COMPANY: New Company 26/10/23 15:42:50 MM

JOB NAME: CPWD TENDER


SUBCONTRACT PACKAGE: FIRE FIGHTING
SUBMISSION DATE:
PAGE ITEM DESCRIPTION UNIT QUANTITY RATE
1 A CIVIL
33 2.9

Supplying, installation, testing and


commissioning of Electric driven Main Fire Pump
suitable for automatic operation and consisting
of following, complete in all respects, as
required : (a) Horizontal type, multistage,
centrifugal, split casing pump of cast iron body &
bronze impeller with stainless steel shaft,
mechanical seal conforming to IS 1520. (b)
Suitable HP Squirrel cage induction motor,
TEFC, synchronous speed 1500 RPM, suitable
for operation on 415 volts, 3 phase 50 Hz, AC
supply with IP 55 protection for enclosure,
horizontal foot mounted type with Class-'F'
insulation, conforming to IS-325. (c) M.S.
fabricated Common base plate, coupling,
coupling guard, foundation bolts etc. as required.
(d) Suitable cement concrete foundation duly
plastered with anti vibration pads. Note: *The
head of the pump is selected in a manner so
as to give a minimum 3.5kgf/cm2 pressure at
the highest/farthest point.

33 2.9.1 2850 lpm at 88 m Head Set 2 530000


33 2.10

Supplying, installation, testing and


commissioning of diesel engine driven main fire
pump suitable for automatic operation and
consisting of following, complete in all
respects, as required : (Diesel Driven Pump)
Horizontal type, multistage, centrifugal pump
of cast of iron body and bronze impeller
with stainless steel shaft, mechanical seal
conforming to IS 1520. Suitable HP, 1500
RPM water cooled with radiator, diesel engine
conforming to relevant IS standard complete
with auto starting mechanism, 12 /24 volts
electric starting equipment, diesel tank, exhaust
pipe extended upto 10 m outside pump house
duly insulated with 50 mm thick glass wool
with 1.0 mm thick aluminium sheet cladding,
residential silencer, instruments and protection
as per standard specification, stop solenoid for
auto stop in the event of fault with audio
indications, painted with post office red colour
etc. as required. M.S fabricated, common base
plate, coupling, coupling guard, foundation bolts
etc. as required. Suitable cement concrete
foundation duly plastered and with anti
vibration pads. Note: * The head of the pump
is selected in a manner so as to give a
minimum 3.5kgf/cm2 pressure at the
highest/farthest point.

34 2.10.1 2850 lpm at 88 m Head Set 1 708500


34 2.11

Supplying, installation, testing and


commissioning of electric driven pressurisation
pump suitable for automatic operation and
consisting of following, complete in all
respects, as required : (Jockey Pump) Horizontal
type, multistage, centrifugal pump of cast iron
body and bronze impeller with stainless steel
shaft, mechanical seal conforming to IS : 1520.
Suitable HP squirell cage induction motor TEFC
type suitable for operation on 415 volts, 3 phase
50 Hz AC supply with IP 55 class of protection
for enclosure, horizontal foot mounted type with
Class-'F' insulation, conforming to IS : 325.
M.S.fabricated Common base plate, coupling,
coupling guard, foundation bolts etc. as required.
Suitable cement concrete foundation duly
plastered and with anti vibration pads.

34 2.11.1 180 lpm at 88 m Head Set 2 145000


34 2.12

CONTROL PANELS Fabrication, supply,


Insallation testing & commissioning of
Electrical control panel of cubical construction,
floor mounted type, fabricated out of 2mm thick
CRCA sheet, compartmentalised with hinged
lockable doors, dust and vermin proof,
powder coated of approved shade after 7 tank
treatment process, cable alley, interconnection
with suitable size copper conductor cable/solid
copper strip, having switchgears and accessories,
mountings and internal wiring, earth terminals,
numbering etc. complete in all respect, suitable
for main fire pump, pressurisation pump &
diesel pump set complete as per CPW D
specification with following in coming and
Outgoings, suitable for operation on 415V, 3
phase, 50Hz Ac Supply with enclosure protection
class IP 42 as required :
switch Ammeter (0-800 A) with selector swtich
34 2.12.1 & CTs etc. LED type RYB phase indicating lamps, Set 1 255000
ON, OFF, trip indicating lamps Set of Copper Bus
Bar 1000Amps Outgoings ( Note : All outgoing
feeders for pumps should have digital Ammeter
with selector switches, and LED type ON, OFF, trip
indicating lamps) Main Fire Pump 250 Amp, 50kA
TPN MCCB, Ics=100% Icu, with fully automatic
Star/Delta starter suitable for 100 hp pump with
overload protection, current sensing type single
phase preventor complete with all acceessories
and internal wiring required for automatic
operation, selector switch for
local/remote, auto/manual/OFF operation. - 2
sets Jockey Pump 125 Amp, 50kA TPN MCCB,
Ics=100% Icu, with Suitable HP fully automatic
Star/Delta starter with overload protection,
current sensing type single phase preventor
complete with all acceessories and internal wiring
required for automatic operation, selector switch
for local/remote, auto/manual/OFF operation. -
2 sets DIESEL ENGINE CONTROL Control for
diesel engine comprising - Automatic/Manual
selctor switch & 3 attempts starting device,
timers and relays as required, push buttons,
start/stop in manual mode Indicating lamp for
high/ Low Lub. Oil pressure, High Water Temp
and Engine on indication Battery charger
suitbale for 12V/24 V DC with boost and trickle
selector switch, 0-30 V DC volt meter, and 0-20
A DC Ammeter All standard relays and
accessories for automatic operation of diesel
engine System Controller Designing, Supply,
Installation, Testing and commissioning of
system controller to control operation of main
electric fire pump, diesel pump,
Pressurization pump, Terrace pump in sequence
as per specification consisting of relays, timers.
35 2.13

Providing laying, testing & commissioning of 'C'


class heavy duty MS Pipe conforming to IS
1239/3589 i/c fittings like elbows, tees, flanges,
tapers, nuts bolts, gaskets etc. in ground
including welding, excavation & providing cement
concrete blocks as supports, anticorrosive
treatment with coaltar/asphalt tape as per IS
10221, refilling the trench etc. of following sizes
complete as required.

35 2.13.1 150 mm dia m 400 2400


35 2.14

Providing, laying, testing & commissioning of 'C'


class heavy duty MS pipe conforming to IS
3589/IS 1239 including Welding, fittings like
elbows, tees, flanges, tapers, nuts bolts, gaskets
etc. and fixing the pipe on the wall/ceiling with
suitable clamp/support frame and painting
with two or more coats of synthetic enamel paint
of required shade complete as required :

35 2.14.1 25 mm dia m 1,150 400


35 2.14.2 32 mm dia m 1,350 450
35 2.14.3 40 mm dia m 1,190 550
35 2.14.4 50 mm dia m 360 625
35 2.14.5 65 mm dia m 300 780
35 2.14.6 80 mm dia m 210 975
35 2.14.7 100 mm dia m 310 1550
35 2.14.8 150 mm dia m 650 2400
35 2.14.9 200 mm dia (Wall thickness 6.3 mm) m 12 4200
35 2.14.10 250 mm dia (Wall thickness 6.3 mm) m 20 5700
35 2.15

Providing, laying, testing & commissioning of 'B'


class heavy duty G.I. pipe conforming to IS 1239
including welding, fittings like elbows, tees,
flanges, tapers, nuts, bolts, gaskets etc. and
fixing the pipe on the wall/ceiling with suitable
clamp/support frame and painting with two or
more coats of synthetic enamel paint of required
shade complete as required :

35 2.15.1 50 mm m 200 800


35 2.16
Supplying and fixing single headed internal
hydrant valve with instantaneous
Gunmetal/Stainless Steel coupling of 63 mm dia
with cast iron wheel ISI marked conforming to IS
5290 (Type -A) with blank Gunmetal/Stainless
Steel cap and chain as required :

35 2.16.1 Single headed Gunmetal Set 60 10500


35 2.17
Supplying and fixing Single headed external yard
hydrant valve with 1 No. 63 mm dia
instantaneous FM Gunmetal/Stainless Steel
coupling and cast iron wheel, ISI marked,
conforming to IS 5290 (type A) with blank
Gunmetal/Stainless Steel cap and chain as
required :

35 2.17.1 Single headed Gunmetal Set 8 10500


35 2.18
Supplying, fixing, testing and commissioning of
butterfly valve of PN 1.6 rating with
bronze/gunmetal seat duly ISI marked complete
with nuts, bolts, washers, gaskets conforming to
IS 13095 of following sizes as required :

35 2.18.1 50 mm dia Set 27 3250


35 2.18.2 80 mm dia Set 8 4000
35 2.18.3 100 mm dia Set 11 4750
35 2.19
Supplying, fixing, testing & commissioning of
double flanged sluice valve of rating PN 1.6 with
non rising spindle, bronze/gun metal seat, ISI
marked complete with nuts, bolts, washers,
gaskets and conforming to IS 780 of following
sizes as required :

35 2.19.1 80 mm dia Set 2 15500


35 2.19.2 100 mm dia Set 2 19500
35 2.19.3 150 mm dia Set 7 32500
35 2.19.4 200 mm dia Set 3 48500
35 2.20 Each 20 275
Supplying and fixing orifice plate made out of 6
mm thick stainless steel (Grade 304) with orifice
of required size to be fitted between flange &
landing valve of external and internal hydrants to
reduce pressure at the outlet to the level of 3.5
kg/cm2 complete as required.

36 2.21
Providing, installation, testing and
commissioning of non-return valve of following
sizes confirming to IS: 5312 complete with
rubber gasket, GI bolts, nuts, washers etc.as
required :
36 2.21.1 80 mm dia Set 2 3500
36 2.21.2 150 mm dia Set 6 4500
36 2.22
Providing, installation, testing and
commissioning of stainless steel Y-strainer
fabricated out of 1.6 mm thick stainless steel,
Grade 304, sheet with 3 mm dia holes with
stainless steel flange.
36 2.22.1 100 mm dia Each 2 17000
36 2.22.2 200 mm dia Each 3 35000
36 2.23
Supplying and fixing 63 mm dia, 15 m long RRL
hose pipe with 63 mm dia male and female
couplings duly bound with GI wire, rivets etc.
conforming to IS 636 (type-A) as required :

36 2.23.1 Gun Metal Set 76 6200


36 2.24

Supplying and fixing first-aid Hose Reel with MS


construction spray painted in post office red,
conforming to IS 884 complete with the following
as required. 20 mm nominal internal dia
water hose thermoplastic (Textile reinforced)
type -2 as per IS: 12585 20 mm nominal
internal dia gun metal globe valve & nozzle.
Drum and brackets for fixing the equipmets on
wall. Connections from riser with 25 mm dia stop
gun metal valve & M.S. Pipe and socket.

36 2.24.1 30 m Set 30 6600


36 2.25
Supplying & fixing 63 mm dia gun metal short
branch pipe with 20 mm nominal internal
diameter size nozzle conforming to IS 903
suitable for instantaneous connection to
interconnect hose pipe coupling as required :

36 2.25.1 Gun Metal Nos. 38 3200


36 2.26
Supplying and fixing of fire brigade connection of
cast iron body with gun metal male
instantaneous inlet couplings complete with cap
and chain as reqd. for suitable dia MS pipe
connection conforming to IS 904 as required :

36 2.26.1 4 way-150 mm dia M.S. Pipe Set 1 8500


36 2.26.2 3 way-150 mm dia M.S. Pipe Set 3 7500
36 2.27 Set 3 25000

Supplying and fixing air vessel made of 250 mm


dia, 8 mm thick MS sheet, 1200 mm in height
with air release valve on top and flanged
connection to riser, drain arrangement with 25
mm dia gun metal wheel valve with required
accessories, pressure gauge and paintingwith
synthetic enamel paint of approved shade as
required.

36 2.28
Providing, fixing, testing & commissioning of
15mm dia quartzoid bulb type sprinklers of rating
68 degree centigrade with required accessories :

36 2.28.1 Pendent Sprinkler Each 1,500 300


36 2.28.2 Upright Sprinkler Each 1,000 300
36 2.28.3 Horizontal side wall sprinkler Each 5 300
36 2.29 Each 6 3000
Providing & fixing of pressure switch in M.S. pipe
line including connection etc. as required.

36 2.30
Providing & fixing flow switch in following sizes
M.S. pipe including connection etc as required.

36 2.30.1 100 mm dia Each 27 4500


36 2.31

Providing, fixing, testing & commissioning of


installation control valve of cast iron body,
brass/bronze working parts comprising of water
motor alarm, bronze seat clapper, clapper arm
and hydraulically driven mechanical gong bell to
sound continuous alarm when the wet
riser/sprinkler system activates, pressure
gauges, emergency releases, strainer, pressure
switch, cock valve complete with drain valve and
bypass, test control box, ball valves, MS pipe of
required size, flanges, orifice plate, gasket etc of
follwing sizes as required :

37 2.31.1 150 mm dia Set 1 47500


37 2.32

Supplying, installation, testing & commissioning


of sprinkler flexible pipe (UL Listed) of stainless
steel complete with 15 NPT on reducer thread
with maximum working pressure of 175 PSI test
pressure of 875 PSI (Burst) with branch line
(Inlet) 25mm NPT male thread to sprinkler
head (Outlet) 15mm NPT female thread with
reducer, nipple, 2 side brackets, center bracket,
stockbar of following sizes complete as required.

37 2.32.1 1200 mm Set 1,200 1750


37 2.33 Each 15 110
Providing, installation, testing & commissioning
of adjustable rosette plate for 15mm dia in white
finish UL Listed or FM approved complete as
required.
37 2.34 Each 38 4500

Supplying and fixing hose cabinet of size 750


mm x 600 mm x 250 mm made of 2 mm thick MS
sheet with 6mm thick glazed glass doors i/c
necessary locking arrangement suitable to
accommodate external hydrant with butterfly
valve, 2 Nos. 15 mtr. long Hose pipe, 1 No.
branch pipe, mounted on wall OR raised brick
plateform & duly painted with Post office red
externally and white internally with synthetic
enamel paint complete in all respect, for
external/internal hydrant, FBC etc. complete as
required.

37 2.35
Supply and installation of following size auto
air vents / purge valves at the highest points
in water piping complete with nipple/socket
welded to pipe, ball valve, making connections
etc. complete as required.

37 2.35.1 25 mm Each 6 2750


37 2.36
Supplying, fixing, testing and commissioning of
following size valves, gauges and strainers for
water circulation with out insulation as per
specifications.
37 2.36.1 15 mm dia SS ball valve Each 34 1150
37 2.36.2 25 mm dia bronze ball valve IS:318 Each 2 1500
37 2.36.3 50 mm dia bronze ball valve IS:318 Each 2 2400
37 2.36.4 150 mm dia Cast Iron flanged end foot valve Each 1 15500
IS:210
37 2.37

Providing and fixing ISI marked, PESO


approved, Ce & EN certified ABC powder stored
pressure type fire extinguisher of following
capacity and rating confirming to IS: 15683 & IS:
4308 up to date amended, steel can having
epoxy powder coated interior & epoxy
polyester powder coated exterior, forged brass
valve with in built pressure relief device,
aluminium siphon tube & diffuser, stainless steel
safety pin, high durable vinyl label, QR code
label with printed serial number, pressure
gauge, carrying handle, controllable discharge
mechanism, 4m discharge range etc on wall
surface using suitable mounting accessories
complete as required.

37 2.37.1 4 kg, 3A 89B, MAP 90, 13 sec discharge time Each 30 2450
37 2.38

Providing and fixing ISI marked, PESO


approved, CE 7 CN certified CO2 gas type fire
extinguisher of following capacity and rating
confirming to IS: 15683 up to date amended
with 99.7% pure CO2 gas, seamless extruded
aluminium cylinder coated with high glossy PU
paint, dual spindle valve with aluminium wheel &
collar / squeeze grip brass valve, aluminium
siphon tube, high durable vinyl label, QR code
label with printed serial number, pressure gauge,
carrying handle, controllable discharge
mechanism etc. on wall surface using suitable
mounting accessories complete as required.

37 2.38.1 4.5 kg, 55B, 13s discharge time Each 6


37 2.39

Providing and fixing ISI marked, CE certified


ABC powder stored pressure wheeled type fire
extinguisher of following capacity and rating
confirming to IS: 16018 & IS: 4308 up to date
amended, Pure polyester powder coated body
with internal & external coating, rugged trolley
with heavy duty wheel assembly fitted with shock
absorbing bushes, forged brass cap union, built
pressure relief device, delivery hose, shut off
valve with discharge nozzle, high durable vinyl
label, QR code label with printed serial number,
pressure gauge, controllable discharge
mechanism, etc. on wheel mounted trolley
with all accessories complete as required.

38 2.39.1 Each 1 32500


25 kg, 20A 233B, MAP 90, 30 sec discharge time
38 2.39.2 Each 2 45000
50 kg, 20A 233B, MAP 90, 45 sec discharge time
38 2.40
Supplying and testing of following size one
number XLPE insulated and PVC sheathed
armoured copper conductor power cable of 1.1
kV grade conforming to IS 7098 (Part 1) 1988 as
required.
38 2.40.1 2C x 1.5 sq. mm m 600 165
38 2.40.2 3C x 4 sq.mm m 20 210
38 2.40.3 3C x 50 sq.mm SH-III: Fire Alarm System m 50 1020
38 3.1
Supplying and drawing following sizes of FRLS
PVC insulated copper conductor, single core
cable in the existing surface/ recessed steel/
PVC conduit as required.

38 3.1.1 2 x 1.5 sq. mm Metre 5,000 165


38 3.2
Supplying and fixing of following sizes of steel
conduit along with accessories in surface/recess
including painting in case of surface conduit, or
cutting the wall and making good the same in
case of recessed conduit as required.

38 3.2.1 25 mm Metre 4,000 250


38 3.3

Supplying, installation, testing and


commissioning of micro processor based
intelligent addressable main fire alarm panel,
central processing unit with the following loop
modules and capable of supporting not less than
240 devices (including detectors) and minimum
120 detectors per loop and loop length up to
2 km, network communication card, minimum
320 character graphics/ LCD display with
touch screen or other keypad and minimum
4000 events history log in the non volatile
memory (EPROM), power supply unit (230 ± 5%
V, 50 hz), 48 hrs back-up with 24 volt sealed
maintenance free batteries with automatic
charger. The panel shall have facility to connect
printer to printout log and facility to have
seamless integration with analog/digital voice
evacuation system (which is part of the schedule
of work under SH: PA System) and shall be
complete with all accessories . The panel shall
be compatible for IBMS system with open
protocol BACnet/ Modbus over IP complete as
per specifications.

38 3.3.1 Ten Loop Panel Each 1 750000


38 3.4 Each 1 95000
Supplying, installation, testing & commissioning
of repeater panel wih 320 character/ Touch
screen LCD display with inbuilt reset,
acknowledge and silence switches complete as
required.
38 3.5 Each 200 3200
Supplying, installation, testing & commissioning
of intelligent analog addressable photothermal
detector complete with mounting base
complete as required.

38 3.6 Each 10 750


Supplying, installation, testing & commissioning
of response indicator on surface/recessed MS
Box having two LED, metallic cover complete
with all connections etc as required.
38 3.7 Each 20 4500
Supplying, installation, testing & commisssioning
of intelligent addressable programmable sounder
complete as required.

38 3.8 Each 20 4500


Supplying, installation, testing & commissioning
of fault isolator complete with base as required.

38 3.9 Each 10 3200


Supplying, installation, testing & commissioning
of intelligent addressable thermal detector with
rate of rise cum fixed tempreature thermistor
complete with base as required.

38 3.10 Supplying, installation, testing & commissioning Each 20 4500


of addressable fire control module complete as
required.
38 3.11 Supplying, installation, testing & commissioning Each 1 4500
of addressable phone control module complete
as required.
39 3.12 Supplying, installation, testing & commissioning Each 27 4750
of addressable manual call point complete as
required.
39 3.13 Supplying, installation, testing & commissioning Each 1 2750
of addressable horn cum strobe complete as
required.
39 3.14 Supplying, installation, testing & commissioning Each 3 3500
of fire fighter telephone handset complete as
required.
39 3.15 Each 3 2850
Supplying, installation, testing & commissioning
of fire fighter phone jack complete as required.

39 3.16 Each 1 32500


Supplying, installation, testing & commissioning
of 6 zone, voice alarm controller with USB, MP3
player (including 6 zone button paging station)
with seamless integration facility with main fire
alarm panel for voice evacuation complete as
required.

39 3.17 Each 60 3250


Supplying, installation, testing & commissioning
of 1.5/3/6W metal box ceiling/wall speakers
complete as required.

39 3.18 Each 3 3250


Supplying, installation, testing & commissioning
of ceiling/wall mounted loud speaker, 3/1.5 W
att in ABS enclosure complete as required.
39 3.19 Each 1 3500
Supplying, installation, testing & commissioning
of exit point directional sound speaker with voice
and integral audio amplifier with selectable
sound pulse patterns complete as required.

39 3.20 Each 1 25000


Supplying, installation, testing & commissioning
of Voice command keypad 6 zone, with
microphone assembly complete as required.

39 3.21
Supplying and drawing of cable Fire Retardant
PVC insulated copper conductor cable in the
existing surface / recessed steel conduit of
following pairs, cores and size including
connections and interconnections etc. as
required.

39 3.21.1 Speaker cable Two pair, 2-core, 1.5 sqmm Metre 400 75
39 3.22 Metre 200 45
Supplying and fixing 25 mm dia MS flexible pipe
with PVC coating along with all ancillaries and
accessories like coupler etc. as required.

39 3.23
Supplying, installation, testing & commissioning
of following digital audio amplifier 25 V rms
operating at 240 Volt AC Supply complete as
required.
39 3.23.1 480 W Each 1 35000
39 3.24

Supplying, Installation, testing & commissioning


of following energy efficient LED Laser etched
signage with illuminated Exit signage with lpm
technology smps, 8000 to 10000 mcd super
bright LEDs, Green/Red colour, with power
consumption not more than 2 W, inbuilt
battery of minimum 2200 mah, minimum 5
hours back up, power cord with plug top, all
accessories and are assembled in a MS powder
coated housing or ABS housing etc. complete as
required.

39 3.24.1 Pendant type single side Each 20 3200


39 3.24.2 Pendant type Double side Each 20 3200
39 3.24.3 Conceled type Single side Each 5 3200
39 3.24.4 Conceled type Double side Each 5 3200
39 3.25

Providing and fixing of photo luminescent (shall


glow in dark) non-toxic, non-radio active
maintenance free self glowing
"Informatory/Cautionary signage" for directional
usage, having alphabets/numerals/pictures
printed on U-1000 photo luminescent III as base
chemical cover with UV stabilised coating of
required sizes to help evacuating procedure
during power failure /emergency including
fixing on wall or hanging from ceiling with
aluminium tubes/chain at different
places/floors/areas of the building as per
direction of Engineer-in-charge as specified
below. The colour combination and size of the
letters shall be as per IS:12349 (Note: The normal
size of signage shall be 15 cm x 15 cm, 15 cm x
20 cm, 15 cm x 30 cm, 30 cm x 10 cm, 40cm x
15cm or as per site requirement).

40 3.25.1 Sq. cm 20,000 10


3 mm Aluminium composite Panel single side
40 3.25.2 Sq. cm 10,000 10
3 mm Aluminium composite Panel Double side
40 3.26 Each 2 1750
Supply and installation of in position the
signages "FIREORDER". It should contain the
following matter on 3 mm thick "Opaque"
PVC foam board of computerized cut, PVC Non-
reflective self adhesive vinyl painted foam board
of 3'x4'. . A) ALERT THE SECURITY BY ACTUATING
MANUAL CALL POINT LOCATED AT STRATEGIC
LOCATIONS. B) EVACUATE THE OCCUPANTS BY
USING FIRE EXITS AND EMERGENCY EXITS ONLY,
AND ASSEMBLE AT VARIOUS ASSEMBLY POITS.
C) IF POSSIBLE TRY TO EXTINGUISH THE FIRE BY
USING NEAREST / SUITABLE PORTABLE FIRE
EXTINGUISHER OR WATER FROM NEAREST HOSE
REEL. D) BE CALM AND DO NOT GIVE ANY ROOM
FOR PANIC. WALK, DO NOT RUN. E) IF YOU
ENCOUNTER SERIOUS DIFFICULTY IN
EVACUATION ,LAY FLAT AND TRY TO ATTRACT
ATTENTION OF RESCUE TEAM. F) TRY TO COVER
YOUR FACE WITH A WET TOWEL TO AVOID
BREATHING SMOKE OR OTHER TOXIC FUMES.
ACTION BY SECURITY / RECEPTION UPON
RECEIPT OF INFORMATION THROUGH FIRE
ALARM OR PUBLIC ADDRESS SYSTEM. A) ALERT
THE OCCUPANTS BY USING PUBLIC ADDRESS
SYSTEM. B) INFORM FIRE CONTROL THROUGH
ANYONE OF THE FOLLOWING PHONE
NUMBERS:101 /………………….( Local fire
station number) C) REFER EVACUATION PLAN.D)
GUIDE THE FIRE FORCE, ON THEIR ARRIVAL TO
THE SEAT OF FIRE. E) IN CASE OF CASUALTIES,
CALL AMBULANCE (Local numbers:) PHONE : -
The above shall be got approved by the
Engineer-in-charge prior to fabrication.
AMOUNT

1060000
0

708500
0

290000
0
255000

960000
0

460000
607500
654500
225000
234000
204750
480500
1560000
50400
114000
0

160000
0

630000
0

84000
0

87750
32000
52250
0

31000
39000
227500
145500
5500

7000
27000
0

34000
105000
0

471200
0

198000
0

121600
0

8500
22500
75000

450000
300000
1500
18000

121500
0

47500
0

2100000
1650

171000

16500
0

39100
3000
4800
15500
0

73500
0

0
0

32500

90000

99000
4200
51000
0

825000
0

1000000
0

750000
95000

640000

7500
90000

90000

32000

90000

4500

128250

2750

10500

8550

32500

195000

9750
3500

25000

30000
9000

35000
0

64000
64000
16000
16000
0

200000

100000
3500

18646000

You might also like