HVAC-2 Report

Name: Bola Khalil Ragheb


ID: 19015530

VCRS&VARS
1-VCRS
Carrier catalogue:
Copcat=5.29 Tevap=6.7-6=0.7°C

c.ccat=424 kw Tcond=29.4+11=40.4°C

R-134a---chart

assume etacomp =100%


h1=250 kj/kg
h2=405 kj/jg
h3=430 kj/kg
h4= h1=250 kj/kg

𝑐.𝑐 h2−h1 405−250


copcalc = Wcomp = h3−h2 = 430−405 = 6.2

copcalc>copcat because the assumption of there is no losses & compressor


efficiency is assumed to be 100%
2-VARS
Flue Gas type lithium Bromide Absorption Chiller.
WorkingPrinciple:
Fuel is burned in the gas turbine combustion chamber to produce high pressure and temperature gas to drive gas

turbine generator, flue gas of which is directed to lithium bromide absorption chiller to produce chilled (hot)

water for air conditioning.

Application Features:

• Gas turbine generator is working based

on simple circle, which is beneficial to

improve rate of utilizing waste heat.

• Flue gas from gas turbine is used in flue

gas type lithium bromide absorption

chiller/heater, to simplify the installation

configuration, save equipment investment, and improve the energy integrated utilization in system.
Copcat= 1.08 Tevap=7-4=3°C

c.ccat=470 kw Tcond=Ta=38+7=45°C

Tg=110°C

ζws=fn(Ta& Tevap) …………… ζws=.634

ζss=fn(Tg& Tcond) …………… ζss=.665

𝜁𝑤𝑠 .634
𝜆=𝜁 =.665−.634=20.452
𝑠𝑠 −𝜁𝑤𝑠

Enthalby:

point:2

T2=45°C & 𝜁2 = 𝜁𝑤𝑠 =.634 chart h2=-155kj/kg

point:3

h3= h2=-155kj/kg

point:4

T4=110°C & 𝜁4 = 𝜁𝑠𝑠 =.665 chart h4=-30kj/kg


point:5

h5= h4=-30kj/kg

point:6(S/H)

T6=110°C h6=2501+1.88(T6)=2707.8 kj/kg

point:7 (sat.liq)

T7=45°C h7=hf=188.4 kj/kg

point:8

h8= h7=188.4 kj/kg

point:1(sat.vap)

T7=2°C h1=hg=2504.2 kj/kg

C.C=mׄ(h1- h8)=470kw mׄ =0.203 kg/s

mׄss= 𝜆mׄ=4.151 kg/s

Mׄws=(1+ 𝜆)mׄ=4.354 kg/s


Generator energy balance:

Qׄg = 𝜆mׄ h4 + mׄ h6 - (1+ 𝜆)mׄ h3 = 1100.118 kw

𝑐.𝑐
Copcalc= =.427
𝑄ׄ 𝑔

Copcat= 1.08

𝑇𝑒 𝑇𝑎
Copmax= ( ) (1- ) =1.185
𝑇𝑐−𝑇𝑒 𝑇𝑔

Copcat> Copcalc Because the assumption of

You might also like