BP in Salah RB211-24G62 / DLE Onshore Power Generation (ONPG) M.A214
BP in Salah RB211-24G62 / DLE Onshore Power Generation (ONPG) M.A214
Confidential: This document is the property of Rolls-Royce and shall Supplier Name Rolls-Royce Energy Systems
not be used in any manner detrimental to the interest of the company.
Supplier Document Number GED00024914
Revision Number 2
Rolls-Royce Energy Systems Inc.
Revision Date 25-AUG-09
SEE GER 0207 FOR DRAWING DEFINITIONS API 546 AC GENERATOR DATA
Document Title
SHEET
Information Only
Preliminary – Do not use For Construction
For Approval
Purchaser review and comments shall not be assumed to indicate either responsibility
X Certified
or liability for accuracy and completeness of this document or to alter any contractual
Certified – As Built
terms and conditions.
Certified – As Installed
Purchaser Disposition Purchaser's Tag Numbers
RRESI PROGRAM SO-M.A214 1 Reviewed and No comment.
RRESI PRODUCT MO-60A21401 Submit final version of
Documents as required.
J-EG-080301
CUSTOMER PETROFAC KRECHBA
P.O. NO. IM0002 2 Revise and resubmit. Work
may proceed subject to
incorporation of changes
REFER TO DOCUMENT TRANSMITTAL LETTER FOR Name Date
indicated.
SPECIFIC INSTRUCTIONS
3 Revise and resubmit. Work
may not proceed.
Document Number
Rev
(Purchase Order Number - SDRL Code - Sequential No)
IM0002-D03-0001 3
40.0 Notes
Generators shall be continuously rated for the maximum potential power developed by the gas turbine driver when operating with the minimum site ambient temperature (Existing site
40.1
generators are 25.375 KVA @ 0.8 power factor)
40.2 Refer to Combustion Gas Turbine Data sheet for site conditions, utilities, area classification, noise limits and general requirement.
40.3 Neutral earthing resistor by generator supplier. Refer to sketch on page 5.
40.4 CTs : 3EA for O/C & E/F, 3EA for differential, 1EA for SBEF, 3EA to be supplied loose for differential protection.
40.5 20% normal or 17% (saturated). No negative tolerance.
40.6 Refer to generator specification no. JI 189-UU00-B-MJSP-000-0015 for full details.
40.7 Rogowski coil to be supplied and fitted with access to terminals for 'ON LINE' insulation check.
40.8 VTA: Vendor to advise, SBEF : Standby earth fault protection.
41.1 Type - AMS 42.1 Positive sequence Resistance (R1) %, Tot± 0.52 ± 15%
41.2 Frame Designation - 1250LC 42.2 Zero sequence Resistance (R0) %, Tot± 0.28 ± 15%
41.3 Degree of Protection IP55 42.3 Negative sequence Resistance (R2) %, Tot± 0.74 ± 15%
41.4 Synchronous Speed rpm 1500 42.4 Zero sequence Reactance (X0) % 9.8
41.5 1st critical speed rpm 1800 42.5 Negative sequence Reactance (X2) % 25.8
Direction of rotation seen towards
41.6 CW / CCW 42.6 Direct axis synchronous reactance (Xd) % Unsat/sat 160/157%
drive
41.7 Rated Voltage V 10000 42.7 Direct axis transient reactance (x'd) % Unsat/sat 35.4/31.9%
41.8 Rated Frequency Hz 50 42.8 Direct axis sub-transient reactance (X"d) % Unsat/sat 26.0/20.1%
41.9 Rated output at 40°C base kVA MW 20.3 42.9 Short circuit ratio - 0.637
44.0 Notes
44.1 VTA: Vendor to advise. NA : Not applicable
EQUIPMENT TAG NO. J-EG-080301 DOCUMENT NO. JB00-K-NNFE-080-0001
45.1 Voltage Constant Speed - 48.1 Radial - Drive end Sleeve Diameter 355 OD
45.1.1 Load change from 50 to 0% %, secs .+20, 2 48.2 Radial - Non drive end Sleeve Diameter 355 OD
45.1.2 Load change from 100 to 50% %, secs .+20, 2 48.3 Thurst bearing NA
45.1.3 Load changes from 0 to 50% %, secs -0.15, 1 48.4 Bearing vibration detector type / manufac. 3300 / Bently Nevada
45.1.4 Load changes from 50 to 100% %, secs -0.14, 1 48.5 Number in each bearing 2
45.2 Frequency Response - 48.6 Bearing temperature detector type PT 100
45.2.1 Sudden load change from 50 to 0% %, secs See Note, 53.2 48.7 Number in each bearing 1
45.2.2 Sudden load change from 100 to 50% %, secs See Note, 53.2 48.8 Method of bearing lubrication Forced
45.2.3 Sudden load change from 0 to 50% %, secs See Note, 53.2 48.9 Lubrication oil flow rate m3/h 2.94
45.2.4 Sudden load change from 50 to 100% %, secs See Note, 53.2 48.10 Lubrication oil pressure Barg 1.5
46.6 Nominal Exciter Response ratio 1/S 1.6 50.1 Alternator kW 2.4
46.7 Current at Alternator base kVA A 11.5 50.2 Exciter kW 0.4
46.8 Insulation Class - Stator / Rotor F/F 51.0 Aux. Cooling Fans -
46.9 Temp. rise class - Stass / Rotor B/B 51.1 Rating kW 18.5 per fan
CB 1 / 2 CB 2 / 3
NC
NC
CB3
NC CB1 NC CB2
10kV SWITCHBOARD
(BY PURCHASOR)
BY GTG SUPPLIER
G G G
G3 - NOTE 54.2
EXISTING PROPOSED
54.0 Remarks:
The regulation capability of the main AC generator and AVR syatem under steady state and transient conditions shall be voltage regulation grade, 2.33 (VR2.33) as defined in BS 4999 part 140.
54.1
Transient performance is defined with rated kVA at 0.8 p.f. rejected.
54.2 This data sheet uses a third generator - G3 (Plant No. J-XM-080301) which will be connected to the RHS of the existing 10kV switchboard No. J-EH-080001.