Professional Documents
Culture Documents
PSCO CHapter 1
PSCO CHapter 1
Chapter one
• Protective zones
Relaying elements and quantities, Operating
principles of relays
Relay types and characteristics
Protection of transmission lines, generators,
motors and transformers.
4/12/2022 1
INTRODUCTION
• The primary function of a protection system in an electrical
power network is to ensure the continuity of the electricity
supply.
• Protection scheme required for the protection of power system
components against abnormal conditions.
Essentially consists of protective relaying and Circuit Breakers
Protective relay functions as sensing device, it senses the fault,
then determines its location and finally, it sends tripping
command to the CB
4/12/2022 2
ZONE OF PROTECTION
4/12/2022 3
ZONE OF PROTECTION
• Each zone is defined by a closed, dashed line. As shown in
Figure below, Zone 1 for example, contains a generator
and connecting leads to a transformer ,.
• In some cases a zone may contain more than one
component.
• For example, Zone 3 contains a generator-transformer unit
and connecting leads to a bus, and Zone 10 contains a
transformer and a line.
• Protective zones have the following characteristics:
– Zones are overlapped.
– Circuit breakers are located in the overlap regions.
– For a fault anywhere in a zone, all circuit breakers in that
zone open to isolate the fault.
4/12/2022 4
ZONE OF PROTECTION……
4/12/2022 5
PROTECTIVE RELAYS
Relay is a device that detects the fault and initiates the operation of
the CB to isolate the defective element from the rest of the system.
4/12/2022 6
Relay circuit
It consist of three parts,
1.Primary winding of a CT is connected in
series with the line to be protected.
2.Secondary winding of CT and the relay
operating Coil.
3. Tripping circuit which may be either AC or
DC. It consists of a Source of supply, trip coil
of CB and the relay stationary contact.
4/12/2022 7
Requirements/Qualities of Protective Relaying
Selectivity
It is the ability of the protective system to select correctly part
of the system in trouble and disconnect the faulty part without
disturbing the rest of the system.
Speed
The relay system should disconnect the faulty section as fast as
possible.
Electrical apparatus may be damaged if they are made to carry
the fault currents for a long time.
A relay must operate at the required speed.
4/12/2022 8
Sensitivity
It is the ability of the relay system to operate with low value
of actuating quantity.
Reliability
It is the ability of the relay system to operate under the pre-
determined conditions.
• Without reliability, the protection would be rendered largely
ineffective and could even become a liability.
Simplicity
• The relaying system should be simple so that it can be
easily maintained.
• Reliability is closely related to simplicity.
• The simpler the protection scheme, the greater will be
its reliability.
4/12/2022 9
CLASSIFICATION OF RELAYS
4/12/2022 11
Definite time – lag relays.
Operation is quite independent of the magnitude of the current or
other quantity which cause operation
Inverse time – lag relays.
The time of operation is inversely proportional to the magnitude of
current other quantity which cause operation.
4/12/2022 12
Inverse- Definite minimum time lag (I.D.M.T) relays.
The time of operation is inversely proportional to the smaller values of current
other quantities which cause operation and tends to definite minimum time
as the value increases without limit.
4/12/2022 14
Electromagnetic Induction Relays
4/12/2022 15
Induction relays
Based on the structures used in the induction relays, they are
classified as
Shaded-pole structure
Watt hour-meter structure
Induction cup structure
Important Terms
Pick-up current:
It is the minimum current in the relay coil at which the relay
starts to operate.
So long as the current in the relay is less than the pick-up value,
the relay does not operate and the breaker controlled by it
remains in the closed position.
4/12/2022 16
However, when the relay coil current is equal to or greater than
the pickup value, the relay operates to energize the trip coil which
opens the circuit breaker.
Current setting:
It is often desirable to adjust the pick-up current to any required
value.
This is known as current setting and is usually achieved by the use
of tapping's on the relay operating coil.
Pick-up current = Rated secondary current of C.T. × Current setting
4/12/2022 17
Example suppose that an overcurrent relay having current setting of
125% is connected to a supply circuit through a current transformer of
400/5
The rated secondary current of C.T. is 5A
Therefore, the pick-up value will be 25% more than 5 A i.e. 5 × 1·25
= 6·25 A
The relay will actually operate for a relay coil current equal to or
greater than 6·25
Plug-setting multiplier (P.S.M.):
It is the ratio of fault current in relay coil to the pick-up current.
i.e.P.S.M. =Fault current in relay coil / Pick - up current
4/12/2022 18
Example , suppose that a relay is connected to a 400/5 current
transformer and set at 150%. With a primary fault current of 2400
A, the plug-setting multiplier can be calculated as under :
Pick-up value = Rated secondary current of CT × Current setting
= 5 × 1·5 = 7·5 A
Fault current in relay coil = 2400× 5/400=30 A
∴ P.S.M. = 30/7·5 = 4
4/12/2022 19
Time-setting multiplier:
A relay is generally provided with control to adjust the time of
operation.
This adjustment is known as time-setting multiplier.
The time-setting dial is calibrated from 0 to 1 in steps of 0.05 sec.
The actual time of operation is calculated by multiplying the time
setting multiplier with the time obtained from time/P.S.M. curve
of the relay.
4/12/2022 20
Time/P.S.M. Curve
•Shows the curve between time of operation and plug setting
multiplier of a typical relay
•If the P.S.M. is 10, then the time of operation (from the curve) is 3
seconds
•The actual time of operation is obtained by multiplying this time
by the time-setting multiplier.
4/12/2022 21
EXERCISE
Calculate the plug setting and time multiplier setting for an IDMTL
relay on the following network so that it will trip in 2.4 s using the
curve
4/12/2022 22
Induction Relays
Induction relays are three types based on the operation
Non directional relays
Directional Power relays
Directional current relays Difference between the three:…………?
4/12/2022 24
Distance or Impedance Relays
It consists of two element.
Current element
Voltage element.
Also called voltage restrained over current relay.
4/12/2022 25
The relay operates when the ratio V/I is less than a predetermined
value
4/12/2022 26
Types of Distance Relay
A distance or impedance relay is essentially an ohmmeter and operates
whenever the impedance of the protected zone falls below a pre-
determined value.
There are two types of distance relays
(i) Definite-distance relay : operates instantaneously for fault up to a
pre-determined distance from the relay.
(ii) Time-distance relay :in which the time of operation is proportional to
the distance of fault from the relay point.
A fault nearer to the relay will operate it earlier than a fault farther
away from the relay. Operating time, T ∝ V/I
∝Z
∝ distance
4/12/2022 27
Differential Relays
A differential relay is defined as the relay that operates when the phase
difference of two or more identical electrical quantities exceeds a
predetermined amount.
4/12/2022 28
Current Differential Relay
•Pair of identical current transformers are fitted on either end of the section to be
protected.
• Secondary of CT’s are connected in series in such a way that they carry the
induced currents in the same direction.
•Operating coil of the overcurrent relay is connected across the CT secondary
circuit.
•The differential relay compares the current at the two ends of the alternator
winding.
1000 A
4/12/2022 29
i) If some current (500 A in this case) flows out of one side while a
larger current (2000 A)enters the other side as shown in Fig. (i),
then the difference of the CT secondary currents i.e. 500* 1/200
=2.5A
2000*1/200 = 10A
10 − 2·5 = 7·5 A will flow through the relay.
4/12/2022 30
Contd..
(II) If current flows to the fault from both sides as shown in Fig.
(i) above then sum of CT secondary currents
i.e. 10 + 5 = 15 A will flow through the relay.
4/12/2022 31
GENERETOR PROTECTION
Major Faults & abnormal conditions in Protective schemes are employed for
case of generator: generator protection
1. Stator or rotor winding 1.Differential protection
insulation failure 2.Inter-turn fault protection
2. Unbalance loading 3.Stator e/f protection
4.o/c & e/f protection
3. Field failure 5.Rotor e/f protection
4. Over load 6.Negative phase-sequence
5. Over voltage protection
6. Failure of prime mover 7.Field failure protection
7. Loss of synchronism 8.Over load protection
9.Over voltage protection
8. Over speed 10.Reverse power protection
9. Under frequency 11.Back up impedance
10. Over heating protection
4/12/2022 12.Under frequency protection 32
Continued…
• Obviously, the short circuit currents caused by these faults can
cause damage to the generator winding & core.
• Hence, these faults should be cleared by high speed
instantaneous relays.
• Faults between conductors can sometimes be repaired by re-
tapping or replacing the conductor,
• Figure below shows the simplified scheme of differential
protection.
• The protection is a unit system of protection & it responds to
internal faults only.
• It must be stable against external faults.
4/12/2022 33
Continued…
4/12/2022 35
Referring figure below & for the worst condition…..
Lm1, Lm2 – Magnetizing Inductances of CT1 & CT2
RCT – CT secondary resistance
RL – lead resistance
RR – relay resistance
LR – relay inductance
RSTAB – stabilizing resistance.
4/12/2022 36
Figure below shows the equivalent circuit of figure above.
From figure, voltage across the relay VR,
VR = IR (RR + XR) = if (RCT + RL)
Normally LR is small & hence XR << RR
4/12/2022 37
• The current through relay IR as given in above equation can be
limited by connecting extra stabilizing resistance Rstab in series
with the relay coil. IR will then reduced to ….
While selecting the value of resistor & earth fault relay setting, the
following aspect should be kept in mind…
Current rating of the resistor
Resistance value
Relay setting
4/12/2022 39
Continued….
• Earth faults are not likely to occur near the neutral point due
to less voltage w.r.to earth.
4/12/2022 40
Continued….
4/12/2022 41
Continued….
4/12/2022 42
Continued….
4/12/2022 43
Continued……
4/12/2022 44
TRANSFORMER PROTECTION
The type of protection for the transformers varies depending
on the application and the importance of the transformer.
Transformers are protected primarily against faults and
overloads.
Why transformer protection ???
To Protect the Transformer from severe damages.
Time required to rectify the Transformer in case of damages is
more and it is very difficult.
4/12/2022 45
Basic Differential Connections for transformer
PROTECTED
I APPARATUS I
im1 im2
Relay
4/12/2022 46
Basic Differential Connections for transformer……
Transformer ratio
The CT should have rating to match the rated currents of the
transformer winding which they are applied.
The current transformer should be connected in Y for ∆
winding and ∆ for Y winding ( see next figure)
Allowance should be made for taping changing by providing
restraining coil.
4/12/2022 47
Power
transformer
C. T.’s C. T.’s
Circuit Circuit
Breaker Breaker
A
A
B
B
C
C
Relay
Example of Differential
o Protection of a Δ/Y
R R Phase A
transformer.
o
R R
Phase B
o
R R Phase C
4/12/2022 48
What cause transformer failure?
Winding Bushing
Insulation deterioration come Bushings deterioration come
from: from:
Moisture General aging
Contamination
Vibration
Cracking
Overheating Internal moisture
Voltage surge
4/12/2022 49
Transformer Protection Scheme
Mechanical Electrical
1. Bias Differential Protection
1. Buchholz relay 2. Over Fluxing
2. Sudden pressure 3. Over Voltage
4. Under Voltage
3. Pressure relief 5. Neutral Unbalance
4. Temperature 6. Restricted Earth Fault
protection 7. Back up O/C & E/F
4/12/2022 50
• Buchholz protection provides an alarm for a number of fault
conditions including:
1. Inter turn faults or winding faults involving only lower power
levels.
2. Core hot spots due to short circuits on the lamination
insulation.
3. Faulty joints.
4. Core bolt insulation failure.
4/12/2022 51
EXAMPLE
Consider a Δ/Y connected, 20 MVA, 33/11 kV transformer with differential
protection applied, for the current transformer ratios shown in Figure
below. Calculate the relay currents on full load. Find the minimum relay
current setting to allow 125 percent overload.
Figure
4/12/2022 52
SOLUTION
20MVA
Is 1049.73 A
3 11kV
4/12/2022 53
SOLUTION….
The C.T. current on the primary side is thus
5
i p 349.91 5.832 A
300
The C.T. current in the secondary side is
5
is 1049.73 A 3 4.545
2000
Note that we multiply by 3 to obtain the values on the line side of the Δ
connected C.T.’s.
The relay current on normal load is therefore
ir is i p 5.832 4.545 1.287A
With 1.25 overload ratio, the relay setting should be
4/12/2022 54
PROTECTION OF INDUCTION MOTOR:
4/12/2022 55
Protection of Low Voltage Induction Motor:
Motor is connected to three phase supply via..
1. Fuse
2. Isolating switch
3. Thermal relay
4. Contactor
5. Control coil
6. ON push button usually green normally off
7. OFF push button usually red and normally closed.
4/12/2022 56
Figure….magnetic contactor starter for LV I.M.
4/12/2022 57
• When we push button 6 is pressed by the operator control coil 5
gets voltage from supply.
4/12/2022 58
If supply voltage fails, control coil is de energized and contactor
opens.
4/12/2022 59
TRANSMISSION LINE PROTECTION
4/12/2022 60
CURRENT GRADING
Current graded systems normally employ high speed high set
o/c relays.
They operate at pre-determined setting without a time lag
Operates at suitable graded current
Fault current are higher near the source.
Relays are set that decreases as distance from the source is
increased.
4/12/2022 61
Time Grading
1. Ensure the breaker nearest to the fault open first, by choosing
an appropriate time setting for each of the relay.
2. Time setting increase as the relay get closer to the source.
4/12/2022 62
Inverse Time Over Current Relaying
1. Evolved because of the limitation imposed by the use
either current or time alone.
2. Time of operation is inversely proportional to the fault
current level. Relays type CO-7 is in common use.
4/12/2022 63
Inverse Time Over Current Relaying
The operating time over current relay varies with the current
magnitude.
There are two setting for this type of relay:
1. Pick-up current is determined by adjusted current coil tap
setting (C.T.S).
The pick-up current is the current that causes the relay to
operate and close the contacts.
2. Time dial setting (or time multiplier setting) refers to the
reset position of moving contact, and it is varies the time of
operation at a given tap setting and current magnitude.
4/12/2022 64
Radial System Protection
• Many radial systems are protected by time delay overcurrent
relays.
• Adjustable time delays can be selected such that the breaker
closest to the fault opens, while other upstream breakers with
larger time delays remain closed.
• That is, relays can be coordinated to operated in sequence so
as to interrupt minimum load during faults.
• Successful relay coordination is obtained when fault currents
are much larger than normal load currents
• Also, coordination of overcurrent relays usually limits the
maximum number of breakers in a radial system to five or less,
otherwise the relay closet to the source may have an excessive
time delay
4/12/2022 65
• Consider a fault at P1 to the right of breaker B3 for the radial
system of figure below.
• We want breaker B3 to open while B2 and B1 remains closed.
• Under these condition, only load L3 is interrupted
• We could select a longer time delay for the relay at B2 so that
B3 operates first
• Thus, for any fault to the right of B3, B3 provides primary
protection
• If B3 fails to open, B2 will open after time delay, thus providing
backup protection
4/12/2022 66
• Similarly, consider a fault at P2, we want B2 to open while B1
remains closed
• Under these conditions, loads L2 and L3 are interrupted
• Since the fault is closer to the source, the fault current will be
larger than for the previous fault considered
• We also select the B1 relay with a longer time delay than B2,
so that B2 opens first.
• Thus, B2 provides primary protection for faults between B2
and B3, as well as back up protection for faults to the right of
B3.
4/12/2022 67
• Similarly, B1 provides primary protection for faults between
B1 and B2, as well as back up protection for further
downstream faults
• The coordination time interval is the time interval between
the primary and remote backup protective devices
• It is the different between the time that the backup relaying
operates and the time that circuit breakers clear the fault
under primary relaying
• Typical time interval between 0.2 to 0.5 seconds are selected
to account in most practical applications
4/12/2022 68
Disadvantages of graded time lag o/c relaying:
Time lag is to be provided, time lag is not desirable for short
circuits.
The method is not suitable for ring mains or interconnected
lines.
It is suitable for radial lines with supply at the one end only.
4/12/2022 69
4/12/2022 70