Electronic Control Equipment
Electronic Control Equipment
Equipment
Integral Control
A115/00
Why choose an actuator with an integrated
control ?
■ FOR ENGINEERINGS : When conventional actuators equipped with
● Simplification and standardization of interface mod- position limits, torque limiters and eventually a
ules. proportional transmitter are integrated into a
process, complex electrical equipment must be
● Makes it possible to choose important functions
installed on site as follows:
before installation.
● reversing starters,
● control components,
■ FOR INSTALLATION OF ACTUATORS :
● positioners,
● Easy commissioning thanks to local controls.
● optional control components,
● Commissioning is possible with only the power
● and so on ...
connected.
● Time savings at commissioning.
It includes an additional important savings for :
● electronic board,
■ FOR EASY USAGE : ● start-up,
● Capable of modifying the control functions even dur-
● dimensional,
ing usage.
● documentation,
● Installation of additional functions on site at lower
● study.
costs.
● Easy to use thanks to local settings and controls. The INTEGRAL+ includes an important cost savings
in controls because all of the control components are
● Local controls are lockable in various positions. integrated into the actuator.
Power
Motor
Power
▲
Informations Information
Actuator
Control station
Local / Remote
Control
Actuator logic
▲
control Power
supply
Control
panel
Information
Integral + : a specific control for each need
REMOTE CONTROL
LOCAL CONTROL
Descriptions of possible functions :
■ CONTROLS: ■ PROTECTION:
E1 ➭ Remote control: Pulse command P1 ➭ Fuses:
● by means of contacts: external power supply Protection against short circuit.
or by electronic board
supplying power (24V) P2 ➭ Motor temperature sensor:
● maintained signal: one pulse for open, Efficient protection for the motor against overheating.
close or stop If the temperature in the winding is too high, the motor
● without maintained signal: actuator continues to supply is stopped. Restarting is possible only after the
function as long as the temperature decreases.
signal is maintained
P3 ➭ Torque limiteur:
and stops when
released The electronic board memorizes actions of the torque
limiter and prohibits restarting in the same rotational
Remote control specifications direction. This system guaranties a complete full stop
● Isolated by optocouplers even if the torque limiter pressure is released.
Voltage: 10 to 250V DC/AC
P4 ➭ Phase control:
●
● Current: 10 mA at 24V
Protects against incorrect 3 phase connection and
● Minimum pulse: 100ms includes an automatic phase correction.
● Time of rotational direction change : 50ms or 200ms
4 ■ SIGNALING :
E2 ➭ Proportional: (with positioner)
L1 ➭ Fault relay
● by current: 4 - 20 mA, 0 - 20 mA,
A fault signaling relay detects all malfunctions or unavail-
4 - 12 mA, 12 - 20 mA,
abilities and communicates this information remotely :
● by voltage: 0 - 10 V
● Power supply failure or blown fuse
Remote selector Proportional / pulse command
ESD: Emergency Shut Down for Open. or Close. ● Loss of a phase in 3 Ph
● Thermal motor protection tripped
E3 ➭ Local control at the actuator: ● Selector in "LOCAL" position
● By pulse signal: one pulse for open, close or stop ● No signal 4-20mA (exception: 0-10V or 0-20mA)
● By maintained signal: actuator continues to function
as long as the signal is maintained and stops when Possible choices between the following faults:
released
● Torque limiter open / close tripped
● Local / Remote / Off (stopping) selector lockable in all
3 positions
● Selector in "LOCAL" position not available
● “No signal” not available
E4 ➭ Local internal control: (positioner)
L2 ➭ Remote:
● For commissioning or testing
- 4 options available from 16 possiblities
● Automatic calibration according to selected signal
Timing control (optional) - 3 additional options can be added as an option:
Open/Close/Supply
This optional card will allow extension of the valve oper-
ation speed. The actuator operates by successive pulses Local (option):
adjusted at the card. One part of the stroke can have a - 3 LED's for Open/Close/Supply
normal operating speed and the other part an extended
speed control. An auxiliary limit switch gives the order to L3 ➭ Position transmitter: (with positioner)
switch from normal to slow speed. The adjustments are Transmitting the proportional position signal is of the
independent in both open and close direction. The oper- same scale as the input control signal
ating time for the full valve stroke can be set very long. Example : input 4-12 mA output 4-12 mA
The device is used to avoid hammer effects when open- Exception : input 0-10 V output 0-20 mA
ing and closing a valve.
Integral+ Layout
ACTUATOR Limit switch Torque limiter Potentiometer
Open / Close Open / Close
Motor
Heater Thermal
P2
Reversing
starter
LED's on board
Auto Rotation
phase Open Close Thermal Torque
correction direction
Fuse
P4 Programming
1
A = Standard
B A
P3
P1 1 POSITIONER
2
3
Optional E4
4 1 2 3 4 5 6 7 8 9 10
5
PROGRAMMABLE LOGIC
6 CONTROL
Fuse 7
TR Internal
supply
8
9
5
2 10
11
P1 12
13
LOCAL CONTROL
Opto- Reed Remote
links contact Off
Local
Fuse E3
Supply
24V DC
3
INDICATION
Jumper A B
P1 R1 14
Jumper A B
R2 15
Jumper A B
R3 16
17
18
Jumper A B
R4 19
20
21
L1
Fault Relay
L3
E1 L2 E2
L1 L2 L3 + - Input Output Analog
4 - 20 mA
Set point Controller Positioner
4 - 20 mA
Control
circuit
Motor
This option allows control by an analog signal in order to guarantee precision and frequency efficiencies that correspond
with those defined in our classification system of modulating needs.
1. The internal control loop shown above gives the possibility of reaching the correct open position quickly by meas-
uring the position of the valve. This will allow for a good flow efficiency through the valve without any hunting.
● Result : Modulating is more reliable and the actuator is used less, therefore reducing the actuator and valve wear.
2. While positioning is made locally via the internal control loop, the operation is not damaged by possible interfer-
ences from the position signal. The actuators reaction time during operation automatically acts like a filter for the
incoming signal.
● Result : Modulating is more stable and precise.
3. A precise setting of the valve's position with respect to the value of the incoming control signal is required for prop-
er operation.
The actuator can be set locally independant of the modulating system, thanks to the integrated positioner. This
operation is possible without using the incoming control signal.
● Result : Commissioning is easier and can be accomplished by one person.
Three specialized configurations
POSIGAM+ : POSITIONING EQUIPMENT FOR CLASS III ACTUATORS
Reminder :
Select intermediate positions, with good precision (less than 2 %),
Modulating
on average 360 times/day.
Class III
POSIGAM+ has proven to be the most reliable positioning equipment for Class III actuators.
It includes :
● A GAM-K positioner
● A precision feedback potentiometer of 1000 Ω, linearity < 0.5%
● A contactor based power circuit
50
40 60
Reminder :
30 70 Select intermediate positions, with high precision (less than 1 %),
Modulating
20 80
on a permanent basis every 2 or 3 seconds.
10 90 Class II
50
4045 5560
35 Reminder :
30
65
70 Fast positioning, with excellent precision (0,5 % or less),
25 75 Modulating
20
15
80
85 and continuous movement.
10 90 Class I