SPRINKLER LOCATION REQUIREMENTS 13-73

9.3.9.2 Protection Against Freezing. Sprinklers in exhaust The spacing of the sprinklers over the open -grid ceiling
ducts subject to freezing shall be properly protected against shall then comply with the following:
freezing. ( See 16.4. 1. ) (a ) In light hazard occupancies where sprinkler spacing
9.3.9.3 Sprinkler Access. Access shall be provided to all sprin- (either spray or old-style sprinklers) is less than 10 ft
klers for inspection , testing , and maintenance. x 10 ft (3 m x 3 m ) , a minimum clearance of at least
18 in . ( 450 mm ) shall be provided between the
9.3.9.4 Strainers. A listed line strainer shall be installed in the sprinkler deflectors and the upper surface of the
main water supply preceding sprinklers having nominal K- open -grid ceiling. Where spacing is greater than
factors smaller than K-2.8 ( 40 ) . 10 ft x 10 ft ( 3 m x 3 m ) but less than 10 ft x 12 ft
9.3.10* Open-Grid Ceilings. Open -grid ceilings shall only be ( 3 m x 3.7 m ) , a clearance of at least 24 in .
( 600 mm ) shall be provided from spray sprinklers
installed beneath sprinklers where one of the following is met:
and at least 36 in . ( 900 mm ) from old-style sprin-
(1) Open-grid ceilings in which the openings are '4 in . klers. Where spacing is greater than 10 ft x 12 ft
( 6 mm ) or larger in the least dimension , where the thick- ( 3 m x 3.7 m ) , a clearance of at least 48 in . ( 1.2 m )
ness or depth of the material does not exceed the least shall be provided.
dimension of the opening , and where such openings ( b ) In ordinary hazard occupancies, open -grid ceilings
constitute 70 percent of the area of the ceiling material . shall be permitted to be installed beneath spray
sprinklers only. Where sprinkler spacing is less than
10 ft x 10 ft ( 3 m x 3 m ) , a minimum clearance of at
A I II II II I
least 24 in . ( 600 mm ) shall be provided between the
|—I ZX I—I ZX I—I ZX I—I ZX h- sprinkler deflectors and the upper surface of the
-
hH I I I I h- open-grid ceiling. Where spacing is greater than
Complete
|H - h- H I—I I—I vertical 10 ft x 10 ft ( 3 m x 3 m ) , a clearance of at least
36 in . ( 900 m ) shall be provided.
-H h- H I—I h- H h- divider (2) Other types of open -grid ceilings shall be permitted to be
installed beneath sprinklers where they are listed for such
g -H ZX I—I ZX I—I ZX I—I service and are installed in accordance with instructions
” -H
8 —I
<D
I I I I
I—I

— —
h-H
I I I—I —
•Floor or

U - walkway —
either solid
| or with
_ ventilation
contained in each package of ceiling material.
9.3.11 Drop-Out Ceilings and Ceiling Materials.
“H I—I I—I I— I r openings 9.3.11.1* Drop-out ceilings and ceiling materials shall be
permitted to be installed beneath sprinklers where the ceiling
ZX I—I ZX I—I ZX I—I ZX h-
-H panels or ceiling materials are listed for that service and are
installed in accordance with their listings.
l -H l~ H I—I I—I h-
9.3.11.2 Drop-out ceilings and ceiling materials meeting the
i-- H I— I I—I EH h-
I—I
criteria in 9.3. 11.1 shall not be installed below quick-response
H -
h H -
hH h-
I or extended coverage sprinklers unless specifically listed for
that application.
FIGURE 9.3.7 (a ) Sprinklers in Multitier Bookstacks with 9.3.11.3 Drop-out ceilings and ceiling materials meeting the
Complete Vertical Dividers. criteria in 9.3. 1 1.1 shall not be considered ceilings within the
context of this standard.
1 I I
T -H h -H ZX h -H
I

h + H ZX h - 9.3.11.4* Piping installed above drop-out ceilings and ceiling


materials meeting the criteria in 9.3. 11.1 shall not be consid-
« -H h -H h -H h -H trU Incomplete
r vertical ered concealed piping.
IH h -H
h -H
h -H
h -H
hfH
h+H
|— divider
h-
9.3.11.5* Sprinklers shall not be installed beneath drop-out

£
I - H ZX h + H h + H ZX h + H h
^ Ventilation
ceilings or ceiling materials meeting the criteria in 9.3. 11.1 .
9.3.12* Old-style sprinklers shall be installed in fur storage
vaults.
h+H h+H h+ H |— openings
9.3.13 Stages.
h+H h+H h+ H h-
h+ H 9.3.13.1 Sprinklers shall be installed under the roof at the ceil-
h+H h+ H h-
ing, in spaces under the stage either containing combustible
materials or constructed of combustible materials, and in all
h + H ZX h + H h + H ZX h- adjacent spaces and dressing rooms, storerooms, and work-
h+H h+H h+ H h- shops.
h+H h+ H h+H h- 9.3.13.2 Where proscenium opening protection is required, a
h+ H
. -H h+H h+ H h- deluge system shall be provided with open sprinklers located
not more than 3 ft ( 900 mm ) away from the stage side of the
proscenium arch and spaced up to a maximum of 6 ft ( 1.8 m )
FIGURE 9.3.7 ( b ) Sprinklers in Multitier Bookstacks with on center. ( See Chapter 19 for design criteria. )
Incomplete Vertical Dividers.

2022 Edition