JB00 K Nnfe 080 0001
JB00 K Nnfe 080 0001
XLS 22-10-2007
PAGE 1 OF 5
0 12-08-09 ISSUED FOR CANCELLATION AH HK PNP SK
B 16-03-08 ISSUED FOR REVIEW SA PNP TP SK
A 06-02-08 ISSUED FOR INQUIRY SA PNP TP SK
REV DATE DESCRIPTION PRPD CKD APPD APPD CLIENT APPD PEC JOB NO : JI-189 ISG JOB NO :
AREA KRCHBA
17.0 Direct Axis Sub-Transient Reactance % Note 40.5 38.0 Space Heater Voltage V 440 / 230V AC
18.0 Direct Axis Transient Reactance % VTA 39.0 Environmental Conditions - Note 40.2
19.0 Parallel Operation - Yes / No
20.0 Unbalanced Load - Yes / No
21.0 Surge Overvoltage Protection - Yes / No
22.0 Main Terminals -
22.1 Cable - Yes
22.2 Cable Size - 9X1CX630mm2
22.3 Cable Type - XLPEPVCSWAPVC
23.0 Netral Terminal -
23.1 Cable Size - 1X630mm2
23.2 Cable Type - XLPEPVCSWAPVC
24.0 Primary Coolant - AIR
25.0 Secondary Coolant - AIR
26.0 Cooling Classification - CACA
27.0 Cooling Temperature (Max / Min) °C 55 / -5
28.0 Area Classification - Note 40.2
29.0 Generator Enclosure Classification - Industrial
30.0 Generator Ingress Protection - IP55
40.0 Notes
Generators shall be continuously rated for the maximum potential power developed by the gas turbine driver when operating with the minimum site ambient temperature (Existing site
40.1
generators are 25.375 KVA @ 0.8 power factor)
40.2 Refer to Combustion Gas Turbine Data sheet for site conditions, utilities, area classification, noise limits and general requirement.
40.3 Neutral earthing resistor by generator supplier. Refer to sketch on page 5.
40.4 CTs : 3EA for O/C & E/F, 3EA for differential, 1EA for SBEF, 3EA to be supplied loose for differential protection.
40.5 20% normal or 17% (saturated). No negative tolerance.
40.6 Refer to generator specification no. JI 189-UU00-B-MJSP-000-0015 for full details.
40.7 Rogowski coil to be supplied and fitted with access to terminals for 'ON LINE' insulation check.
40.8 VTA: Vendor to advice, SBEF : Standby earth fault protection.
41.1 Type - VTA 42.1 Positive sequence Resistance (R1) %, Tot± ± 15%
41.2 Frame Designation - VTA 42.2 Zero sequence Resistance (R0) %, Tot± ± 15%
41.3 Degree of Protection IP55 42.3 Negative sequence Resistance (R2) %, Tot± ± 15%
41.4 Synchronous Speed rpm 1500 42.4 Zero sequence Reactance (X0) %, Tot± ± 15%
41.5 1st critical speed rpm VTA 42.5 Negative sequence Reactance (X2) %, Tot± ± 15%
Direction of rotation seen towards
41.6 CW / CCW 42.6 Direct axis synchronous reactance (Xd) %, Tot± Unsat/sat ± 15%
drive
41.7 Rated Voltage V 10000 42.7 Direct axis transient reactance (x'd) %, Tot± Unsat/sat ± 15%
41.8 Rated Frequency Hz 50 42.8 Direct axis sub-transient reactance (X"d) %, Tot± Unsat/sat ± 15%
41.9 Rated output at 40°C base kVA MW VTA 42.9 Short circuit ratio - VTA
44.0 Notes
44.1 VTA: Vendor to advice. NA : Not applicable
45.1 Voltage Constant Speed - 48.1 Radial - Drive end Sleeve Diameter
45.1.1 Load change from 50 to 0% %, secs VTA 48.2 Radial - Non drive end Sleeve Diameter
45.1.2 Load change from 100 to 50% %, secs VTA 48.3 Thurst bearing NA
45.1.3 Load changes from 0 to 50% %, secs VTA 48.4 Bearing vibration detector type / manufac. 3300 / Bently Nevada
45.1.4 Load changes from 50 to 100% %, secs VTA 48.5 Number in each bearing 2
45.2 Frequency Response - 48.6 Bearing temperature detector type PT 100
45.2.1 Sudden load change from 50 to 0% %, secs VTA 48.7 Number in each bearing 1
45.2.2 Sudden load change from 100 to 50% %, secs VTA 48.8 Method of bearing lubrication Forced
45.2.3 Sudden load change from 0 to 50% %, secs VTA 48.9 Lubrication oil flow rate m3/h VTA
45.2.4 Sudden load change from 50 to 100% %, secs VTA 48.10 Lubrication oil pressure Barg VTA
46.2 Full Load Current (40°C) A VTA 49.2 Number of stator winding terminals 12
46.3 Full Load Voltage V VTA 49.3 Winding temperature detector type PT 100
46.4 Ceiling Current (40°C) A VTA 49.4 Number in each phase 2
46.6 Nominal Exciter Response ratio 1/S VTA 50.1 Alternator kW VTA
46.7 Current at Alternator base kVA A VTA 50.2 Exciter kW VTA
46.8 Insulation Class - Stator / Rotor F/F 51.0 Aux. Cooling Fans -
46.9 Temp. rise class - Stass / Rotor B/B 51.1 Rating kW VTA
CB 1 / 2 CB 2 / 3
NC
NC
CB3
NC CB1 NC CB2
10kV SWITCHBOARD
(BY PURCHASOR)
BY GTG SUPPLIER
G G G
G3 - NOTE 54.2
EXISTING PROPOSED
54.0 Remarks:
The regulation capability of the main AC generator and AVR syatem under steady state and transient conditions shall be voltage regulation grade, 2.33 (VR2.33) as defined in BS 4999 part 140. Transient
54.1
performance is defined with rated kVA at 0.8 p.f. rejected.
54.2 This data sheet uses a third generator - G3 (Plant No. J-XM-080301) which will be connected to the RHS of the existing 10kV switchboard No. J-EH-080001.