Interconnection (Wiring) Diagram - Safe Area Din-Rail (Signal)
Interconnection (Wiring) Diagram - Safe Area Din-Rail (Signal)
Interconnection (Wiring) Diagram - Safe Area Din-Rail (Signal)
For
manufacturing
Terminal B
purposes only. Power Supply (+)
1
Do not connect!
2
Power Supply (-) X1
3
J1 Chassis
1 1
J4 1
2 For testing 2
3 purposes only. 3
Cable
4
5 Do not
4 C1
6 connect!
J5 AUX 5
If sheilded cable is used,
SAPG7/MODBUS RS485 + the sheild must not be
1 6 connected to chassis
SAPG7/MODBUS RS485 -
2 earth, but isolated from
J2 the Junction Box Chassis.
1 4-20mA +
NO EXTERNAL EARTH
2 4-20mA -
ALLOWED. CONTROLLER
J3 CARD IS ISOLATED.
1 1 1 1
12
Dokumentet kan ikke endres uten godkjenning fra sertifiseringsorganet (Presafe)
This document cannot be changed without the approval from the notified body (Presafe))
13
1
Isolated Power
2 Barrier
SR22 - Serial Resistors
3 1
2 1
1
Isolated Power
2 2 Barrier**
3 C1
J1
1 1
2 2
3 3
2.3.2 Connecting the instrument cable (C1) to the Barrier Module
Sentech 4 4 13 Fieldbus
This document cannot be changed without the approval from the notified body (Presafe))
1 Isolating Repeater
Controller Card 5 5 14
Busprobe V2 2 RS485
6 6
J2
1 Terminal B Terminal A
2
Connection to
Serial Resistors
(Blue Terminals)
Power Supply Isolator
+
1
KFD0-SD2-Ex1.10100
-
2 8 +24VDC
7 - 0VDC
Scheduled Document
Project Number: P.O. Number: Part-/Serial Number:
48030 NIL Isolating Power Barrier
Sentech Document Number: Customer Document Number:
48030-XT-Ex-008 NIL
Document Title: Sheet: Size:
KFD0-SD2-Ex1.10100 wiring 1 of 1 A4
Rev Date: Reason for Issue: Author:
14
Dokumentet kan ikke endres uten godkjenning fra sertifiseringsorganet (Presafe)
This document cannot be changed without the approval from the notified body (Presafe))
2.4.3 Fieldbus Isolating Barrier
This isolation barrier enables communication with the instrument via Fieldbus RS485. Two
different models can be used in two different communication setups. Please see the Electrical
Schematics provided with delivery for more information on your system setup.
13
B+
14 3 +24VDC
4 - 0VDC
5 A-
RS 485
6 B+
Scheduled Document
Project Number: P.O. Number: Part-/Serial Number:
48030 NIL Isolating Fieldbus Barrier
Sentech Document Number: Customer Document Number:
48030-XT-Ex-007 NIL
Document Title: Sheet: Size:
D1061 wiring RS485/RS485 1 of 1 A4
Rev Date: Reason for Issue: Author:
15
Dokumentet kan ikke endres uten godkjenning fra sertifiseringsorganet (Presafe)
This document cannot be changed without the approval from the notified body (Presafe))
2.4.3.2 RS232 – RS485 Setup
B+
14 3 +24VDC
4 - 0VDC
5 X NC
6 X NC
9
2
8
3
7
4
6
5
DSUB 9P
RS 232
Pin5 - Gnd
Pin3 - TxD
Pin2 - RxD
Scheduled Document
Project Number: P.O. Number: Part-/Serial Number:
48030 NIL Isolating Fieldbus Barrier
Sentech Document Number: Customer Document Number:
48030-XT-Ex-006 NIL
Document Title: Sheet: Size:
D1061 wiring RS232/RS485 1 of 1 A4
Rev Date: Reason for Issue: Author:
Input U 20 .. 30V
(Safe Side) I 100mA@24V
Um 250Vrms
Ta -20 .. 60°C
16
Dokumentet kan ikke endres uten godkjenning fra sertifiseringsorganet (Presafe)
This document cannot be changed without the approval from the notified body (Presafe))
2.4.4 4-20mA Repeater Power Supply
This isolation barrier enables reading the measurements from the instrument via a 4-20mA loop.
Not all installations have this output, it depends on your system. Two different models can be
used.
- 4-20mA
1 11 - 4-20mA
12 + 4-20mA
13 - 0VDC
14 + 24VDC
Scheduled Document
Project Number: P.O. Number: Part-/Serial Number:
48030 NIL 4-20mA Isolating barrier
Sentech Document Number: Customer Document Number:
48030-XT-Ex-009 NIL
Document Title: Sheet: Size:
MTL 5541/42 or 5041/42 Wiring 1 of 1 A4
Rev Date: Reason for Issue: Author:
17
Dokumentet kan ikke endres uten godkjenning fra sertifiseringsorganet (Presafe)
This document cannot be changed without the approval from the notified body (Presafe))
20
must be placed on the positive (+) wire from the 4-20mA Repeater Power Supply described in Section
If the customer requires a local reading of the 4-20mA loop located in the Hazardous area, the meter
This document cannot be changed without the approval from the notified body (Presafe))
Ci: 500nF (Max)
Out In
2.4.3. The meter must be connected as described in section 2.3.3.1.
(-) (+)
Cable C1
2.4.5 Passive 4-20mA Meter