c tio n F u s e s
f2 = C o n tr o l F u s e s
F .S .U = F u s e S w itc h U n it ( O p tio n a l)
G = D i e s e l G e n e r a to r
CT = M a in S u p p l y C u r r e n t T r a n s f o r m e r
FIG 5. BLOCK DIAGRAM OF DYNAMIC COMPENSATION SYSTEM IN CLOSED LOOP
G
CT
~ Variable
Load
F.S.U
Reactive f2
Power
Controller
F1 F2 Fn
S1 S 2 Sn
2000kVA,
33/0.44 kV Trafo.
440V bus
M 500HP DC
900kVAr
Drive
Capacitor
1000HP
Induction Motor
Case – 3
• Problem experienced:
• Frequent failure of capacitors installed for
power factor correction.
Case – 3- Analysis
• A team of engineers from MEHER made an analysis
at the site. The result of the analysis is as follows:
• The capacitors installed were drawing more than it’s
rated current. A 50 kVAr, 440V capacitor was
drawing a current of 200A against the rated value of
65amps, thus constituting an overload greater than
300%.
• This abnormal over load resulted in frequent
capacitor failure.
• The total harmonic voltage distortion at the
secondary of this 2000 kVA transformer with all the
capacitors switched on was more than 25%. This
value is higher than acceptable levels.
Case – 3- Conclusion
• Thus the use of conventional capacitor in harmonic
rich environment resulted in:
• Over loading of capacitors due to parallel
resonance.
• Increased harmonic distortion at the LV
bus.
• Frequent failure of capacitor banks.
• Inability of the customer to maintain the
desired power factor.
• Financial losses incurred by customer.
What Are Harmonics ?
• Distorted sine wave cause harmonics.
• Distorted current wave cause current harmonics.
• Distorted voltage wave cause voltage harmonics.
• Fourier expansion result in integral multiples of
fundamental frequency components.
• Nth order harmonics is of n.Fs frequency.
• Generally odd harmonics are prevalent because of
half wave symmetry.
How Harmonics Are Generated ?
• Non-linear loads generate current harmonics.
• Harmonic currents flow largely through capacitors.
• Harmonic currents also flows through network.
• The flow of harmonic currents cause voltage harmonics.
• Harmonics are thus injected to other linear loads
connected in the same bus.
• Harmonics injected into the network flow towards other
users connected to the network.
What Loads Generate Harmonics
• Equipment using switched mode power supply
- Television
- Computers, other IT loads
• Equipment using power electronic devices
- AC & DC drives
- Frequency converters
- Rectifiers
- Arc & induction furnaces
- UPS
- Compact fluorescent & other discharge lamps
Sources of Harmonics
Following are some of the non-linear loads which generates
harmonics:
•Static Power Converters and Rectifiers, which are used in UPS,
Battery chargers, etc.
•Arc furnaces.
•Power Electronics for motor controls (AC/DC Drives)
•Computers.
•Television receivers
•Saturated Transformers
•Fluorescent Lighting with electronic ballast.
•Telecommunication equipment.
Type of Harmonics
Characteristic harmonics
- Related to circuit configuration.
- Fairly predictable frequency spectrum.
- Frequency spectrum given by k*p+1 ; k = 1,2,3….
- For ex. 5&7 for 6 pulse, 11 & 13 for 12 pulse.
- Magnitude inversely proportional to order.
Non-characteristic harmonics
- Caused by frequency converters.
- System imbalance (voltage & impedance)
Triplen harmonics
- 3.(2n+1) order n = 0,1,2… i.E 3,9,15,21.. Etc.
- Zero sequence in nature.
- Accumulates as neutral current.
Harmonic Order & Phase
Sequence
• Each harmonic order has a particular phase
sequence relationship with respect to
fundamental.
R Y B
Fundamental +120o 0o -120o B
B
Second +240o 0o -240o
Negative Sequence
Harmonic -120o 0o +120o
Y
Third
Harmonic +3600 00 -3600
00 00 00
Fundamental Third Harmonics
R
Zero Sequence
Positive Sequence
Y R
Y
B
Thus third harmonic behaves as
B a zero sequence component.
Accumulation of 3rd harmonic current in the neutral
Three phase system
R - phase.
Y - phase.
B - phase.
Phase Sequence + - 0 + - 0 + - 0
Accumulates in the
Aids the fundamental Opposes the fundamental
neutral
Trip level set lower than the fundamental Trip level set higher than the fundamental value.
value. The relay should trip as the fundamental The relay should not trip as the fundamental
value is higher than the trip level. But the value is lower than the trip level. But the
presence of harmonics has reduced the peak presence of harmonics has increased the peak
value. Hence the protective relay will not trip. value. Hence the protective relay will trip.
Circuit configuration of
six pulse drive
Current spectrum of six pulse drive for
star-star & star-delta configuration
Twelve pulse drive configuration
Current spectrum of twelve pulse drive
How Capacitors &
Harmonics Are Related -1
Network behaviour without capacitors
• Network do not reveal harmonics.
• Most of the harmonic currents internal to
network go to the grid.
• No resonance at harmonic frequencies.
• Network power factor is unacceptably low.
Network Without
Capacitors
Harmonic currents flow towards Grid.
GRID
Min. Import of Harmonics from Grid.
No Resonance at harmonic frequencies.
M
How Capacitors &
Harmonics Are Related -2
lh XC XL
Harmonic Filters
Harmonic Mitigation Concept
fR= Resonant
Capacitive Inductive
Frequency
f < fR - Capacitive
Impedance
f > fR - Inductive
Harmonic filters
are classified based
upon how close fR is
to a Harmonic
fR Frequency frequency
Classification of
Harmonic Filters
• Detuned or harmonic suppression filters
• Resonance frequency fR< 90% of
lowest dominant harmonic frequency.
• Tuned or harmonic absorption filters
• Resonance frequency fR within 10% of
the frequency of the harmonic to be
absorbed.
Classification of Harmonic
Filters
Harmonic
Filters
Detuned Tuned 3Ф
Filters Filters 3wire
3Ф
7% 4wire
14 % Single
Phase
Selection Criteria for
Harmonic Filters
• Detuned filters
• Power factor correction is of paramount importance.
• If ordinary capacitors draw > 130% of its rated
current.
• Reduction of THD(V) not relevant.
• To prevent capacitors from harmonic overload
• Harmonic study not required for installing standard
detuned filters.
Selection Criteria for
Harmonic Filters
• Tuned filters
• Power factor correction & reduction of THD(V) are
of paramount importance.
• Ordinary capacitors draw > 130% of its rated
current.
• Harmonic study required for installing tuned filters.
• Specifically designed for each location.
• More bulky, since it carries large amount of
harmonic currents. Hence expensive.
Standard Detuned Filters-1
• Standard detuned filters have a fixed percentage
tuning factor “p”
• Percentage tuning factor is defined as
Reactor reactance at system frequency
p = Capacitor reactance at system frequency X 100 %
• Standard detuned filters are available for 7%
tuning factor
• The resonant frequency of the filter fR is related to
tuning factor “p” by
Fr = Fs/ √(p/100) = 189 Hz for 7% filter
Standard Detuned Filters-2
• Standard 7% detuned filters are suitable for use in
majority of installations where the dominant
harmonics are higher than 189 Hz like 5th and
higher.
• 7% detuned filters should not be used in
installations where predominant 3rd harmonics are
present like “IT based” industries.
• For “IT based” industries 14% detuned filters
(fR=134 Hz) should be used.
Design Features of
Detuned Filter
L L L L L L L
C∆ CY CY
Parallel Resonance
Description of the Problem
A 500kVA, 415V, 3 phase, 50Hz., 4% impedance
drop transformer is feeding a 100kW, 6pulse DC
drive. The PF of the DC drive under full load
condition is 0.7 lag. Calculate the following :-
• A) Calculate the harmonic current spectrum of
100kW DC drive.
• B) Calculate the kVAr required to improve the PF of
the drive above 0.99 lag.
• C) Calculate the harmonic voltage distortion and
harmonic overload with the following :-
• 1) Without any capacitors.
• 2) With conventional capacitor connected to the
network.
• 3) With de-tuned filter connected to the network.
Harmonic Spectrum
• Harmonic spectrum of 100kW, 6 pulse, 0.7 PF DC
drive is given by the relation: Ih =i1/h, where h is the
harmonic order.
Since the drive is 6 pulse, h = 5,7,11,13,17,19.
h Ih Amps
5 40
7 28.6
11 18.2
13 15.4
17 11.8
19 10.5
Estimation of kVAr
• kVAr required to improve the PF above 0.99 lag.
500 kVA
100 kW,
3ph,415V, DC
drive Linear resistive
Loads
Network Without Capacitors
Equivalent Circuit
XT
Ih
Calculation of Transformer
Impedance Xt
• We use the following formula.
= (√(4.772+4.772+4.772+4.772+4.772+4.772)/415)*100
THDV% = (11.69/415)*100
THDV% = 2.82%
Network With Capacitors:
• Calculation of harmonic voltage distortion and
harmonic overload:
• With conventional capacitor of rating 100 kVAr.
Capacitive reactance Xc= V2/ (kVAr x 1000) ohms.
= 4152 / (100 x 1000).
Xc = 1.72225 ohms.
Transformer reactance.
Xt = V2 x (%Z / 100 ) / (kVA x 1000) ohms
= 4152 x (4 / 100) / (500 x 1000).
Xt = 0.013778 ohms.
Network With Capacitors
500 kVA
100 kW,
3ph,415V, DC 100 kVAr,
drive Linear resistive 3ph,415V
Loads
Network With Capacitors:
Equivalent Circuit
Ih Xt XC
Harmonic Simulation With
Capacitors
h Ih Xth=Xt*h Xch=Xc/h |Xtotal| = Vh = Ic =
Xth*Xch √3*Ih*Xtotal Vh/(√3*
|(Xth-Xch)| Xch)
Iceff=571 Amps.
Overload = 411 %
THDV% With Capacitors
=(√(5.972+7.852+149.152+13.562+3.642+2.532)/415)*100
= (150.16)/415*100
= 36.18%
Calculation With Detuned Filters
500 kVA
XLF
100 kW,
3ph,415V, DC
drive Linear resistive 112.5 kVAr,
Loads
3ph,440V,DF
Why 112.5 kVAr
• The detuned filters, supplied by L&T/Meher are rated
for a bus voltage of 440V. This is mainly done to
provide a standardized solution.
• The kVAr output of a 440V capacitor is reduced if
connected to a 415 volts system, given by the relation.
= (Vsystem/Vrated)2 * kVAr.
= (Vrated/Vsystem)2 * kVAr
= (440/415)2 * kVAr
= 1.124 * 100
= 112.5 kVAr. (approx.)
Network With Detuned
Filters: Equivalent Circuit
Ih Xt XLF
XCF
Detuned Filter of
112.5 kVAr, 440V
Capacitive kVAr = 112.5 * (1 – p/100)
= 112.5* (1-7/100)
= 112.5 *0.93
= 104.625 kVAr
XC = 4402 / (104.625 x 1000)
XCF = 1.8504 ohms.
Reactance of reactor
XLF = p/100* Xc
= 0.07*1.8504
= 0.129528 ohm.
Harmonic Simulation
Transformer reactance.
Xt = 0.013778 ohms.
Harmonic Simulation With
Detuned Filter
Xth = XLFH = XCFH = XFilter = Xtotal = Vh = Ic= Vh/
h Ih Xt*h XLF*h XCF/h
XLFH – Xfilter*Xth √3*Ih* (√3*XFilter)
XCFH ( XFilter+Xth) Xtotal
Ifeff=139.43 Amps.
Overload = Negligible.
THDV% With Detuned Filters
THDV% = (√(V52+V72+V112+V132+V172+V192) / V1) x 100
= (√(3.822 +4.152+4.262+4.282+4.292+4.302)/415)*100
THDV% = (10.25/415)*100
THDV% = 2.47%
Summary
It is seen that the introduction of capacitors into
a network with non-linear loads not only leads
to very high overloading of the capacitors but
also increases the harmonic voltage distortion
in the network due to parallel resonance.
Active Compensation
SCOPE
• ACTIVE COMPENSATION
• NEED
• PRINCIPLE
• BENEFITS
• SOLUTIONS
• AHF - ACTIVE HARMONIC FILTER
• INTELLVAr - E
• Electronic VAr Compensation
Need for Active Compensation - I
Total PF No risk of
Control Resonance
Voltage Extremely
Stabilty Flexible
Sinusoidal
Load Current with Supply
Harm onics Supply
Current
System
Compensating
Current
Active
Filter
+ =
(Time Domain)
+ =
(Frequency Domain)
Waveform of current without Active filter
Waveform of current with Active filter
Current harmonics without active filter
Current harmonics with active filter
Cost-Technology Pyramid of Harmonic Filters
Top end solution for wide
spectrum of current
Suitable for installations Active harmonics & suitable for
having high harmonic filters installations having
distortion (cement, sugar sensitive equipment
& steel plants, etc.)
Hybrid Filters
Tuned Filters
7% Detuned Filters
Most common, Base end product suitable for majority
of industries having 5th and above harmonics