BP In Salah

RB211-24G62 / DLE Onshore Power Generation (ONPG)


M.A214
Supplier Document
API 546 AC GENERATOR DATA SHEET GED00024914
Division: Rolls-Royce Energy Systems Job Number JI-189
Author: Dennis O’Keefe
Purchase Order Number IM0002

Confidential: This document is the property of Rolls-Royce and shall Supplier Name Rolls-Royce Energy Systems
not be used in any manner detrimental to the interest of the company.
Supplier Document Number GED00024914

Revision Number 2
Rolls-Royce Energy Systems Inc.
Revision Date 25-AUG-09
SEE GER 0207 FOR DRAWING DEFINITIONS API 546 AC GENERATOR DATA
Document Title
SHEET
 Information Only
 Preliminary – Do not use For Construction
 For Approval
Purchaser review and comments shall not be assumed to indicate either responsibility
X Certified
or liability for accuracy and completeness of this document or to alter any contractual
 Certified – As Built
terms and conditions.
 Certified – As Installed
Purchaser Disposition Purchaser's Tag Numbers
RRESI PROGRAM SO-M.A214 1 Reviewed and No comment.
RRESI PRODUCT MO-60A21401 Submit final version of
Documents as required.
J-EG-080301
CUSTOMER PETROFAC KRECHBA
P.O. NO. IM0002 2 Revise and resubmit. Work
may proceed subject to
incorporation of changes
REFER TO DOCUMENT TRANSMITTAL LETTER FOR Name Date
indicated.
SPECIFIC INSTRUCTIONS
3 Revise and resubmit. Work
may not proceed.

4 No further review required. Signature

Document Number
Rev
(Purchase Order Number - SDRL Code - Sequential No)
IM0002-D03-0001 3

Drawing No: GED00024914 Front Rolls-Royce Energy Systems, Inc.


Rev.2, 25 AUG 2009 1 of 5 M.A214
Petrofac
AC GENERATOR DATA SHEET
1.0 Installation Site - KRECHBA
Quantity required - 1 EA
3.0 Item No./TagNo. - J-XM-080301
4.0 Serial No. - 8268123
5.0 Service - Main Generation
6.0 Manufacturer - ABB Automation Technology Products
PURCHASOR'S DATA
Design Output (MW) (Note 40.1) 18.7MW min. @ 40°C Current Transformers
7.0 MW B 31.0 B -
Max/Min (without negative tolerence) (Note 40.4)
8.0 Rated Power Factor - 0.8 31.1 In Phase Line End - Yes
9.0 Service Voltage V 10,000 31.2 In phase Neutral End - Yes
10.0 Rated Frequency Hz 50 31.3 In Neutral Connection - Yes
11.0 No. of Phases - 3 ph 32.0 Insulation Class - F
12.0 Duty Type - S1 33.0 Temperature Rise Class - B Total
13.0 Generator Neutral Earthing - Note 40.3 34.0 Vibration Detection - Yes
14.0 Earth Fault Current A 750A 35.0 Winding Temp. Detection - Yes
15.0 Neutral Earth Resistor Rating A, secs 750A, 10secs 36.0 Bearing Temp. Detection - Yes
16.0 Excitation - Brushless 37.0 Mounting - Foot
Direct Axis Sub-Transient Reactance
17.0 % 26.0/20.1 (unsat/sat) 38.0 Space Heater Voltage V B 230V AC
(Note 40.5)
18.0 Direct Axis Transient Reactance % 34.1/29.3 (unsat/sat) 39.0 Environmental Conditions - Note 40.2
19.0 Parallel Operation - Yes / No
20.0 Unbalanced Load - Yes / No
21.0 Surge Overvoltage Protection - Yes / No
22.0 Main Terminals -
22.1 Cable - Yes
22.2 Cable Size - 9X1CX630mm2
22.3 Cable Type - XLPEPVCSWAPVC
23.0 Neutral Terminal B -
23.1 Cable Size - 1X630mm2
23.2 Cable Type - XLPEPVCSWAPVC
24.0 Primary Coolant - AIR
25.0 Secondary Coolant - AIR
26.0 Cooling Classification - CACA
27.0 Cooling Temperature (Max / Min) °C 55 / -5
28.0 Area Classification - Note 40.2
29.0 Generator Enclosure Classification - Industrial
30.0 Generator Ingress Protection - IP55

40.0 Notes

Generators shall be continuously rated for the maximum potential power developed by the gas turbine driver when operating with the minimum site ambient temperature (Existing site
40.1
generators are 25.375 KVA @ 0.8 power factor)
40.2 Refer to Combustion Gas Turbine Data sheet for site conditions, utilities, area classification, noise limits and general requirement.
40.3 Neutral earthing resistor by generator supplier. Refer to sketch on page 5.
40.4 CTs : 3EA for O/C & E/F, 3EA for differential, 1EA for SBEF, 3EA to be supplied loose for differential protection.
40.5 20% normal or 17% (saturated). No negative tolerance.
40.6 Refer to generator specification no. JI 189-UU00-B-MJSP-000-0015 for full details.
40.7 Rogowski coil to be supplied and fitted with access to terminals for 'ON LINE' insulation check.
40.8 VTA: Vendor to advise, SBEF : Standby earth fault protection.

EQUIPMENT TAG NO. J-EG-080301 DOCUMENT NO. JB00-K-NNFE-080-0001

DESCRIPTION DATA SHEET FOR AC GENERATOR REVISION B PAGE 1 OF 4

Rolls-Royce No. GED00024914, Sheet 2 of 5


Petrofac
AC GENERATOR DATA SHEET
SUPPLIER'S DATA

Generator - 42.0 Generator Parameter (All) -

41.1 Type - AMS 42.1 Positive sequence Resistance (R1) %, Tot± 0.52 ± 15%
41.2 Frame Designation - 1250LC 42.2 Zero sequence Resistance (R0) %, Tot± 0.28 ± 15%
41.3 Degree of Protection IP55 42.3 Negative sequence Resistance (R2) %, Tot± 0.74 ± 15%
41.4 Synchronous Speed rpm 1500 42.4 Zero sequence Reactance (X0) % 9.8
41.5 1st critical speed rpm 1800 42.5 Negative sequence Reactance (X2) % 25.8
Direction of rotation seen towards
41.6 CW / CCW 42.6 Direct axis synchronous reactance (Xd) % Unsat/sat 160/157%
drive
41.7 Rated Voltage V 10000 42.7 Direct axis transient reactance (x'd) % Unsat/sat 35.4/31.9%
41.8 Rated Frequency Hz 50 42.8 Direct axis sub-transient reactance (X"d) % Unsat/sat 26.0/20.1%

41.9 Rated output at 40°C base kVA MW 20.3 42.9 Short circuit ratio - 0.637

Rated output at DE side max power Quadrature axis synchronous reactance


41.10 MW 28.3 42.10 %, Tot± Unsat/sat 97.0/94.6% ± 15%
10° C (Xq)
41.11 Power factor cos phi 0.8 42.11 Quadrature axis transient reactance (X'q) %, Tot± NA
Quadrature axis sub-transient reactance
41.12 Duty type S1 42.12 %, Tot± Unsat/sat 35.2/30.0 ± 15%
(x"q)
Direct axis O.C. transient time constant
41.13 Rated Current A 1465 42.13 secs 6.07
(T'do)
Direct axis S.C. transient time constant
41.14 Thermal rating - IEC 60034-1 42.14 secs 0.914
(T'ds)
Max. allowable neg. phase seq. Direct axis O.C. sub-transient time
41.15 % 8 42.15 secs 0.04
current constant (T"do)
Max. allowable content of Direct axis S.C. sub-transient time
41.16 % 0 42.16 secs 0.019
overharmonics constant (T"ds)
Quadrature axis O.C. transient time
41.17 Efficiency - 100% base kVA % 97.88 42.17 secs NA
constant (T'qo)
Quadrature axis S.C. transient time
41.18 Efficiency - 75% base kVA % 97.66 42.18 secs NA
constant (T'qs)
Quadrature axis O.C. transient time
41.19 Efficiency - 50% base kVA % 97.04 42.19 secs 0.113
constant (T"qo)
Quadrature axis S.C. transient time
41.20 Field current No Load A 208.6 42.20 secs 0.041
constant (T"qs)
41.21 Field current Full Load A 494 42.21 Potier Reactance (Xp) %, Tot± 37.10%
41.22 Insulation Class - Stator / Rotor F/H 42.22 Damping factor - 3.2
41.23 Temp. rise Class - Stator / Rotor B total / B total 42.23 Saturation factor - 1.2
41.24 Overload Capability %, hrs % hrs 42.24 Basic Impulse level kV 45
41.25 Overload Capability %, secs 203% 10 secs 43.0 Dimensions & Weights -
41.26 Sustained Short Circuit %, secs 300% 10 secs 43.1 Overall Dimensions - LxWxH 5310mm x 8502 mm x 6150 mm
41.27 Moment of Inertia Rotor kg m2 3205 43.2 Weight of Machine kg 75000
41.28 Cooling Method IC6A1A6 43.3 Weight of Stator kg 27150
41.29 Cooling water flow rate m3h NA 43.4 Weight of heat exchanger - (Dry) kg 16500
41.30 Cooling water design pressure Barg NA 43.5 Weight of coolant kg NA
41.31 Leak Detection System NA

44.0 Notes
44.1 VTA: Vendor to advise. NA : Not applicable
EQUIPMENT TAG NO. J-EG-080301 DOCUMENT NO. JB00-K-NNFE-080-0001

DESCRIPTION DATA SHEET FOR AC GENERATOR REVISION B PAGE 2 OF 4

Rolls-Royce No. GED00024914, Sheet 3 of 5


Petrofac
AC GENERATOR DATA SHEET
SUPPLIER'S DATA

System Response - 48.0 Bearings -

45.1 Voltage Constant Speed - 48.1 Radial - Drive end Sleeve Diameter 355 OD
45.1.1 Load change from 50 to 0% %, secs .+20, 2 48.2 Radial - Non drive end Sleeve Diameter 355 OD
45.1.2 Load change from 100 to 50% %, secs .+20, 2 48.3 Thurst bearing NA
45.1.3 Load changes from 0 to 50% %, secs -0.15, 1 48.4 Bearing vibration detector type / manufac. 3300 / Bently Nevada
45.1.4 Load changes from 50 to 100% %, secs -0.14, 1 48.5 Number in each bearing 2
45.2 Frequency Response - 48.6 Bearing temperature detector type PT 100
45.2.1 Sudden load change from 50 to 0% %, secs See Note, 53.2 48.7 Number in each bearing 1
45.2.2 Sudden load change from 100 to 50% %, secs See Note, 53.2 48.8 Method of bearing lubrication Forced
45.2.3 Sudden load change from 0 to 50% %, secs See Note, 53.2 48.9 Lubrication oil flow rate m3/h 2.94

45.2.4 Sudden load change from 50 to 100% %, secs See Note, 53.2 48.10 Lubrication oil pressure Barg 1.5

46.0 Exciter - 49.0 Windings -


46.1 Type - GLA 600D 49.1 Stator connection Y
46.2 Full Load Current (40°C) A 11.5 49.2 Number of stator winding terminals 12
46.3 Full Load Voltage V 61 49.3 Winding temperature detector type PT 100
46.4 Ceiling Current (40°C) A 22.3 49.4 Number in each phase 2

46.5 Ceiling Voltage V 124 50.0 Heater Rating - -

46.6 Nominal Exciter Response ratio 1/S 1.6 50.1 Alternator kW 2.4
46.7 Current at Alternator base kVA A 11.5 50.2 Exciter kW 0.4
46.8 Insulation Class - Stator / Rotor F/F 51.0 Aux. Cooling Fans -

46.9 Temp. rise class - Stass / Rotor B/B 51.1 Rating kW 18.5 per fan

47.0 AVR - 51.2 Manufacturer ABB


47.1 Model No. DECS-200 51.3 Frame Design 180
47.2 Manufacturer Basler Electric 51.4 Number Off 3
47.3 Range of No Load Adjustment ±10% 51.5 Duty % 3 x 50%
47.4 Accuracy % ±0.25 52.0 Neutral Earthing Resistor -
47.5 Forward Gain (KA) - 1 52.1 Type Edgewound RP
47.6 Feedback Gain (KF) - Acc. To setting list 52.2 Resistance Ohms 7.7
47.7 Regular Amplifier Time Constant (TA) secs 0 52.3 Resistance rating A, secs 750 / 10
47.8 Regular Feedback Time Constant (TF1) secs < 1cycle 52.4 Degree of Protection IP54
47.9 Max. Regulator Output (VR MAX) p.u. 6.9
47.10 Min. Regulator Output (VR MIN) p.u. 0
47.11 Max. rate of change of Reg. output (VRMAX) Traverse rate 10s
47.12 Input Filter Time Constant (TR) secs 0.005
47.13 Exciter Gain (KE) - 1 p.u.
47.14 Exciter Time Constant (TE) secs 0.49
47.15 Exciter Output (E MAX) - 4.9 p.u.
47.16 Exciter Output (E MIN) No sturation in exciter 1
47.17 Exciter saturation at 75% E MAX (SE75) No sturation in exciter 1
47.18 Exciter saturation at 100% E MAX (SE100) No sturation in exciter 1
47.19 IEEE Model Type - AC8B
47.20 Regulator Feedback Time Constant (TF2) secs < 1cycle

53.0 Notes / Remarks


53.1 AVR data will be given as a transfer function.
53.2 R-R to advise subsequent details from test data report document after system test.
53.3 VTA: Vendor to advise.
EQUIPMENT TAG NO. J-EG-080301 DOCUMENT NO. JB00-K-NNFE-080-0001

DESCRIPTION DATA SHEET FOR AC GENERATOR REVISION B PAGE 3 OF 4

Rolls-Royce No. GED00024914, Sheet 4 of 5


Petrofac
AC GENERATOR DATA SHEET
SYSTEM DATA

CB 1 / 2 CB 2 / 3

10kV BOARD No.


J-EH-080001

NC

NC
CB3
NC CB1 NC CB2

10kV SWITCHBOARD
(BY PURCHASOR)

BY GTG SUPPLIER

G G G
G3 - NOTE 54.2

N.E.R. N.E.R. N.E.R.


750 A 750 A 750 A
10 SECS 10 10 SECS
7,7 OHMS SECS 7,7 OHMS
7,7
OHMS

*N.E.R. - NEUTRAL EARTHING


RESISTOR

EXISTING PROPOSED

54.0 Remarks:
The regulation capability of the main AC generator and AVR syatem under steady state and transient conditions shall be voltage regulation grade, 2.33 (VR2.33) as defined in BS 4999 part 140.
54.1
Transient performance is defined with rated kVA at 0.8 p.f. rejected.
54.2 This data sheet uses a third generator - G3 (Plant No. J-XM-080301) which will be connected to the RHS of the existing 10kV switchboard No. J-EH-080001.

EQUIPMENT TAG NO. J-EG-080301 DOCUMENT NO. JB00-K-NNFE-080-0001

DESCRIPTION DATA SHEET FOR AC GENERATOR REVISION B PAGE 4 OF 4

Rolls-Royce No. GED00024914, Sheet 5 of 5