Design Summary for Sport Hall Building

Fresh air Exhaust air


AC Unit Ref Space Name Floor No. AC system Type Area (m2) Indoor Conditions
(L/s) (L/s)

PU-02 SPORT HALL G-01 SPORT HALL Package Unit 436 23 ± 1 Dry Bulb @ 50% ± 5 % RH 1500 -
Toilets - SPORT HALL - - - - 525
Store - SPORT HALL - - - - 130
DSU-01 SPORT HALL G-04 SPORT HALL Ducted Split System 17.5 23 ± 1 Dry Bulb @ 50% ± 5 % RH - -
DSU-02 SPORT HALL G-05 SPORT HALL Ducted Split System 17.5 23 ± 1 Dry Bulb @ 50% ± 5 % RH - -
Total Fresh Air for Main School building 1500 L/s

SELECTION SHALL BE BASED ON:


- AMBIENT TEMPERATURE = 46°C DB
- MAXIMUM OPERATING TEMP. 55°C DB
- ALL UNITS TO BE CONTROLLED BY ROOM THERMOSTATS
- SELECTION SHALL BE BASED ON MEDIUM SPEED
CCTV EQUIP. ROOM 9 1.7
CCTV ROOM 9 3.5
GUARD ROOM 13.5 3.5
GUARD-TELECOM ROOM 7.5 2.7
SERVICES ROOM 9 1.9
1.4 21.9 / 16.613.0 / 12.5
3.1 21.6 / 16.112.8 / 12.3
3 21.8 / 16.413.1 / 12.6
2.5 21.1 / 15.712.8 / 12.3
1.6 21.7 / 16.413.0 / 12.5
Offered
Carrier Tag Model Air Flow L/S Total KW Sensible KW

SU-01 42KHB018H ** 4.69 4.69


SU-02 42KHB024H ** 5.80 5.80
SU-03 42KHB030HN ** 7.97 7.97
SU-04 42KHB036HNN ** 9.09 9.09

12.61/9.03 53KDMT18N-718 247 4.05 3.44


12.64/9.22 53KDMT24N-718 334 5.49 4.62
11.61/8.57 53KDMT30N-718 541 7.31 6.78
11.91/8.64 53KDMT36N-718T 541 9.02 7.40
12.84/8.9 53KDMT42N-518T 538 9.53 8.55
Input Power Dimension LxWxH
AC Type
W mm
1760.00 630X558X233 Split System Split System Rentable
2300.00 780X558X233 Split System Ducted Split Services
3200.00 880X558X233 Split System
3735.00 930X558X233 Split System

1642.00 920 × 270 × 635 Ducted Split System


2199.00 920 × 270 × 635 Ducted Split System
3313.00 1200 × 300 × 865 Ducted Split System
3580.00 1200 × 300 × 865 Ducted Split System
3666.00 1200 × 380 × 625 Ducted Split System