Technical Support: Collecting Data Page 1 of 5

Technical Support: Collecting Data


This feature is only relevant for Vision controllers using PID with Autotune.

PID Server collects data during the VisiLogic Autotune process. If you need technical support, you save this data into an .upl file and
send it, together with the PID Ladder application, to Unitronics' technical support department.

Overview: Assembling Data for PID Technical Support


Detailed instructions follow the overview given in the following diagram.

Collecting Data with PID Server


Getting Started
1. Connect the PC to the controller and start PID Server from:
- within VisiLogic via the menu bar, Tools> PID Server,
or
- within Windows via Start>Programs>Unitronics> PID Server.
2. From the Connection menu, click controller model, and then select your controller type.
3. From the Connection menu, click Communication - PC Settings, and select the appropriate settings.
4. Open the VisiLogic PID application. This enables you to get data you need for the PID Server file.
Setting up the PID Server file
1. Click File>New Loop.
2. PID Server opens the PLC OS and FB Version box. Fill in the requested information:
a. Enter the OS Version. To determine the OS version in the controller, in VisiLogic click Connection>Communication and look
under OPLC Information.

mk:@MSITStore:C:\Program%20Files%20(x86)\Common%20Files\Unitronics\PIDs... 17/08/2023
Technical Support: Collecting Data Page 2 of 5

b. Enter the FB Version. In VisiLogic, click View>FB Information. Under FB types, click PID Autotune and note the version
number.

c. Select Input and Output types via the drop-down arrows.

3. Configure the PID Server file parameters using the same operand addresses you use in your VisiLogic PID Ladder application.
Marking a PID Server parameter as Visible will cause PID Server to graph the value during On-line Test mode.
a. Enter the same operands that are in the PID Configuration.

mk:@MSITStore:C:\Program%20Files%20(x86)\Common%20Files\Unitronics\PIDs... 17/08/2023
Technical Support: Collecting Data Page 3 of 5

b. Enter the same operands that are in the PID FB Control Components. Note the parameter Resolution Factor in the Control
Component FB. In most applications, you can use a value of 10 for this parameter.

c. Note that the parameters in Loop Properties have a default address of 0. Unused parameters will therefore all have the value
of 0. This causes a 'duplicate operand addresses error'. Avoid this by changing the default address.
4. Click the Edit Comments button to edit data or enter a comment.

Collecting PID Data


1. Connect the controller to the PC so that you can establish a communication link between the PC running PID Server and the Vision
running the PID application.
2. Toggle PID Server into On-line Test mode. Do not run the PID Sever Autotune!!

mk:@MSITStore:C:\Program%20Files%20(x86)\Common%20Files\Unitronics\PIDs... 17/08/2023
Technical Support: Collecting Data Page 4 of 5

3. Activate PID Autotune in the Vision Ladder application.

If the PC-PLC communication link is active, PID Server is now recording Autotune data.

4. Wait while Vision performs Autotune. When Autotune is complete, and the system has reached setpoint, let the system stabilize.
5. Turn off On-Line Test Mode.
6. Click File>Save As to create a .upl file.

If you do not save the file, all of the data


will be lost.

Sending the Data to Unitronics


Send the following information to support@unitronics.com:

This .upl file


The VisiLogic PID application
A description of your system problem

mk:@MSITStore:C:\Program%20Files%20(x86)\Common%20Files\Unitronics\PIDs... 17/08/2023
Technical Support: Collecting Data Page 5 of 5

Related features

PID Server Features

mk:@MSITStore:C:\Program%20Files%20(x86)\Common%20Files\Unitronics\PIDs... 17/08/2023