SPRINKLER HEAD SCHEDULE GENERAL NOTES

THREADED SIZE
ROOM TYPE OF HEAD RATING °C (mm) K (METRIC)

RECEPTION & LOUNGE QUICK RESPONSE 74 ° C 80.6


1. ALL FIRE PROTECTION EQUIPMENT SUPPLIED IN THE INSTALLATION SHALL
PENDENT 15

QUICK RESPONSE
CLINIC AREA A & B
PENDENT
74 ° C 15 80.6 BE UL/FM LISTED.
QUICK RESPONSE 74 ° C 80.6
STORAGE & PANTRY
PENDENT 15

2. ALL PIPES OF ANY SIZE SHALL BE BLACK IRON (B.I.) ERW.

928 2358 1624 PIPE SIZES WALL THICKNESS

25mmØ Pipe BRANCH LINE 25Ø THRU 150Ø SCHEDULE 40


343

200Ø & LARGER SCHEDULE 40

940
25mmØ
32mmØ
32mmØ 25mmØ
2158

3. PIPE SHALL BE INSTALLED AS INDICATED. ANY RELOCATION REQUIRED

SHALL BE WITH PRIOR APPROVAL OF THE CONSULTANT.

2463
32mmØ DROP NIPPLE

25mmØ
25Øx15mmØ 4. PIPES PASSING THROUGH BUILDING STRUCTURES SHALL BE PROVIDED
32mmØ REDUCER
25mmØ CEILING BOARD
WITH PIPE SLEEVES MADE OF STANDARD STEEL PIPE, WITH 12mm.
2525

ORIFICE PENDENT
SPRINKLER
CLEARANCE ALL AROUND. THIS CLEARANCES SHALL BE CAULKED WITH

2157
PENDENT TYPE SPRINKLER HEAD
32mmØ SPRINKLER HEAD DETAILS FIRE RESISTANT MATERIAL.
25mmØ
32mmØ
25mmØ 5. PIPE SUPPORTS/HANGERS SHALL BE OF APPROVED TYPES AND SHALL
2004

BE INDEPENDENT FROM CEILING AND DUCT SUPPORTS. PROVIDE


1482

SLAB

CONCRETE STEEL
LEGENDS
32mmØ 32mmØ EXPANSION SHIELD
EARTHQUAKE BRACING AS PER NFPA STANDARDS.
25mmØ 25mmØ
SYMBOL DESCRIPTION
1109

1109
40mmØ

B
C A 6. ELECTRICAL AND MONITORING CONNECTIONS TO THE SYSTEM SHALL BE
EXISTING SPRINKLER PIPELINES
'W' x 'T'
CARRIED OUT BY ELECTRICAL SUB-CONTRACTOR.
SIZE MATERIAL WIDTH
SPRINKLER PIPELINES
EXISTING TAPPING POINT & THICKNESS

1455 2802 1654 UPRIGHT SPRINKLER HEAD 7. ALL WORKS SHALL BE EXECUTED IN ACCORDANCE TO THE PROVISION OF
UR
PENDENT TYPE SPRINKLER HEAD
P THE FIRE CODE OF THE PHILIPPINES AND THE NATIONAL FIRE PROTECTION
R dia. THREADED ROD
PIPE SUPPORT
ASSOCIATION (NFPA)
SPRINKLER SYSTEM LAYOUT
SCALE: 1:50 M.T.S.
SIDEWALL TYPE SPRINKLER HEAD
8. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR THE EXACT LOCATION

EXISTING UPRIGHT TYPE SPRINKLER HEAD AND DIMENSIONS OF ALL REQUIRED WALL AND FLOOR OPENING.
DETAIL OF PIPE HANGER 600X600 MANHOLE

SPRINKLER SYSTEM
REPUBLIC ACT 9266 PROJECT TITLE OWNER: REVISION DATE SHEET CONTENTS SHEET NO.
ART IV, SECTION 33
DRAWINGS AND SPECIFICATIONS DULY

2
SIGNED AND SEALED AS INSTRUMENT OF
SERVICE ARE INTELLECTUAL PROPERTY. PROFESSIONAL MECHANICAL ENGINEER
AS-BUILT PLAN AS SHOWN
IT SHALL BE UNLAWFUL FOR ANY PERSON
TO DUPLICATE OR TO MAKE COPIES FOR
PRC REG. NO: PTR NO:
FOR CLINIC RENOVATION DR. VINCENT TAYAG
-------------------------------------------
DOCTOR'S ALLEY MEDICAL CLINIC
DESIGNED BY : 09459784516 CAD BY : JOHN KARL BENTING
ME
USED IN REPETITION, WETHER EXECUTED
PARTLY OR WHOLE, WITHOUT THE DATE: ISSUED ON: CHECKED BY : DATE : 05 JULY 2023
WRITTEN CONSENT OF THE AUTHOR IOPOA NO: ISSUED AT: LOCATION: L3 ROBINSON METRO EAST,MARCOS HI-WAY , PASIG CITY
FILENAME :
------------------ MECHANICAL

You might also like