DB-G-D-R-003 - Dynamic Load Report at Pile-3 - A1
DB-G-D-R-003 - Dynamic Load Report at Pile-3 - A1
DB-G-D-R-003 - Dynamic Load Report at Pile-3 - A1
Green Concrete
Ground Floor ,11/15 Tajmohol Road,Mohmmedpur, Dhaka - 1208, Bangladesh
CONTENT
1. INTRODUCTION ............................................................................................................... 2
5. RESULTS ............................................................................................................................ 5
6. CONCLUSION .................................................................................................................... 7
1. INTRODUCTION
1.1 General
This report is prepared to represent the bearing capacity of cast-in- place bored pile from
dynamic load test at Unit-2, South End Sweater Co. Ltd at Ashulia. The test was conducted
by GC in presence of professional trained person on date 7th July 2022. This report contains
the load bearing capacity, total resistance, skin friction and integrity condition of pile.
Reference Standard:
ASTM D 4945: Standard Test Method for High-Strain Dynamic Testing of Piles
Reference Document:
2. LOCATION OF TEST
Physical description of test piles and equipment used are provided in Table 1 and table 2
below.
3 Cables Pcs 2
4. WORK FLOWCHART
The work sequence of dynamic testing of piles works is described in the following flow-
charts.
1. Preparation of pile
Investigation
3. Setting of Equipment
5. Analyzing of Report/Data
5. RESULTS
3.431 MN
Mobilized Static Resistant Shaft
(349.7 Mt)
0.098 MN
Mobilized Static Resistant Toe
(10.0 Mt)
3.529 MN
Mobilized Total Static Resistance
(359.73 Mt)
4.674 MN
Ultimate Capacity As Per Modelled Result
(476 Mt)
Higher than 3.529 MN
Ultimate Capacity As Per IS 2911 (IV) - a
(359.73 Mt)
>239.82 Mt
Safe Capacity As Per IS 2911 (IV)-b
6. CONCLUSION
In PDA/DLT system, the process of analysis is based on dynamic pile capacity. After having
the information of soil dynamic parameters, the dynamic capacity can be easily converted to
static capacity. BNBC 2020 & IS 2911 (IV) has provided guidelines for interpreting the static
pile capacity and settlement criteria:
a) Two thirds of the final load at which the load displacement attains a value of 12 mm unless
otherwise required in a given case on the basis of nature and type of structure in which
case, the safe load should be corresponding to the stated total displacement permissible.
b) Fifty (50) percent of the final load at which the total displacement equals to 10 percent of
pile diameter case of uniform diameter piles and 7.5 percent of bulb diameter in case of
under-reamed piles.
For TP-3, the gross settlement obtained from this load test is 6.0 mm and net settlement is
1.50 mm according to TNO Soil Model.
According to BNBC 2020 criteria (a), the allowable capacity is two thirds of the final load at
which the load displacement attains a value of 12 mm. For Test TP-3, the gross settlement
obtained from the load was less than 12 mm, so according to BNBC 2020 criteria (a) the
ultimate bearing capacity is less than the mobilised static resistance for the pile as mentioned
in the above table.
According to BNBC 2020 criteria (b), the gross settlement value was far less than 10 percent
of pile diameter (500*0.1= 50 mm). So, the ultimate bearing capacity can,t be defined from
test result but can be define from modelled static load test curve.
From the above criteria & outcome pile capacity can be consider 359.73 Mt with a settlement
6.0mm & modelled ultimate capacity 476 Mt with a settlement 100 mm.
However, Static capacity may also decrease or increase over time after the pile installation, and
both static and dynamic tests represent the capacity at the time of the respective test. Correlations
between measured ultimate axial static compression capacity and dynamic test estimates generally
improve when using dynamic restrike tests that account for soil strength changes with time.
Input Data
----------
Dimensions Data
Material Data
Part Number E - Density
Modulus
[MPa] [kg/m3]
Pile 1 40000 2400
Output Data
-----------
Total mobilised static resistance 3.529 [MN]
Static mobilised shaft resistance 3.431 [MN]
Static mobilised toe resistance 0.098 [MN]
Soil Borelog
Depth in feet
Sample Type
Boring Dia
Graphics
Discription of Classification (Visual)
15cm
15cm
15cm
30cm
0 10 20 30 40 50 60 70 80 90 100
10.64 35 7 10 12 22 D-7
12.16 40 6 12 14 26 D-8
13.68 45 8 14 20 34 D-9
Light Brown medium dense to dense
fine SAND with little to trace some
15.20 50 silt and mica
9 13 18 31 D-10
16.72 55 12 19 22 41 D-11
18.24 60 7 9 19 28 D-12
19.76 65 8 10 15 25 D-13
22.80 75 12 17 20 37 D-15
24.32 80 13 20 25 45 D-16
28.88 95 19 30 20 50 D-19
Calibration Certificates
Sensor data
Serial number AC1147
Type Piezoresistive accelerometer
Range > (-5000…+5000) g
Frequency range DC to > 8000 Hz
Damping ratio 0.7
Electrical Test:
Offset +/- [mV] @ 10V
Input impedance 1671 [Ω]
Output impedance 887 [Ω]
Operating temp. -40 to 120 [°C]
Max. excitation 12 [V]
Calibration data
Sensitivity @ 1000g, 700 Hz 0.0276 [mV/g] @ 10 V excitation
Note: The above accelerometer has been calibrated against a reference instrument traceable to ISO 5347.
Calibration Certificate of
the Profound acceleration sensor
Sensor data
Serial number AC1149
Type Piezoresistive accelerometer
Range > (-5000…+5000) g
Frequency range DC to > 8000 Hz
Damping ratio 0.7
Electrical Test:
Offset +/- [mV] @ 10V
Input impedance 1670 [Ω]
Output impedance 886 [Ω]
Operating temp. -40 to 120 [°C]
Max. excitation 12 [V]
Calibration data
Sensitivity @ 1000g, 700 Hz 0.0265 [mV/g] @ 10 V excitation
Note: The above accelerometer has been calibrated against a reference instrument traceable to ISO 5347.
Calibration Certificate of
the Profound strain sensor
Sensor data
Serial number ST1289
Strain range -2000…+2000 µm/m (IAW ASTM D4945-17)
Bridge resistance 350 Ohm
Strain gauges 4 foil gauges
Insulation resistance >10 GOhm
Cable Unitronic FD P plus 4x 0.14
Wiring:
Calibration data
Static Calibration Number 4.70
Sensitivity (S) 2.35 µV/V.µStrain
Zero load output 1.8 µV/Volt
Sensor data
Serial number ST1290
Strain range -2000…+2000 µm/m (IAW ASTM D4945-17)
Bridge resistance 350 Ohm
Strain gauges 4 foil gauges
Insulation resistance >10 GOhm
Cable Unitronic FD P plus 4x 0.14
Wiring:
Calibration data
Static Calibration Number 4.24
Sensitivity (S) 2.12 µV/V.µStrain
Zero load output 35.6 µV/Volt
Inspection Documents
Pile Drawing
Test Image