1
Lineup Details/Model Selection
The maximum number of input and output points for the entire system is 256 points/384
pointsÚ1.
Product for extending I/O of extension cable
2 4 I/O module type.
Up to 16 extension modules can be connected. (Extension power supply modules and
(extension cable type) connector conversion modules are not included in the number of connected modules.)
Some products are powered.
Up to 4 high-speed pulse I/O modules can be connected.
For details, refer to “Rules for System Configuration” on p. 77.
Module for extending power supply if CPU Power can be supplied to I/O module, intelligent function module, and bus conversion
3 FX5 extension power supply module's internal power supply is insufficient. module.
module
Extension cable is enclosed. Up to 2 modules can be connected.
Up to 16 extension modules including the I/O module can be connected
Module with functions other than
5 FX5 intelligent function module input/output. (Extension power supply modules and connector conversion modules are not included in
the number of connected modules.)
Module for connecting FX5 Series (extension
6 Connector conversion module connector type) extension module. An extension module (extension connector type) for FX5 can be connected.
The maximum number of input and output points for the entire system is 256 points/384
pointsÚ1.
7 I/O module Product for adding extension connector type
Up to 16 extension modules can be connected. (Extension power supply modules and
(Extension connector type) inputs/outputs.
connector conversion modules are not included in the number of connected modules.)
Using this type of I/O module requires the connector conversion module.
Conversion module for connecting FX3 Series FX3 extension module can be connected only to the right side of the bus conversion module.
8 Bus conversion module
extension module. When using FX5-CNV-BUSC, a connector conversion module is required.
Board connected to front of CPU module to Up to 1 module can be connected to the front of the CPU module. (Expansion adapter
9 FX5 expansion board expand functions. can also be used.)
Adapter connected to left side of CPU Up to 2 communication adapters and up to 4 analog adaptersÚ2 (up to 6 adapters in total) can
10 FX5 expansion adapter module to expand functions. be connected on the left side of the CPU module. When 9 is used, the number is limited.
Module for extending power supply if CPU
11 FX3 extension power supply module's internal power supply is insufficient.
Up to 2 modules can be connected.
module The bus conversion module is required for use.
Extension cable is enclosed.
When using the FX3 extension power supply module, up to 8 modulesÛ3 can be used.
Module with functions other than
12 FX3 intelligent function module input/output. When not using the FX3 extension power supply module, up to 6 modulesÛ3 can be used.
The bus conversion module is required for use.
Up to 1 safety main module and up to 2 safety input extension modules can be connected.
Module for configuring a safety control Extension modules cannot be connected on the downstream side (right side) of any
13 FX5 safety extension module system. safety extension module.
Bus conversion modules and FX3 extension modules cannot be used simultaneously.
Û1: Supported by FX5U CPU modules Ver. 1.100 or later and by GX Works3 Ver. 1.047Z or later.
Û2: Up to 2 modules of the FX5-4A-ADP can be connected in the entire system.
Û3: Excluding some models
2 -1) I/O module (AC power supply/DC input type) (extension cable type)
Number of Power supply capacity No. of No. of
Model Function occupied input/ 5 V DC 24 V DC service I/O type input output
output points power supply power supply points points
FX5-32ER/ESÛ1 DC input (sink/source)/relay output
I/O module
250 mA 16 16
FX5-32ET/ESÛ1 (24 V DC service power 32 points 965 mA DC input (sink/source)/transistor (sink)
(310 mAÛ2) points points
built-in)
FX5-32ET/ESSÛ1 DC input (sink/source)/transistor (source)
Û1: Can be connected only to the AC power type system
Û2: Power supply capacity when an external power supply is used for input circuits.
2 -2) I/O module (DC power supply/DC input type) (extension cable type)
Number of Power supply capacity No. of No. of
Model Function occupied input/ 5 V DC 24 V DC I/O type input output
output points power supply power supply points points
FX5-32ER/DSÛ DC input (sink/source)/relay output
16 16
FX5-32ET/DSÛ I/O module 32 points 965 mA 310 mA DC input (sink/source)/transistor output (sink)
points points
FX5-32ET/DSS Û
DC input (sink/source)/transistor output (source)
Û: Can be connected only to the DC power type system
1 FX5-4LCÛ1
4-ch temperature control (resistance temperature detector/
thermocouple/micro voltage)
8 points 140 mA — 25 mA
FX5-20PG-PÛ1 Pulse output for 2-axis control (transistor output) 8 points — — 120 mA
Lineup Details/Model Selection
FX5-20PG-DÛ1 Pulse output for 2-axis control (differential driver output) 8 points — — 165 mA
FX5-40SSC-S Simple motion 4-axis control (SSCNET Ⅲ/H compatible) 8 points — — 250 mA
FX5-80SSC-S Simple motion 8-axis control (SSCNET Ⅲ/H compatible) 8 points — — 250 mA
FX5-40SSC-GÛ2 Motion 4-axis control (CC-Link IE TSN compatible) 8 points — — 240 mA
FX5-80SSC-GÛ2 Motion 8-axis control (CC-Link IE TSN compatible) 8 points — — 240 mA
FX5-CCLGN-MSÛ3 CC-Link IE TSN master/local 8 points — — 220 mA
FX5-ENETÛ4 Ethernet communication 8 points — 110 mA —
FX5-ENET/IPÛ4 EtherNet/IP communication, Ethernet communication 8 points — 110 mA —
FX5-CCL-MSÛ1 CC-Link system master/intelligent device station 8 pointsÛ5 — — 100 mA
FX5-CCLIEFÛ6 CC-Link IE Field Network intelligent device station 8 points 10 mA — 230 mA
FX5-ASL-M Û1
AnyWireASLINK system master 8 points 200 mA — 100 mAÛ7
FX5-DP-M Û4
PROFIBUS-DP master 8 points — 150 mA —
FX5-OPCÛ8 OPC UA communication 8 points — 110 mA —
Û1: Supported by FX5U/FX5UC CPU module Ver. 1.050 or later.
Û2: Supported by FX5U/FX5UC CPU module Ver. 1.230 or later.
Û3: Supported by FX5U/FX5UC CPU module Ver. 1.210 or later.
Û4: Supported by FX5U/FX5UC CPU module Ver. 1.110 or later.
Û5: When using FX5-CCL-MS as a master station, the number of remote I/O points on the network increases.
Û6: Supported by FX5U/FX5UC CPU module Ver. 1.030 or later.
Û7: This value does not include the supply current to slave modules (Max. 2 A).
Û8: Supported by FX5U/FX5UC CPU module Ver. 1.245 or later.
Û: Current consumption when an external power supply is used for the input circuits.
Lineup Details/Model Selection