Professional Documents
Culture Documents
100 - Generator Stator Earth Fault Protection
100 - Generator Stator Earth Fault Protection
100 - Generator Stator Earth Fault Protection
Figure 1
b) Important Settings Parameters:
i) Resistance Conversion Factor: It can be seen that relay measures 20Hz
voltage & current in secondary terms. Resistance measured by the relay is
basically secondary resistance which needs to be converted to primary
resistance by some conversion factor. Let’s say relay is getting I20 Current and
V20 voltage.
Relay is getting 20Hz current through a miniature CT. So, actual 20Hz current
through NGT secondary will be 𝐼20 × 𝑀𝑖𝑛𝑖𝑎𝑡𝑢𝑟𝑒 𝐶𝑇 𝑅𝑎𝑡𝑖𝑜.
Relay is getting 20Hz voltage through voltage divider. So, actual 20Hz voltage
across NGT secondary will be 𝑉20 ÷ 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝐷𝑖𝑣𝑖𝑑𝑒𝑟 𝑅𝑎𝑡𝑖𝑜.
NGT Secondary resistance will be:
𝑉20
𝐼20 × 𝑀𝑖𝑛𝑖𝑎𝑡𝑢𝑟𝑒 𝐶𝑇 𝑅𝑎𝑡𝑖𝑜 × 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝐷𝑖𝑣𝑖𝑑𝑒𝑟 𝑅𝑎𝑡𝑖𝑜
To transfer this secondary resistance to NGT primary side, multiplication
with square of NGT ratio has to be done.
So primary side resistance will be:
𝑉 𝑁𝐺𝑇 𝑅𝑎𝑡𝑖𝑜 2
( 𝐼20 ) × 𝑀𝑖𝑛𝑖𝑎𝑡𝑢𝑟𝑒 𝐶𝑇 𝑅𝑎𝑡𝑖𝑜×𝑉𝑜𝑙𝑎𝑡𝑔𝑒 𝐷𝑖𝑣𝑖𝑑𝑒𝑟 𝑅𝑎𝑡𝑖𝑜
20
From this we can deduce the formula of Resistance Conversion Factor as:
𝑁𝐺𝑇 𝑅𝑎𝑡𝑖𝑜2
𝑅𝐶𝐹 =
𝑀𝑖𝑛𝑖𝑎𝑡𝑢𝑟𝑒 𝐶𝑇 𝑅𝑎𝑡𝑖𝑜 × 𝑉𝑜𝑙𝑎𝑡𝑔𝑒 𝐷𝑖𝑣𝑖𝑑𝑒𝑟 𝑅𝑎𝑡𝑖𝑜
The commissioning was done for a 250MW Generator.
NGT is rated as 15.75kV/240V.
Voltage Divider Ratio is 2/5.
Miniature CT ratio is 400/5.
So RCF is calculated to be 134.57. This data is given to generator protection
relay.
ii) Correction Angle:
In the resistance measurement, inaccuracies are incorporated due to
miniature CT phase angle error, and NGT transformation error. To
compensate these errors, an angle correction setting is used in the relay. It
will be adjusted during calibration period. Preliminarily it is set at 0°.
iii) Series Resistance:
If the connection circuit is observed carefully, it can be seen that in resistance
measurement, always NGT resistance will be included. This will be measured
later and will be compensated. Preliminarily this setting is kept at 0Ω.
iv) Trip and Alarm Settings:
In normal condition, it has been seen that generator stator resistance lies
around 40-100kΩ range. So, alarm settings is kept at 10kΩ with a time delay
of 10s and trip settings is kept at 2kΩ with a time delay of 1s. These
resistance values of 10kΩ & 2Ω are primary resistance values. If the relay
accepts secondary settings value, then these resistance values have to be
converted to secondary terms by dividing them with RCF. Resolution in relay
may not allow to input exactly these values. In that case nearest resistance
values may be incorporated.
Someone may think why we use 1s time delay for tripping when we know
this is a generator internal fault. Why we don’t make this protection tripping
instantaneous like differential protection?
First of all, this resistance measurement is based on a superimposed 20Hz
signal. So, lot of filtering and noise cleaning are associated with the
measurement process which requires some time for making a confirm
decision. In later testing it can be seen that the difference in 20Hz current
during fault and non-fault condition is very minimal. So, relay makes
subsequent measurements to improve the accuracy.
It was also mentioned earlier that first stator earth fault is not that
detrimental for the generator. So, a time delay of 1s can be spared to reach a
confirmed decision instead of generating wrong trip command
instantaneously.
c) Step 1 Injection:
With above settings, generator neutral isolator was kept open and 20Hz injection
was carried out. Following readings were taken from the relay:
20Hz Voltage (V20) 0.4V
20Hz Current (I20) 33mA
Secondary Resistance (R20sec) 13Ω
Primary Resistance (R20pri) 1749.41Ω
Angle between 20Hz voltage & current (Ɵ20) 0° to 1°
As generator neutral isolator was open, generator capacitance did not come in the
picture. The 20Hz current was divided in two parts. One was through the load
resistor and another was very small 20Hz magnetizing current of the NGT. Now as
the injection point of 20Hz voltage was before the miniature CT, the CT recorded the
current flow through load resistor which is 33 mA. So, the voltage across load
resistor was around (0.033×80×0.34) V or 0.89V and voltage across voltage divider
was around (0.89×2/5)V or 0.36V which is roughly shown as 0.4V by the relay.
Figure 2
d) Step 2 Injection:
After circuit rectification injection was done (Figure 3) and results were recorded:
20Hz Voltage (V20) 0.5V
20Hz Current (I20) 0.5mA
Secondary Resistance (R20sec) 9999Ω
Primary Resistance (R20pri) 9999.99 kΩ
Angle between 20Hz voltage & current (Ɵ20) 30° to 40°
Figure 3
In this case the current measured by CT is only the magnetising current of the NGT
from LV side i.e., 0.5 mA (sec) or 40 mA (Pri). Resistance measured is infinite which
is in order with the circuit.
e) Step 3 Injection:
Generator neutral isolator was closed. 20 Hz voltage was injected in this condition.
The results are shown in the table.
20Hz Voltage (V20) 0.4V
20Hz Current (I20) 11.7mA
Secondary Resistance (R20sec) 9999Ω
Primary Resistance (R20pri) 9999.99 kΩ
Angle between 20Hz voltage & current (Ɵ20) 87.5° to 92°
The 20Hz current flow in this condition is due to the generator capacitance only. The
current being a capacitive one should lead the voltage by around 90ᵒ. This is
complemented by test results. This phase angle sign may be different depending on
the convention adopted by different relay manufactures. If sign is found opposite
then miniature CT polarity is needed to be reversed.
f) Step 4 Injection:
According to Figure No. 4, a short circuit was applied across the star point of the
generator. Results are given in the table. The resistance value of 3Ω is the transfer
r
e
s
i
s
t
a
n
c
e
o
f
t
h
e
Figure 4
resistance of the NGT.
g) Step 5 Injection:
Then a variable resistor (decade box) was connected across the star point of the
generator and injection was done as per Figure 5. Fine tuning was done by varying
the correction angle settings. The test results are tabulated as below:
Resistance V20 I20 R20sec R20pri Ɵ20 Correction Angle
50 kΩ 0.4 V 11.1 mA 9996Ω 1344.46 kΩ -88.4ᵒ 0ᵒ
50 kΩ 0.4 V 11.1 mA 9996Ω 1344.46 kΩ -93ᵒ -6ᵒ
40 kΩ 0.4 V 11.2 mA 9996Ω 1344.46 kΩ -91.1ᵒ -6ᵒ
40 kΩ 0.4 V 11 mA 200 Ω 26.88 kΩ -81.3ᵒ +6ᵒ
40 kΩ 0.4 V 11 mA 224 Ω 31.43 kΩ -80.4ᵒ +4ᵒ
40 kΩ 0.4 V 11 mA 281 Ω 37.80 kΩ -85.1ᵒ +2ᵒ
30 kΩ 0.4 V 11 mA 244 Ω 31.43 kΩ -78.9ᵒ +2ᵒ
20 kΩ 0.4 V 10.8 mA 169 Ω 20.82 kΩ -76.6ᵒ +2ᵒ
10 kΩ 0.4 V 10.8 mA 84 Ω 11.36 kΩ -64.1ᵒ +2ᵒ
5 kΩ 0.4 V 11.6 mA 42 Ω 5.65 kΩ -48.9ᵒ +2ᵒ
2 kΩ 0.3 V 15.8 mA 17 Ω 2.33 kΩ -22ᵒ +2ᵒ
In this testing supervision threshold of 20Hz voltage settings was kept at 0.3V
(Range is 0.3V-15V) and supervision threshold of 20Hz current settings was kept at
5mA (Range is 5mA-40mA). Alarm settings was kept at 74 Ω (secondary) or 9958 Ω
(Primary) and trip settings was kept at 20 Ω(secondary) or 2691 Ω (Primary).
d
u
r
i
n
g
t
e
s
t
i
n
g
,
i
t
Figure 5
w
Now during testing, it was found that when the resistance was below trip settings,
tripping was issued from relay and up to 5kΩ resistance, alarm was also issued from
the relay. But above 5 kΩ, although resistance calculation was made correctly, no
alarm was coming from the relay. It was found that during testing up to 5kΩ
resistance no 20Hz generator failure event was appearing in the relay. But beyond 5
kΩ resistance, 20Hz generator failure alarm was appearing.
It may be noticed from the above table that 20Hz Biased Voltage i.e., V20 is
marginally equal to the supervision threshold of 20 HZ Voltage. This was the
probable cause of this 20Hz Generator failure alarm.
Biased voltage across the relay needed to be increased. So, it was decided to use full
ratio of voltage divider i.e., 5/5 instead of 2/5 ratio.
As voltage divider ratio was changed, resistance conversion factor also changed and
new RCF value of 53.8 was updated in the relay. Again, the test was repeated and test
results are tabulated below:
Resistance V20 I20 R20sec R20pri Ɵ20 Correction Angle
Open 1.1 V 11.5 mA 9996Ω 537.78 kΩ -89ᵒ +2ᵒ
Circuited
40 kΩ 1.1 V 11.2 mA 733Ω 39.43 kΩ -82.4ᵒ +2ᵒ
20 kΩ 1.0 V 10.9 mA 415Ω 22.31 kΩ -77.4ᵒ +2ᵒ
10 kΩ 1.0 V 11.0 mA 214Ω 11.53 kΩ -64.6ᵒ +2ᵒ
8 kΩ 1.0 V 11 mA 177 Ω 9.51 kΩ -60.5ᵒ +2ᵒ
5 kΩ 1.0 V 11.6 mA 111 Ω 5.96 kΩ -48.3ᵒ +2ᵒ
1.5 kΩ 0.7 V 17.8 mA 37 Ω 2.01 kΩ -14.5ᵒ +2ᵒ
The problem of 20Hz generator failure event did not arise as 20Hz biased voltage
was around 1 V, which is way above supervision threshold settings of 0.3 V.
h) Step 6 Injection:
Lastly one short circuit was applied at GT LV side and 100% SEF Tripping was
checked and was found to be in order. The test results are found as follows:
20Hz Voltage (V20) 0.3 V
20Hz Current (I20) 33.9 mA
Secondary Resistance (R20sec) 6Ω
Primary Resistance (R20pri) 0.31k Ω
Angle between 20Hz voltage & current (Ɵ20) 21.7ᵒ