Chiller selection Software

Version 4.45 (01-MAY-2009) - Copyright © 2000-2009, Carrier Corp.

* Project
Date 1/24/2013 5:20:11 PM
Location
Company name
Contact name
CARRIER reference

* Product 30HXC080-PH3-opt60
Range 30HXC Phase3 Option60 (460-3-60)

* List of the options selected :


Option 33 or 34A (90-10 CU/NI condenseur) - Sea water

Gross capacity 271 kW


Unit absorbed power 62 kW
Compres. Input power 62 kW
C.O.P. 4.4
No of capacity steps 6
Minimum step 19 %
Refrigerant R134a
Expansion valve EXV

* Evaporator
Fluid Water
Leaving T. 7 °C
Delta T. 10 K
Entering T. 17 °C
Flow rate 6.48 L/s
Evaporator pressure drop 13 kPa
Fouling factor 0.04403 m²-K/kW
Max operating pressure 1000 kPa

* Condenser
Fluid Sea water
Entering T. 32 °C
Delta T. 4 K
Leaving T. 36 °C
Flow rate 19.7 L/s
Pressure drop 43 kPa
Fouling factor 0.088 m²-K/kW
Max operating pressure 1000 kPa

T.H.R. 330 kW

* No of compressors 2
Compressor type screw
Compressor motor speed 58.4 r/s
Starter type WYE/DELTA

* Volts/Phases/Hertz 460-3-60
Power Factor (at max power) 0.85
Maximum current drawn 122 A (U nom.)
Maximum starting current 165 A
Voltage limits 414/506 V

* Operating weight 2274.0 kg


Refrigerant charge 67 kg
Length/Width/Height 2557.4 mm
980 mm
1800 mm

* Acoustic power (dB ref. 1e-12 W) (Full load)


Octave band (Hz)
125 250 500 1K 2K 4K 8K Global
Lw 79 84 89 88 90 84 79 95
Lw(A) 63 75 86 88 91 85 78 94
Global Acoustic power dB(A), according to EUROVENT standard = 94

Average acoustic pressure (dB ref. 2e-5 Pa). Distance 5 m


Octave band (Hz)
125 250 500 1K 2K 4K 8K Global
Lp 52 57 62 61 63 57 52 68
Lp(A) 36.3 48.8 59 61 65 58 51 68
Global pressure level in dB(A) = 68

Estimated average sound pressure Lp at a given distance on a reflective surface in a free field environment.
Estimated Sound Power levels given above are assumed to originate at the acoustic center of the chiller.