1.

ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN


ACCORDANCE W/ THE PROVISIONS OF THE LATEST OF
APPROVED EDITION OF THE PHILIPPINE ELECTRICAL CODE
& RULES & REGULATIONS OF THE AUTHORITIES
CONCERNED IN THE ENFORCEMENT OF ELECTRICAL LAWS
& ORDINANCES.

2.POWER SERVICE TO THE BUILDING SHALL BE 230 VOLTS,


THREE-PHASE, 3-WIRE + 1 WIRE GRND, 60 HERTZ SYSTEM.

3.WIRING METHOD SHALL BE DONE IN PURE INTERMEDIATE


METTALIC(IMC) CONDUIT ALL THROUGHOUT THE
SYSTEM COMPLETE W/ BOXES & NECESSARY ELECTRICAL
FITTINGS.

4.UNLESS OTHERWISE SPECIFIED IN THE LOAD SCHEDULE,


MINIMUM SIZE OF WIRE & CONDUIT TO BE USED SHALL BE
9 3.5 SQ. MM TYPE THHN & 20 MM NOMINAL DIAMETER TRADE
SIZE, RESPECTIVELY. WIRE SHALL BE INSULATED FOR 600
VOLTS.

5.ALL MATERIALS & EQUIPMENT TO BE USED SHALL BE NEW &


OF APPROVED TYPE FOR BOTH PURPOSE & LOCATION
INTENDED.

6.ALL MOUNTING HEIGHT SHALL BE SUBJECT TO THE


ARCHITECT'S APPROVAL. OTHERWISE, THE STANDARD
HEIGHT OF 0.30 M FROM THE FFL SHALL BE USED FOR
CONVENIENCE OUTLETS AND 1.40 M FROM THE FFL SHALL
BE USED FOR LIGHTING SWITCHES & THE LIKE.

7.ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER


THE DIRECT SUPERVISION OF A DULY LICENSED
ELECTRICAL ENGINEER.

8.IN CASE OF DISCREPANCIES SHOWN IN THE PLANS, PLEASE

6 VERIFY ARCHITECT AND THE ELECTRICAL ENGINEER, USING


REQUEST FOR INFORMATION FORMS.

NOTES:
5 4 1. SEE LOAD SCHEDULE AND COMPUTATIONS FOR DETAILS ON EQUIPMENT

3 RATINGS, LOADINGS, BREAKER AND FEEDER SIZES.

10 12 2. LOCATION OF ALL ELECTRICAL PANELS SHALL BE VERIFIED AT SITE AND ARE


SUBJECT TO THE ARCHITECT'S/ENGINEER'S APPROVAL.

3. THE ELECTRICAL CONTRACTOR SHALL BE HELD LIABLE IN OBTAINING THE


ACTUAL SITE CONDITION, MEASUREMENTS, AND CLEARANCES.
COORDINATE WITH OTHER TRADES AT SITE TO AVERT CONFLICT DURING
ACTUAL IMPLEMENTATION.

4 3

8 LP

8
GFCI

FL

4 11 EXISTING
ELECTRICAL
BLDG SUPPLY
7 14mm2 3-Wires

2 9 (Red,Yellow & Blue)

5.5mm2 Ground 5.5mm2 Neutral


Wire Color Green Wire Color White
183

60 AT MAIN
3P IN NEMA 1
1 ENC BOLT-ON TYPE
SQUARE D
A B C

L.O.
20A 1
L.O.
20A 2
L.O.
20A 3
L.O.
20A 4
L.O.

ELECTRICAL LIGHTING-SYSTEM LAYOUT


SCALE: 1:40
ELECTRICAL POWER-SYSTEM LAYOUT
SCALE: 1:40
20A 5
L.O.
M.T.S. M.T.S. 20A 6
C.O.
32A 7
C.O.
32A 8
EMERGENCY LIGHT
EXIT SIGN
20A 9
WH
32A 10
FCU-1
40A 11
FCU-2
40A 12

SPARE
13 20A
SPARE
14 20A
GROUND

NEUTRAL

LINE TO GROUND
PANEL BOARD DETAIL
VICINITY MAP

REPUBLIC ACT 9266 PROJECT TITLE OWNER: REVISION DATE SHEET CONTENTS SHEET NO.
ART IV, SECTION 33
DRAWINGS AND SPECIFICATIONS DULY

1
SIGNED AND SEALED AS INSTRUMENT OF
SERVICE ARE INTELLECTUAL PROPERTY. A R C H I T E C T PROFESSIONAL ELECTRICAL ENGINEER INTERIOR FIT-OUT RENOVATION AS SHOWN
IT SHALL BE UNLAWFUL FOR ANY PERSON
TO DUPLICATE OR TO MAKE COPIES FOR
PRC REG. NO: PTR NO: PRC REG. NO: PTR NO:
FOR SALON DEBELLEZA -------------------------------------------
SALON DEBELLEZA DESIGNED BY : 09459784516 CAD BY : JOHN KARL BENTING
EE
USED IN REPETITION, WETHER EXECUTED OWNER'S REPRESENTATIVE
PARTLY OR WHOLE, WITHOUT THE DATE: ISSUED ON: DATE: ISSUED ON: CHECKED BY : DATE : 02 NOV 2023
WRITTEN CONSENT OF THE AUTHOR LOCATION: TARA RESIDENCE QUEZON CITY
ISSUED AT: TIN NO: ISSUED AT:
FILENAME :
------------------ ELECTRICAL

You might also like