Co., Ltd GRACE01 Variable Frequency Door Operator Page 1 of 24 Version: 10
版本号 Version: 10
GRACE01 变频门机安装调试手册
Installation & Commissioning Manual
for
Grace Series Variable Frequency Door Operator
编 制 张海军
Prepared by
校 对 黄棣华
Checked by
标准化 郭珍珍
Standardized by
审 定 林穗贤
Reviewed by
批 准 尹政
Approved by
广州广日电梯工业有限公司
Guangzhou Guangri Elevator Industry Co., Ltd
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 2 of 24 Version: 10
--English version--
Introduction: All the contents in this Manual are only applicable for GRACE series variable frequency door
operator system.( Program Ver:899)
I. Constitutes of Variable Frequency Door Operator:
Integrated special door operator frequency converter is used for driving permanent magnetic synchronous motor,
in which absolute value encoder is installed and the output axis end of which has no deceleration device, and
driving the mechanic part (door arm) of door operator directly to open/close the door by means of the synchronous
belt.
Note: for side opening, center opening 4-panel variable frequency door operator, the quick opening door panel
shall be dragged by synchronous belt via support arm, the slow opening door panel will be driven by quick opening
door panel according to the structure principle of steel wire rope guide movable pulley.
II. Working Principle:
2.1 When the controller of variable frequency door operator receives the door-opening/closing command from the
control system of elevator, the control motor will make positive or reverse rotation. The movement curve of door
operator will be generated automatically by frequency converter of door operator according to the principle of
distance control. The magnetic pole angle of permanent magnetic synchronous motor of door operator have been set
before delivery and the width of the door have been inputted into the frequency converter, so the self-study on
width of door and magnetic pole angle of motor is not necessary at site. The door operator can run after
electrification. When the door opens/closes in position, the door open/close targeting signal will be inputted into
X3 and X4 of door operator frequency converter TM4 by the magnetic induction switch of door-opening and door-
closing terminal of the main door after treatment in frequency converter of door operator, and outputted the door
opening/closing targeting signal from Y1 and Y2 of output terminal to the master controlled computer of control
cabinet of machine room.
2.2 The schematic diagram of variable frequency door operator is as follows: Picture 1 is paralle door
operator,Picture 2 is Can dooroperator
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 3 of 24 Version: 10
Picture 1
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 4 of 24 Version: 10
Picture 2
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 5 of 24 Version: 10
III. (Mechanical and Electrical System) Verification before Commissioning of Door Operator:
3.1 Electrify adjustment:
Note: the car door shall be closed while adjusting the parameter.
Close the knife switch of door
operator on car top
YES
YES
Have landing door
opening/closing function. Make Adjustment of car
sure the time meets the door is completed
requirement. The whole process
is smooth with little vibration
NO
State of car doorAdjusting methodWhole processIf bump when the door is closedReduce the door-
closing deceleration time P504 or reduce the width of door P201 aptly.If bump when door
opensReduce the door-opening deceleration time P502 or reduce the width of door P201
properly.The final crawl time is too long when the door is closedIncrease the door width
P201or reduce the door-closing acceleration time P503The final crawl time is too long when
door opensIncrease the door width P201or reduce the door-opening acceleration time P503Speed
of door closing is too fastIncrease the door-closing acceleration time P503 or reduce the
width of door P201Speed of door opening is too fastIncrease the door-opening acceleration time
P501 or reduce the width of door P201The door opens reversely when the door is not closed in
positionCheck if the short circuit output of safety edge is normal, if the stalling output
functions when the door opens reversely. If the stalling output functions, increase P604 door-
closing stalling detection threshold (cannot exceed 120%)The door opens reversely when the
door is not opened in positionCheck if the stalling output functions. If blocked output act,
if the stalling output functions, increase P603 door-opening stalling detection threshold
(cannot exceed 200%)Door operator has loud noise during stallingReduce A202 & A203 carrier
frequency or reduce E502 low speed proportional gainThe door cannot open or close or when the
door opens or closes, the motor runs out of powerAdjust H 507 by hand or re-make the self-
study of magnetic pole angle of motor
IV. Introduction for Input/Output Terminal Board Signal of Frequency Converter of Door Operator:
Terminal Description of terminal
Type NO. Name of signal Electric level of signal
signal function
1 X8 CAN_GND terminal CAN signal terminal Compliance with the CAN
3 X6 CANL terminal
Parallel communication :
4 X5 Slowly Door-closing Slowly Door-closing
functions
Input the control signal
Door-closing terminal,
5 X4 Door-closing terminal
closing is effective
Door-opening terminal, DC+24V 8mA photo-
6 X3 Door-opening terminal
closing is effective electric coupler
Door-closing functions, insulation
7 X2 Door-closing/Stop
closing is effective
Door-opening functions,
8 X1 Door-opening / Stop
closing is effective
Common terminal of input signal of
9 XC N24
photo-electric coupler
Common terminal of photo-electric
10 YC N24
Photo-electric coupler output
Low DC
Short-circuit of safety edge, normally
16 MB
open contact Dry contact, contact
Short-circuit of MB-MC
Short-circuit of safety edge, normally capacity, AC250V, less
17 MA safety edge, closed when
closed contact than DC30V, 1A
door is nearly closed
Common terminal of safety edge short- Low DC
18 MC
circuit
V. Commissioning and Operation on Frequency Converter:
5.1 Introduction for control panel of door operator:
5.1.1Interface of control panel:
LOCAL: light will shine when the running command is
given by keypad to frequency converter
FWD: light will shine when the command of positive
——Running mode:
rotation command is inputted
REV: light will shine when the command of reverse
rotation is inputted
——Data indication: to indicate the parameter code, monitoring
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 7 of 24 Version: 10
ENTER
Enter Confirm the parameter value and enter into the menu
MENU
Running/stop key: start/stop frequency converter when the running signal
ESC Menu/ESC Select the group of parameter and ESC (return to the previous status)
is given by keypad
There is an indicator at top left side of the of digital keypad. The corresponding running states of
this indicator: green light on, red light on, red light flickering and extinguishing.
The green light will shine when the driver is ready. The red light will shine when the driver runs. The red light
will flicker when the driver decelerates and stops. The indicator will extinguish when the driver is not ready.
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 8 of 24 Version: 10
Frequency assignment
Indication states Green light on Red light on Red light flickering Green light on Red light on Green light on
U Monitoring parameter Can monitor the state, terminal and faults records
Can make parameter encryption, decryption, self-learning and initialization
OP System operation parameter
operation
A Environmental parameter Can set the parameters of environment, control mode and running mode of driver
Can set the parameters of running mode, speed searching, special running mode
B Application parameter
selection and so on
C Curve time sequence Can set the parameters of acceleration and deceleration time, corner time and
parameter running time sequence
Can set the parameters of frequency command, relationship of frequency command
D Frequency command parameter
and leap frequency
Can set the environment parameter, V/F characteristic parameter, motor
E Motor parameter parameter, ASR characteristic parameter and moment compensation parameter of
driver
H Functional parameter of Can set the multifunctional connection point input (output) parameter, analog
external terminal quantity input (output) parameter
J Auxiliary functional
Can set the frequency detection, moment compensation, calculagraph, principle
parameter of external
axis orientation and rigidity tapping
terminal
Can set the motor overload protection, overheat protection of driver, over-
L Protection function
moment protection, speed protection, phase-failure protection, PG protection
parameter
and so on
O Parameter of keypad Can set the key function, common monitoring parameter selection
Set the special parameter of door operator and door width. Adjust the
P Parameter of keypad
corresponding door opening and closing parameter
5.1.4 Switchover of the parameter groups:
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 9 of 24 Version: 10
When the driver starts, enter into the monitoring interface of commonly used monitoring items directly, press
the key continuously, switchover of each common parameter group can be realized.
Press if want to enter into other interface from the monitoring interface of commonly used monitoring
items.
5.1.5 Parameter monitoring items:
3 corresponding monitoring items can be monitored by modifying the setting of commonly monitoring items (02.01.
~O2.03.) based on the monitoring parameter selection code, which is corresponding to item 1, 2 and 3 of .
The following figure is for monitoring the common monitoring items.
Commonly used monitoring item 1
(Preset target frequency before
delivery)
The monitoring of frequency command, output frequency, output current and output voltage and so on can be
realized by means of the parameter group U, and can indicate the fault content and record as well.
: When radix point is glittery, it means the digit of parameter code is being modified.
Note: the self-study has been completed before delivery, so it is not necessary at site, but self-setting of
the magnetic pole angle of the motor can be done at site if some parameters are lost or in any other exceptional
cases.
Permanent magnetic synchronous motor is used for GRACE motor. The encoder deviation electrical angle can be got
from self-study at the magnetic pole position and be set in parameter (H5.07.), and this value can also be set
manually.
Precautions for setting:
1) Before the self-study of motor parameters, confirm the parameter: type of motor (A1.05 = 1) and the
parameters listed on nameplate of motor (E2.02~E2.10) shall be consistent with the ones on nameplate of motor.
2) When the motor has continuous load (with car door), run the car to non-leveling area (i.e. the landing door
gets away from the car door), pull the door car to the center position by hand (i.e. out of the door
closing/opening in position area).
3) Set parameter OP3=3: self-study of the magnetic pole position of permanent magnetic synchronous motor
(rotary type self-study), start the self-setting by pressing “ENTER” key. The whole process will last for 1-2
seconds. If “LE8” fault alarm is given out during the setting, it means the U/V/W wire connected the motor with
the frequency converter has phase failure. Adjust the wire and then make self-setting again.
After finish the study of H5.07 value record, repeat the self-study for 3 times and select the average value.
Don’t touch the motor during self-study of motor parameters.
VI. Table of Parameters:
6.1 Moter Encoder:
The different types of motor encoders are as follows:
picure2 : old motor encoder LE06 picure3 : new motor encoder LE96
Deceleration time
Δ C111 switchover 0.00 0.00 0.00 Read/write
frequency (Hz)
Min. base blockade
Δ C301 0.50 0.50 0.50 Read/write
time (s)
Max. output
* D201 23.00 23.00 23.00 Read/write
frequency (Hz)
Upper limit of
Δ D202 100.0 100.0 100.0 Read/write
frequency (%)
Lower limit of
Δ D203 0.0 0.0 0.0 Read/write
frequency (%)
Rated power of
F E201 0.10 0.06 0.19 Read/write
motor (kw)
Pole number of
F E202 8 10 10 Read/write
motor
Rated current of
F E203 0.49 0.46 1.1 Read/write
motor (A)
Induced electric
F E204 potential of motor 110 81 101 Read/write
(V)
Rated frequency of
F E205 16.00 16.0 20 Read/write
motor (Hz)
Rated rotary speed
F E206 240 195 238 Read/write
of motor (rpm)
Empty load current
F E207 0.00 0.00 0.00 Read/write
of motor (A)
Primary resistance
F E209 89.4 61.60 21.10 Read/write
of motor (Ω)
Leakage reactance
F E210 2.5 5.5 21.0 Read/write
of motor (%)
High speed
* E501 5.0 5.0 5.0 Read/write
proportional gain
Low speed
* E502 5.0 5.0 5.0 Read/write
proportional gain
Zero speed
Δ E503 20.0 20.0 20.0 Read/write
proportional gain
High speed integral
* E504 10.0 10.0 10.0 Read/write
time (ms)
Low speed integral
* E505 3.0 3.0 3.0 Read/write
time (ms)
Zero speed integral
Δ E506 5.0 5.0 5.0 Read/write
time (ms)
Δ E507 ASR switchover 10.00 10.00 10.00 Read/write
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 15 of 24 Version: 10
frequency (Hz)
Integral upper
Δ E508 100 100 100 Read/write
limit (%)
Filtering time of
Δ E509 0.1 0.1 0.1 Read/write
moment (s)
Upper limit of drag
* E510 150 150 150 Read/write
moment (%)
Upper limit of
* E511 150 150 150 Read/write
braking moment (%)
Source of upper
Δ E512 0 0 0 Read/write
limit of moment
Changing time of
Δ E513 0.3 0.3 0.3 Read/write
moment limit (s)
Deceleration gain
Δ E514 0 0 0 Read/write
attenuation (%)
Vibration restraint
Δ E515 0 0 0 Read/write
coefficient
Filtering time of
Δ H502 3.0 3.0 3.0 Read/write
encoder (ms)
Encoder phase-
F H503 1 1 1 Read/write
sequence
0:LE06 0:LE06 0:LE06
* H510 Encoder type Read/write
1:LE96 1:LE96 1:LE96
Motor over-load
Δ L101 0 0 0 Read/write
protection enable
Overheat protection
Δ L201 0 0 0 Read/write
enable
Over moment
Δ L301 0 0 0 Read/write
protection enable
Stalling protection
Δ L401 0 0 0 Read/write
enable
Over-speed
Δ L404 0 0 0 Read/write
protection enable
Δ L502 Enable encoder 0 0 0 Read/Write 0:record of
distance fault failure, not
show fault
and door
operator
continue to
work
1:record of
failure,show
fauslt ,stop
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 16 of 24 Version: 10
door
operator
Input lack-phase
Δ L601 0 0 0 Read/write
protection function
Output lack-phase
Δ L603 0 0 0 Read/write
protection
Startup output
Δ L604 lack-phase 0 0 0 Read/write
protection
Keypad frequency
Δ O103 0 0 0 Read/write
assignment method
Setting of commonly
Δ O201 used monitoring 1 1 1 Read/write
parameter 1
Setting of commonly
Δ O202 used monitoring 2 2 2 Read/write
parameter 2
Setting of commonly
Δ O203 used monitoring 5 5 5 Read/write
parameter 3
0:parallel
Communication door
* P110 settings 0 0 0 Read/Write operator,
1:Can door
operator
0:Front
Front and back doors door
* P111 set 0 0 0 Read/Write operator,
1:Back door
operator
frequency (Hz)
Min. base blockade
Δ C301 0.50 0.50 0.50 Read/write
time (s)
Max. output
* D201 30.0 35.0 30.0 Read/write
frequency (Hz)
Upper limit of
Δ D202 100.0 100.0 100.0 Read/write
frequency (%)
Lower limit of
Δ D203 0.0 0.0 0.0 Read/write
frequency (%)
Rated power of
F E201 0.07 0.19 0.04 Read/write
motor (kw)
Pole number of
F E202 16 16 16 Read/write
motor
Rated current of
F E203 0.50 1.30 0.78 Read/write
motor (A)
Induced electric
F E204 potential of motor 78 93 42 Read/write
(V)
Rated frequency of
F E205 26.0 31.7 26.0 Read/write
motor (Hz)
Rated rotary speed
F E206 195 238 195 Read/write
of motor (rpm)
Empty load current
F E207 0.00 0.00 0.10 Read/write
of motor (A)
Primary resistance
F E209 40.31 16.75 27.50 Read/write
of motor (Ω)
Leakage reactance
F E210 17.2 27.9 35.6 Read/write
of motor (%)
High speed
* E501 5.0 5.0 5.0 Read/write
proportional gain
Low speed
* E502 5.0 5.0 5.0 Read/write
proportional gain
Zero speed
Δ E503 20.0 20.0 20.0 Read/write
proportional gain
High speed integral
* E504 10.0 10.0 10.0 Read/write
time (ms)
Low speed integral
* E505 3.0 3.0 3.0 Read/write
time (ms)
Zero speed integral
Δ E506 5.0 5.0 5.0 Read/write
time (ms)
ASR switchover
Δ E507 10.00 10.00 10.00 Read/write
frequency (Hz)
Δ E508 Integral upper 100 100 100 Read/write
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 19 of 24 Version: 10
limit (%)
Filtering time of
Δ E509 0.1 0.1 0.1 Read/write
moment (s)
Upper limit of drag
* E510 150 150 150 Read/write
moment (%)
Upper limit of
* E511 150 150 150 Read/write
braking moment (%)
Source of upper
Δ E512 0 0 0 Read/write
limit of moment
Changing time of
Δ E513 0.3 0.3 0.3 Read/write
moment limit (s)
Deceleration gain
Δ E514 0 0 0 Read/write
attenuation (%)
Vibration restraint
Δ E515 0 0 0 Read/write
coefficient
Filtering time of
Δ H502 3.0 3.0 3.0 Read/write
encoder (ms)
Encoder phase-
F H503 1 1 1 Read/write
sequence
0:LE06 0:LE06 0:LE06
* H510 Encoder type Read/write
1:LE96 1:LE96 1:LE96
Motor over-load
Δ L101 0 0 0 Read/write
protection enable
Overheat protection
Δ L201 0 0 0 Read/write
enable
Over moment
Δ L301 0 0 0 Read/write
protection enable
Stalling protection
Δ L401 0 0 0 Read/write
enable
Over-speed
Δ L404 0 0 0 Read/write
protection enable
Δ L502 Enable encoder 0 0 0 Read/Write 0:record of
distance fault failure, not
show fault
and door
operator
continue to
work
1:record of
failure,show
fauslt ,stop
door
operator
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 20 of 24 Version: 10
Input lack-phase
Δ L601 0 0 0 Read/write
protection function
Output lack-phase
Δ L603 0 0 0 Read/write
protection
Startup output
Δ L604 lack-phase 0 0 0 Read/write
protection
Keypad frequency
Δ O103 0 0 0 Read/write
assignment method
Setting of commonly
Δ O201 used monitoring 1 1 1 Read/write
parameter 1
Setting of commonly
Δ O202 used monitoring 2 2 2 Read/write
parameter 2
Setting of commonly
Δ O203 used monitoring 5 5 5 Read/write
parameter 3
0:parallel
Communication door
* P110 settings 0 0 0 Read/Write operator,
1:Can door
operator
0:Front
Front and back doors door
* P111 set 0 0 0 Read/Write operator,
1:Back door
operator
rotating reversely
Creeping
function in
door-closing 0:Invalid
* P107 0 0 0 0 0 0
terminal area 1:Effective
when the door
starts to open
Selection for 0:Invalid
* P108 0 0 0 0 0 0
immediate stop 1:Effective
Counting for door
Times of door
opening/closing which
Read only P109 opening and
can be modified
closing
manually
Adjust according to
the actual width of
Width of door door, full width for
* P201 325 375 420 470 530 580
(mm) sliding door opening,
half width for center
opening
Correct the distance
Corrected between the switch
* P202 10.0 10.0 10.0 10.0 10.0 10.0
distance (mm) and the position of
door fully opened
Distance between the
start position of
Distance
safety edge short-
* P203 between safety 60 60 60 60 60 60
circuit and the
edges (mm)
position of door
completely closed
Actual
Indicate the actual
Read only P204 displacement
position in mm
(mm)
Highest running
* P401 0.40 0.40 0.40 0.40 0.60 0.60
speed (m/s)
Creeping
* P402 5 5 5 5 5 5
frequency (%)
Correction
* P403 50 50 50 50 50 50
frequency (%)
Acceleration
* P501 time of door 1.2 1.2 0.8 0.8 0.8 1.0
opening (s)
* P502 Deceleration 1.5 1.5 0.8 0.8 1.0 1.0
time of door
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 22 of 24 Version: 10
opening (s)
Acceleration
* P503 time of door 1.0 1.0 0.8 0.8 0.7 1.0
closing (s)
Deceleration
* P504 time of door 2.0 2.0 0.8 0.8 0.8 1.2
closing (s)
Time for keeping
creeping travelling
Time delay for when the door
* P505 1.0 1.0 0.5 0.5 0.5 1.0
stop (s) opening/closing
command has been
cancelled
Limit value for
* P601 action torque 150 150 150 150 150 150
(%)
Keeping the
* P602 limit value of 90 90 90 90 90 90
torque (%)
120 120 120 120 120 120
Door opening (tips: (tips: (tips: (tips: (tips: (tips:
stalling 145 at 145 at 145 at 145 at 145 at 145 at
* P603
checkout motor motor motor motor motor motor
threshold (%) type type type type type type
6/20) 6/20) 6/20) 6/20) 6/20) 6/20))
80 80 80 80 80 80
Door closing (tips: (tips: (tips: (tips: (tips: (tips:
stalling 145 at 145 at 145 at 145 at 145 at 145 at
* P604
checkout motor motor motor motor motor motor
threshold (%) type type type type type type
6/20) 6/20) 6/20) 6/20) 6/20) 6/20)
Stalling
* P605 checkout time 1.0 1.0 1.0 1.0 1.0 1.0
(s)
Corrected
* P606 overtime 5.0 5.0 5.0 5.0 5.0 5.0
threshold (s)
belt pulley
(mm)
0: Door opening
Direction
with motor rotating
selection for
* P106 1 1 1 1 1 1 1 positively 1: Door
door
opening with motor
opening/closing
rotating reversely
Creeping
function in
door-closing 0:Invalid
* P107 0 0 0 0 0 0 0
terminal area 1:Effective
when the door
starts to open
Selection for 0:Invalid
* P108 0 0 0 0 0 0 0
immediate stop 1:Effective
Counting for door
Times of door
opening/closing
Read only P109 opening and
which can be
closing
modified manually
Adjust according to
the actual width of
Width of door door, full width
* P201 750 840 1060 1160 1260 1460 1760
(mm) for sliding door
opening, half width
for center opening
Correct the
distance between
Corrected
* P202 10.0 10.0 10.0 10.0 10.0 10.0 10.0 the switch and the
distance (mm)
position of door
fully opened
Distance between
the start position
Distance of safety edge
* P203 between safety 60 60 60 60 60 60 60 short-circuit and
edges (mm) the position of
door completely
closed
Actual
Indicate the actual
Read only P204 displacement
position in mm
(mm)
Highest running
* P401 0.40 0.40 0.60 0.60 0.60 0.60 0.60
speed (m/s)
Creeping
* P402 5 5 5 5 5 5 5
frequency (%)
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 24 of 24 Version: 10
Correction
* P403 50 50 50 50 50 50 50
frequency (%)
Acceleration
* P501 time of door 1.2 0.8 0.8 1.0 1.0 1.0 1.0
opening (s)
Deceleration
* P502 time of door 1.5 0.8 1.0 1.0 1.0 1.0 1.0
opening (s)
Acceleration
* P503 time of door 1.0 0.8 0.7 1.0 1.0 1.0 1.0
closing (s)
Deceleration
* P504 time of door 2.0 0.8 0.8 1.2 1.2 1.2 0.8
closing (s)
Time for keeping
creeping travelling
Time delay for when the door
* P505 1.0 0.5 0.5 1.0 1.0 1.0 1.0
stop (s) opening/closing
command has been
cancelled
Limit value for
* P601 action torque 150 150 150 150 150 150 150
(%)
Keeping the
* P602 limit value of 90 90 90 90 90 90 90
torque (%)
120 120 120 120 120 120 120
Door opening (tips: (tips: (tips: (tips: (tips: (tips: (tips:
stalling 145 at 145 at 145 at 145 at 145 at 145 at 145 at
* P603
checkout motor motor motor motor motor motor motor
threshold (%) type type type type type type type
6/20) 6/20) 6/20) 6/20) 6/20) 6/20)) 6/20))
80 80 80 80 80 80 80
Door closing (tips: (tips: (tips: (tips: (tips: (tips: (tips:
stalling 145 at 145 at 145 at 145 at 145 at 145 at 145 at
* P604
checkout motor motor motor motor motor motor motor
threshold (%) type type type type type type type
6/20) 6/20) 6/20) 6/20) 6/20) 6/20) 6/20)
Stalling
* P605 checkout time 1.0 1.0 1.0 1.0 1.0 0.8 0.8
(s)
Corrected
* P606 overtime 5.0 5.0 5.0 5.0 5.0 5.0 5.0
threshold (s)
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 25 of 24 Version: 10
(mm)
Highest running
* P401 0.40 0.40 0.50 0.50 0.50 0.60
speed (m/s)
Creeping
* P402 5 5 5 5 5 5
frequency (%)
Correction
* P403 50 50 50 50 50 50
frequency (%)
Acceleration
* P501 time of door 1.2 1.2 1.2 1.0 1.0 1.0
opening (s)
Deceleration
* P502 time of door 1.5 1.5 1.5 0.8 1.0 1.0
opening (s)
Acceleration
* P503 time of door 1.2 1.2 1.2 1.0 1.0 1.0
closing (s)
Deceleration
* P504 time of door 1.5 1.2 1.2 1.0 1.0 1.2
closing (s)
Time for keeping
creeping travelling
Time delay for
* P505 1.0 1.0 1.0 0.5 0.5 1.0 when the door
stop (s)
opening/closing command
has been cancelled
Limit value for
* P601 action torque 150 150 150 150 150 150
(%)
Keeping the
* P602 limit value of 90 90 90 90 90 90
torque (%)
120 120 120 120 120 120
Door opening (tips: (tips: (tips: (tips: (tips: (tips:
stalling 145 at 145 at 145 at 145 at 145 at 145 at
* P603
checkout motor motor motor motor motor motor
threshold (%) type type type type type type
6/20) 6/20) 6/20) 6/20) 6/20) 6/20) )
80 80 80 80 80 80
Door closing (tips: (tips: (tips: (tips: (tips: (tips:
stalling 145 at 145 at 145 at 145 at 145 at 145 at
* P604
checkout motor motor motor motor motor motor
threshold (%) type type type type type type
6/20) 6/20) 6/20) 6/20) 6/20) 6/20)
* P605 Stalling 1.0 1.0 0.8 0.8 0.8 0.8
Guangzhou Guangri Installation & Commissioning Manual for Doc No.: SJG06-017
Elevator Industry
Co., Ltd GRACE01 Variable Frequency Door Operator Page 27 of 24 Version: 10
checkout time
(s)
Corrected
* P606 overtime 5.0 5.0 5.0 5.0 5.0 5.0
threshold (s)
The indication is different from the above in case of failure which is as shown in the following figure.
7.2 Status indication for main board of frequency converter of door operator:
The READY and RUN indicators on main board is used to indicate the operating conditions.
Input
Tag line
U2.01 State of input/output terminal
Output
Unused
Connection part of
spindle of motor
Magnetic
particle
4) The connection wire between PCB board of rotary encoder and rotary encoder DB15 has rosin
joint or is disconnected (for the corresponding wire number, see the Diagram of Gap between
Rotary Encoder PCB and Magnetic Pole).
9 pin D
PCB board type outlet
of magnetic
encoder
5) The bouncing pins of JP1, JP2 and JP3 on frequency converter of door operator are for
function selection of receiving the signal from magnetic encoder. When they are inserted in a
wrong way or lost, the driver will give out fault alarm of PGF. Re-
insert the bouncing pins correctly.