Professional Documents
Culture Documents
Meeting The Challenges of Battery Protection
Meeting The Challenges of Battery Protection
OF BATTERY PROTECTION
TWO STAGE POWER DISTRIBUTION
Contents
1. Introduction 3
2. Power distribution and fault paths 3
3. Fuses 3
3.1 DC Circuit and Time Constant 4
3.2 Main interrupting tests 4
3.2.1 Maximum energy test 4
3.2.2 Breaking capacity test 5
3.2.3 Minimum interrupting capability (or overload test) 5
3.2.4 Comment on the Fuse rated Voltage 5
3.2.5 Example of the DC capability for an AC rated fuse 6
3.3 Curves 7
3.3.1 Time vs Current curve (prearc time vs RMS current value) 7
3.3.2 Peak let through current vs short circuit curent 7
3.3.3 I²t vs Short circuit current 7
3.3.4 Arc voltage 7
3.4 Calculation of the fuse Operation 7
3.5 Conclusion and DC fuse selection criteria 8
4. Circuit Breaker selection in a direct current application 8
4.1 Low-voltage switchgear and controlgear 8
4.2 Fault current 8
5. Case studies 9
5.1 Case study Fuse #1 9
5.1.1 UPS data (EXL-S1) 9
5.1.2 Battery data 9
5.1.3 Battery Fault current 10
5.1.4 Discharging data 10
5.1.5 Fuse sizing 10
5.16 A70QS 700Vdc 10
5.1.7 A070URD-31 690Vac 11
5.1.8 Conclusions 14
5.2 Case study #2 14
5.2.1 UPS data (EXL-S1) 14
5.2.2 Battery data 14
5.2.3 Battery Fault current 14
5.2.4 Discharging data 15
5.2.5 Fuse sizing 15
5.2.6 ETI fuse NH serie 15
5.2.7 Conclusion 19
5.3 Case study Fuse #3 19
5.3.1 UPS data (EXL-S1) 19
5.3.2 Battery data 19
5.3.3 Battery Fault current 19
5.3.4 Discharging data 19
5.3.5 Fuse sizing 20
5.4 Case study #4 20
5.4.1 UPS data (EXL-S1) 20
5.4.2 Battery Fault current 20
5.4.3 Discharging data 20
5.4.4 CB selection ABB TMAX T6 21
5.4.5 Conclusion 23
2
1. Introduction
The UPS is supplied by AC and DC sources.
Unlike the short circuit current generated by the AC sources, generally predictable, the short circuit current generated by the
battery is variable and not easily predictable.
With an unpredictable fault current the selection of the rating of the protection is quite challenging.
The purpose of this document is to go more in depth in the analysis of the selection of the suitable current protection devices.
(see “Liebert Design for Safe and Reliable electrical protection of bettery systems” for more details).
as follows:
Resistance R Inductance
t_melting t_clear
Figure 6.
G E Ua Fuse
3.2 Main interrupting tests
The Underwriters Laboratories (UL 248) and the
i
International Electro technical Commission (IEC 60269)
describe standard tests conditions for fuses under DC
Figure 3. voltage.
( R
( ))
i(t) = Ifault * 1 – exp – – * t
L
These are applied to industrial fuses, semi conductor
protection fuses and special DC rated fuses as well.
As for the testing under AC voltage there are 3 typical tests :
Ifault yyMaximum energy test (also named critical current)
yyBreaking capacity test (maximum interrupting ability)
yyOverload test (or minimum interrupting capacity)
The tests required by the standards are giving essential
information on the fuse DC capability. However it is
L t
necessary to provide more information and more specifically
Figure 4. the curve giving maximum L/R values as a function of the
DC working voltage U (see examples in figure 8).
Where:
This curve is an essential characteristic for the selection of
yyProspective current, Ifault = E/R fuses in DC applications.
yyCircuit Time constant = L/R 3.2.1 Maximum energy test
The equation of the current shows the L/R influence As shown earlier the arc energy depends upon a great
on the fuse prearcing time (or melting time). extent on the energy stored in the inductance. It has been
Therefore the larger is L/R, the slower is the rate of change demonstrated that the arc energy in the fuse is maximum
of the current (small di/dt), and longer is the prearcing when the energy stored in the inductance is maximum as
duration of the fuse (see figures 5 and 6). The arcing well.
duration and arcing I²t depend upon the energy dissipated A study of the energy stored in the inductance L shows that
inside the fuse during this period of time. a maximum is reached when the prearching time t_melting
of the fuse is about equal to the time constant L/R of the
circuit (Fig. 7).
Ifault
Once more the large influence of L/R on the fuse behavior
is demonstrated. This test tremendously stresses the fuse
Imelting
and consequently determines the maximum L/R value for a
given working voltage.
The L/R vs voltage curve (Fig. 8) is plotted according to
the maximum energy test results at various voltage values.
t_melting t_clear
It means larger values of L/R are acceptable when the
prearcing time is much smaller than L/R.
Figure 5.
4
3.2.4 Comment on the Fuse rated Voltage
The three fundamental tests and the curve in figure 6
Ifault
show that it is not possible to select the DC voltage rating
Imelting of a fuse purely on the basis of the working voltage value
of the DC circuit to be protected.
It is absolutely necessary to plot the curve L/R = f(U).
This curve is plotted from the maximum energy tests
t_melting = L/R t_clear
results. Larger values of L/R are acceptable when the
prearcing time is much smaller than L/R.
Figure 7.
L/R (ms)
100
90
80
70
60
50
40
30
20
10
0
1000
1200
1400
1600
1800
2000
2200
2400
U (V)
Figure 8.
5
TWO STAGE POWER DISTRIBUTION
70 80 a 300
100 a 360
60
Time Constant
125 a 460
50
160 a 650
40 200 a 880 a 850
Maximum L/R of the fault path versus the DC working voltage U. 630 a 5000 a 3700 b 3250
700 a 5600 a 4300 a 3900
L = 80 ms 800 a 5300 a 4800
R L = 25 ms
R 900 a 7800 a 5600
Um(V)
1000 b 9000 a 6600 a 5200
L = 10 ms
1000 R 1100 a 7700
1250 b 11000 a 7400 a 6500
800 1400 b 12500 a 8600 a 7800
1600 a 10600 a 9600
600
1800 a 15600 a 11200
2000 b 18000 a 13200
400
2200 a 15400
2500 b 22000
200
2800 b 25000
0
200 400 U (V) Letter a, b indicate the L/R curve to use in the L/R vs U graph.
Ipm is the minimum breaking current of each fuse.
Provides the DC Voltage capability of the fuse as a function of circuit time constant
(L/R ratio). * Consult Factory for DC capabilities on amper rating not shown.
Peak arc voltage Um of the fuse versus the DC working voltage U for
three values of the time constant L/R.
6
3.3 Curves points of the 2 following curves (figure 11 and figure 12) it is
possible to calculate:
3.3.1 Time vs Current curve (prearc time vs RMS current
value) yyUsing figure 12, the intersection between the curve
[time vs current] of the fuse (red curve) with the
The curve plotted with AC or DC tests is the same because
curve [current vs time] of the external circuit (black
of the use of the RMS value of the prearc current. This curve
curve), calculated with the formula in section 3.1 and
allows to calculate the prearc time as a function of the fault
rappresented in figure 11, gives the prearc time (21.6ms)
current and the time constant L/R as well as to calculate the
and the melting current (3700Arms)
peak let through current and the prearc I²t.
yyUsing figure 11, it is possible to see what is the peak
3.3.2 Peak let through current vs short circuit curent
value and rms value of the melting current.
There is a different curve for each different value of the time
Data:
constant L/R. There is an unlimited number of curves and
for this reason there is no published curve. It is possible to Fuse rated 600Vdc 500A gRB type in body size 73
calculate the peak current from the time current curve.
Fault characteristics:
3.3.3 I²t vs Short circuit current
yy10 KA
There is a different curve for each different value of the time
yy500 Vdc
constant L/R. There is an unlimited number of curves and
for this reason there is no published curve. It is possible yyL/R = t = 25 milliseconds
to calculate the prearc I²t from the time current curve, but Results:
there is no simple formula for the calculation of the arc I²t
and the total clearing I²t. yyPrearc time and Pre-arc Irms: 21,6 ms; 3700Arms (see
figure 12)
3.3.4 Arc voltage
yyPeak let through current: 5785 A (calculated with the
There is a specific curve for each value of the time constant equation of i at time 21.6 ms, see note 1)
L/R as shown in the figure 9.
yyEstimated arc time: 25 ms to 30 ms (see § 3.4.2 in docu-
ment EduPack 201-Behaviour and operation of the fuse).
Um (V)
yyTotal clearing time: 50 ms (pre-arc time + arc time)
2000
L/R=80ms
yyPrearc i²t: 295700 A²S (see note 2)
L/R=25ms
L/R=10ms
(A)
1500
5785
1000
3700
500
0 100 200 300 400 500 600 700 800 900 1000 21.6 50 ms
Figure 9. Peak arc voltage (Um) of the fuse versus the DC working Ifault 10kA, L/R = 25 ms
voltage (U) for three values of the time constant L/R Ifault 10kA
7
Time current characteristics
4. Circuit Breaker selection in a direct current
10R
application.
The product standard for circuit breakers is IEC 60947-
1000
2:2016. The purpose of these CB is making, carring and
breaking currents in normal and fault conditions.
100
4.1 Low-voltage switchgear and controlgear
PSC 690 V gRB Circuit-breakers
10 500 A size 73
A Circuit Breaker in a direct current application needs to be
1
selected respecting the following parameters:
Irm=f(t) of the 10k
a) Ue: rated operation voltage, that is the voltage which the
0,1 fault with L/R=25ms circuit breaker is designed to operate. A single breaker
may be rated for several voltages and be compatible with
0,01
3700 A RMS 21,6 ms both AC and DC voltages.
b) In: current of the protection trip placed on the circuit
0,001 breaker.
100 1000 10K 100K
E.M.S current, A
c) Icu(kA): short-time withstand current the CB can
withstand when it is closed, making or breaking is not
Figure 12. Determination of the melting point of the fuse guaranteed.
d) Icm (%Icu): rated making short-circuits current
Note 1: (1 operation), it is usually expressed as a percentage of
The RMS value of he fault current is given by: Icu, typical values are 25%, 50%, 75%, 100%.
e) Ics (%Icu): rated service short-circuits current
(3 operations), it is usually expressed as a percentage
of Icu, typical values are 25%, 50%, 75%, 100%.
With L/R = 25ms and t=26,1ms Other electrical, mechanical, enviromental characteristics
yyi = 5785 A shall be taken in consideration as well but they are not in the
scope of this guide, for these latter refer to manufacturers
yyIrms = 12240 A specifications.
The scope of this paragraph is to define some common rules
for the UPS DC battery circuit protection with the use of
Note 2: circuit breakers (CB):
Prearc i²t can be calculated as follows 1. Identification of the power distribution and the fault
prearc: i²t = Ieff² x t = 3700² x 0,0216 = 295700 earthing paths (see cap. 2).
3.5 Conclusion and DC fuse selection criteria 2. Identification of Un, rated voltage of the system (Ue≥Un)
3. Current during battery discharge and at the EoD.
For all DC applications it is recommended to select the fuse
following the below steps: 4. Available fault current
a) Select a DC rated fuse, in case of a AC rated one make The opening time is another paramenter that should be
sure it is specified its with DC voltage capability. considered, for this rules describe in the above paragraph
will be taken in consideration.
b) Voltage Rating considering the downgrade due to the
L/R, the type of power distribution (see cap. 2). 4.2 Fault current
c) The time constant (L/R) of the circuit lower than 10ms Once estimated the available fault current, this should be
d) Available fault current compared with the magnetic threshold of the breaker
(I3). The Thermomagnetic trip units have a I3 that can be
It is required as well to get all necessary information about
typically set between 5 ÷ 10 x I1 (I1, nominal current of the
the rated current passing in the fuse as well as the load
CB) in the most common CB, it can be lower in some other
cycles and overloads to withstand in order to calculate the
types of breaker (e.g. 2 ÷ 2.5 x I1). A good selection criteria
current rating of the fuse so that its life time fits with the life
consists on selecting a body rated for an higher nominal
time of the equipment it must protect.
current than the one required by th system in order to fulfil
the Ue requirement and if possible a lower tripping units.
8
Electronic trip units can provide a more flexible selection 5. Case studies
(e.g. I3 = 1.1 x I1) with the drawback of an higher cost than
5.1 Case study Fuse #1
the previous ones.
The use of AC rated CB in a DC application is allowed if the 5.1.1 UPS data (EXL-S1)
supplier declares the Ue value in DC, and if the bimetal part yyRating: 100kVA; 90kW (PF=0.9)
is sensible to r.m.s and average current (no variation in the yyRuntime: 15 minute
tripping curves for overload times). It should be understood
yyBattery type: C&D UPS 12-475; 122Ah @ 10h rate
that the magnetic tripping can be affected by DC so that
I3 needs to be increased. In this latter case 5*I1<I3< 10 yyNumber of blocks/cells: 40/240
I3min=5*I1 -> I3min=5Km*I1 (with Km>1). yyFloat voltage: 540Vdc at 25°C ambient (2.25V/cell)
The factor Km is function of the circuit breaker, the yyEoD voltage: 396Vdc (1.65V/cell)
connection type and number of poles.
In case of battery cabinet in parallel (or battery strings)
it should be taken in consideration that an internal fault
(upstream the breaker) can drive current from the other
cabinets or strings and the ultimate short circuit breaking
capability should be selected accordingly (Icu>n°batt
cabinets*Ib).
5.1.2 Battery data
UPS12-475 - Specifications
Cells per Unit Voltage per Unit Weight Electrolyte Maximum Discharge Short Circuit Ohms Imped.
Current Current 60 Hz (w)
6 12.84 100 Ibs. Absorbed H2SO4 800 Amps 5000 Amps 0.0023 Ohms
45 kg @ 0.1 sec
475 watts per cell at the 15 minute rate to 1.67 volts per cell at 77°F (25°C)
Capacity 134 Ah @ 20hr. rate to 1.75 volts per cell@ 77°F (25°C)
122 Ah @ 10hr. rate to 1.80 volts per cell@ 20°C (68°F)
Discharge: -40° F (-40°C) to + 160° F (71°C), Charge: -10° F (-23° C) to +140° F (60°)
Operating Temperature Range
(With temperature compensation)
Nominal Operating Temperature Range +74° F (23° C) to + 130°F (27° C)
Float Charging Voltage 13.5 to 13.8 Vdc/Unit Average at 77° F (25° C)
Recommended Maximum Charging
C/5 amperes (27 amperes @ 100% depth of discharge)
Current Limit
Equilization and Cycle Service Charging
14.4to 14.8 Vdc/Unit Average at 77° F (25° C)
Voltage
0.5% rms or 1.5% p-p of float charge voltage racommended for best result
Maximum Ac Ripple (Charger) Maximum voltage allowed - 1.4% RMS (4% P-P)
Maximum voltage allowed - 6.7% amperes RMS (C/20)
Dynasty UPS batteries may be stored for up to 6 months at 77° F (25° C) and then a freshening
Self Discharge
charge is required. For higher temperatures the time interval will be shorter
Accessories Inter unit connectors, rack and cabinet system are available
Terminal Threaded brass insert to accept 0.25" (6 mm) bolt
Terminal Hardware Torque 110 In.-Ibs. (12.4 N-m)
* All dimensions in inches and (millimeters). All dimensions are for reference only. Contact a C&D Rapresentative for complete dimensional information.
Table 1.
Constant Power Discharge Rating - Watts per Cell @ 77°F (25° C) - Operating Time to End Point V dimensionoltage (in minutes)
End Point
5 10 15 20 30 40 45 50 60 90
Volt/Cell
1.75 685.0 515.0 437.3 366.3 283.4 236.1 217.4 201.7 172.8 122.8
1.70 725.0 542.9 451.5 379.2 293.2 221.6 221.6 205.5 177.8 125.0
1.67 750.0 577.0 475.0 393.0 302.0 227.0 227.0 210.0 182.0 129.0
1.65 770.1 588.6 481.4 401.9 311.2 233.1 233.1 214.9 185.2 131.0
1.60 785.2 606.1 488.4 410.4 315.9 238.0 238.0 220.1 188.0 135.5
Table 2.
9
5.1.3 Battery Fault current b) Voltage Rating considering the downgrade due to the
The battery fault current value is usually given by the L/R. Assuming L/R = 10ms the DC voltage capability
battery manufacturer and it is available on the product remains 700Vdc (Fig. 13). The DC voltage capability
datasheet. If it is not available, it can be requested to the must be verified against the possible voltages present
battery manufacturer. during the different type of fault:
For this specifc case see the above table 1: yyFault between the poles, POS to NEG. The fuse must be
able to open the float battery voltage 540Vdc that is well
yyShort circuit current: 5000A for 0.1 sec
below the DC capability of the sinlge fuse (700Vdc).
yyIn accordance with the previous consideration, the
yyGround fault, worts case is NEG to GND. The fuse must
available battery short circuit current is affected by the
be able to open the negative DC link 370Vdc that is well
state of charge and the aging of the battery. Another
below the DC capability of the fuse (700Vdc).
important parameter that will reduce the available fault
current is the impedance of the connection. c) The time constant (L/R) of the circuit lower than 10ms.
The time constant depends by the cabels and how they
yyThe final fault current to be considerd for the sizing of
are routed. Cables routed very close to each other will
the protection will be 60% of the nominal hence 3kA.
have a L/R lower than connections with the cables
5.1.4 Discharging data connected to the positive distant than the cables
The battery protection device MUST NOT open during a connected to the negative. The inductance increase
battery discharge at risk of losing the UPS basic functionality by increasing the distance between the cables.
of the load supply in mains failure. A time constant of 10ms is representative of a typical
installation.
Battery power (Bw) = (Pn x PF) / (DC/AC) = (100 x 0.9) /
0.957 = 94kW. d) Available fault current. The fault current provided by
the battery depends by various factors such as state
Max discharge current at EoD = Bw / (ncell x 1.65) = 240A
of charge, aging and connection cables. To take care of
Calculation of the Power x Cell = 94000 / 240 = 392W/Cell
the variable related to the battery (EoD and EoL) the
Number of strings Calculation actual fault current will be 60% of the nominal one. The
From the above table 2 we can see that the watts per cell selection of the connections cable (section and length)
during 15 minutes are 481W. should guarantee that the voltage drop between UPS
N.Strings = 392 / 481 = 0,82 therefore 1 strings and battery, with max discharging current, is less than 1%
5.1.5 Fuse sizing of the UPS battery voltage at the EoD.
The key points for the selection of the fuse are: e) Intervention time. The rating current of the fuse should
a) DC rated fuse or AC rated with specified DC voltage allow the UPS to operate in battery mode in all specified
capability. conditions and open the fault in a limited time whit the
60% of the fault current in 100ms. The Melting curve
b) Voltage Rating considering also the downgrade due to
provide the following info: max current below which the
the L/R
fuse dose not open; time to the melting of the fuse (tp).
c) The time constant (L/R) of the circuit lower than 10ms The key data are:
d) Available fault current yyGreen area, normal operating conditions. Max current
The right type of fuse to use is a semiconductor fuse. These (EoD current) 240A.
type of fuses have a very Low l2t for improved protection of yyRed area, fault conditions. Minimum fault current 5kA x
equipment, compared to other types. 0,6 = 3kA.
Looking at the Ferraz/Shamut brand (as an example), two The melting time of a 400A fuse at 60% of the nominal fault
different models can be chosen: A70QS 700Vdc rated; current is about 50ms well below the expected 100ms. The
A070URD-31 690Vac rated. melting time of the fuses higher than 400A are greater than
5.1.6 A70QS 700Vdc 100ms, this does not gurantee that the fuses reaches the
melting point (Fig. 14). For fuses smaller than 400A, the
The four steps check list to be covered is: melting time is smaller, it must be verified if the fuse carries
a) It is rated 700Vdc. The actual DC voltage capability the discharging current.
should be checked based on the circuit time constant
L/R.
10
Clearing I2t at 700V DC, 100kA, L/R = 10 ms 5.1.7 A070URD-31 690Vac
Ampere Rating (A2sx103) Clearing I2t
35 0.25
The four steps check list to be covered is:
40 0.35 a) It is rated 690Vac with specified DC voltage capability
50 0.60
70 1.3 based on the time constant L/R. See below data sheet
80 1.8 (Tab 4.).
90 2.4
100 3.1 b) DC voltage rating considering the downgrade due to
125 5.3 the L/R. In the below “DC voltage capability vs Time
150 8.1
175 12 constant” curves, curve a Fig. 15 is the one that should
200 16
225 21.5 be used based on the possible current rating of the fuse
250 27.5 to be selected. Assuming L/R = 10ms the DC voltage
300 42
350 63 capability is 540Vdc. The DC voltage capability must be
400 85 verified against the possible voltages present during the
450 115
500 150 different type of fault:
600 201
700 325 yyFault between the poles, POS to NEG. The fuse must
800 450 be able to open the float battery voltage 540V that is
Table 3.
equal to the DC capability of the sinlge fuse (540Vdc).
DC Voltage Capability vs. Time Constant yyGround fault, worts case is NEG to GND. The fuse must
900
be able to open the negative DC link 370Vdc that is
well below the DC capability of the fuse (540Vdc).
800
c) The time constant (L/R) of the circuit lower than 10ms.
The time constant depends by the cabels and how they
are routed. Cables routed very close to each other will have
DC Voltage Capability
700
a L/R lower than connections with the cables connected
to the positive distant than the cables connected to the
negative. The inductance increase by increasing the
600
distance between the cables. A time constant of 10ms is
representative of a typical installation.
d) Available fault current. The fault current provided by
500
the battery depends by various factors such as state of
charge, aging and connection cables. To take care of the
variable related to the battery (EoD and EoL) the actual
400
fault current will 60% of the nominal one. The selection
0 10 20
L/R Time Constant (ms)
30 40 50 of the connections cable (section and length) should
Figure 13. guarantee that the voltage drop between UPS and
Melting Time - Current Data, 700V Fuses battery, with max discharging current, is less than 1% of
100
70 200A the UPS battery voltage at the EoD.
225A
50
250A e) Intervention time. The rating current of the fuse should
30
20
300A
350A allow the UPS to operate in battery mode in all specified
10
400A
450A conditions and open the fault in a limited time whit the
7 500A
600A 60% of the fault current in 100ms. The Melting curve
5
3
700A provide the following info: max current below which the
800A
2 fuse dose not open; time to the melting of the fuse (tp).
Time in Seconds
200
300
500
700
1000
2000
3000
5000
7000
10000
Current in Amperes
smaller than 100ms but make sure that it carries they carry
Figure 14. the discharging current. (Fig. 17).
11
690 Volt European/IEC Style Ratings and Application Data
Body Amp Rated Melting Total I�t ***Watts DIN 110 DIN 80 French Blade Tapped Single
Size Rating Voltage I2 t @ 660VAC Loss Catalog NO. Catalog NO. Catalog NO. Catalog NO.
(A2s x 103) (A2s x 103) @ Rated Type D11A Type D08A Type EF TypeTTF
Current (W)
12
Application information cont. - All sizes
DC Voltage Capability vs. Time Constant Retail Curves (*) and Ipm corresponding to the rating
current 30 31 32 33 2x32 2x33
IN (A) * Ipm (A) * Ipm (A) * Ipm (A) * Ipm (A) * Ipm (A) * Ipm (A)
L (ms)
R 63 a 230
80 b a 80 a 300
100 a 360
70 125 a 460
160 a 650
60
Time Constant
700A
250A
400A
500A
200A
630A
315A
800
t (S)
Sec
600 C 3,5 mm
103 1000
400
100
102
200 30 C1
10
0 10
200 400 U (V)
Time in Seconds
a = 130
B1 = 1,25
1 A2 = 0,5
Figure 16. B2 = 0,6
C13 = 0,8
Provides the DC Voltage capability of the fuse as a function of circuit time constant
(L/R ratio). *Consult Factory for DC capabilities on amper rating not shown.
10 -1
10 -2
10 -3
10 -4
10 -2 10 -3 10 -4 I (A)
Current in Amperes
Figure 17.
13
5.1.8 Conclusions 5.2 Case study #2
Both selected fuses, A70QS 400A and A070URD 450A 5.2.1 UPS data (EXL-S1)
models, are suitable to protect the battery against short yyRating: 400kVA; 400kW (PF = 1)
circuit, the Magnetic intervention time is below 100msec
yyRuntime: 5 minute
at 3-5kA.
yyBattery type: CSB GPL 121000; 100Ah @ 20h rate
The backup time of 15 minutes can be easily managed by
the fuses, the A70QS fuse curve does not provide Time in yyNumber of blocks/cells: 40/240 or 50/300
seconds above 100(s), therefore we have been forced to yyFloat voltage: 545V or 681V at 20°C ambient (2.27 V/cell)
ask the supplier about its capability at 15 minutes, 900(s). yyEoD voltage: 396V or 495V (1.65 V/cell)
The Interrupting ratings for both types are 100kA,
considering the worst-case scenario for the short circuit
current of 5kA, the fuses can safely trip.
5.2.3 Battery Fault current yyShort circuit current: 2606A, not specified the duration.
The battery fault current value is usually given by the yyThe available battery short circuit current is affected by
battery manufacturer and it is available on the product the state of charge and the aging of the battery. Another
datasheet. If it is not available, it can be requested to the important parameter that will reduce the available fault
battery manufacturer. current is the impedance of the connection.
For this specifc case see the above table 6: yyThe final fault current to be considerd for the sizing of
the protection will be 60% of the nominal hence 1.6kA.
14
5.2.4 Discharging data cables connected to the negative. The inductance
increase by increasing the distance between the cables.
The battery protection device MUST NOT open during a
A time constant of 10ms is representative of a typical
battery discharge at risk of losing the UPS basic functionality
installation.
of the load supply in mains failure.
Battery power = (Pn x PF) / (DC/AC)η = 400 kW / 0.96 = d) Available fault current. The fault current provided by
417 kW. the battery depends by various factors such as state
Max discharge current at EoD = Battery Power / EoD of charge, aging and connection cables. To take care of
voltage = 417kW / 396V = 1050A for 240Cells and 417Kw / the variable related to the battery (EoD and EoL) the
495V = 843A for 300Cells. actual fault current will 60% of the nominal one. The
selection of the connections cable (section and length)
Number of strings Calculation should guarantee that the voltage drop between UPS
From the above table 7 we can see that for 5 minutes the and battery, with max discharging current, is less than
battery power is 4008W/battery. 1% of the UPS battery voltage at the EoD.
Total power of one string 4kW x 40 = 160kW or 4Kw x 50 e) Intervention time. The rating current of the fuse should
= 200kW allow the UPS to operate in battery mode in all specified
N.Strings with 40 battery => 417kW / 160kW = 2,6 therefore conditions and open the fault in a limited time whit the
3 strings needed. 60% of the fault current in 100ms. The Melting curve
N.Strings with 50 battery => 417kW / 200kW = 2,1 therefore provide the following info: max current below which the
3 strings needed. fuse dose not open; time to the melting of the fuse (tp).
Current at the EoD is 1050 A / 3 = 350A and 842A / 3 = 281A The key data are:
Each string will have its own fuse.
yyGreen area, normal operating conditions. Max
5.2.5 Fuse sizing current (EoD current) 350A and 281A
The key points for the selection of the fuse are: yyRed area, fault conditions. Minimum fault current
a) DC rated fuse or AC rated with specified DC voltage 2.6kA x 0,6 = 1.6 kA.
capability. The 224A rated one, size 2, can andle 422A for 5 minutes
b) Voltage Rating considering the downgrade due to the (Tab 8).
L/R It has a melting time of about 150ms slightly above the target
c) The time constant (L/R) of the circuit lower than 10ms (100ms) but still acceptable (Fig. 20). The other variabile
d) Available fault current that must be considered is the fuse switch disconnector
because the supplier indicated what is the Max. permissible
5.2.6 ETI fuse NH serie
power loss fuse link in continuos operation. This introduces
The four steps check list to be covered is: a further limitation into the fuse selection:
a) It is available in two ratings 550Vdc and 700Vdc. The yyMax operating current at EOD 350A for 240Cells and
actual DC voltage capability should be checked based 281A for 300Cells
on the circuit time constant L/R. yyFrom the fuse data sheet (see below Tab. 9), the power
b) Voltage Rating considering the downgrade due to the dissipation at rated nominal current is 37W. Considering
L/R. Assuming L/R = 10ms the available DC voltage the discharging current ar 1.8V/cell and 240 cells hence
capability is 550Vdc and 700Vdc. The DC voltage 320A, the power dissipation of the fuse calculated with
capability must be verified against the possible voltages the below formula is 75W
present during the different type of fault:
yyThe max power handled by the fuse switch disconnector
yyFault between the poles, POS to NEG. The fuse must size 2 is only 34W (Tab. 10)
be able to open the float battery voltage of 545Vdc yyIn continuos operation the fuse supplier does not allow
in case of 40 blocks and 681Vdc in case of 50 blocks. to use this fuse with this switch disconnector for this
yyGround fault, worts case is NEG to GND. The fuse application. Since this fuse will not work with such
must be able to open the negative DC link 370Vdc. current continuously, it is necessary to consider to
A 700Vdc rated fuse covers 40 blocks and 50 blocks. use bigger fuse link size 3 , and also size 3 fuse switch
c) The time constant (L/R) of the circuit lower than disconnector
10ms. The time constant depends by the cabels and
how they are routed. Cables routed very close to each
other will have a L/R lower than connections with
the cables connected to the positive distant than the
15
Power dissipation for 240Cells
When choosing fuse switch disconnector consider
Pd(IB) = (IB/In)2 x Pd (In)
fuse link power dissipation!
Pd(IB) = (320/224)2 x 37
Pd(IB) � Py
Pd(IB) = 75W
Power dissipation of fuse link at maximal operating
current (IB): Pd(IB) = (IB/In)2 x Pd (In)
IB Maximal operating current
Pd(IB) Power dissipation of link at maximal operating
current
Pd(In) Power dissipation of fuse link at nominal current
Py Maximal permessible fuse link power dissipation
mounted in fuse switch disconnector
16
Technical data (in accordance with IEC/EN 60947-3)
Fuse Current Rating
Size 2 3
Technical Characteristics
Rated operational voltage Ue V 400 AC 500 AC 690 AC 250 DC 440 DC 400 AC 500 AC 690 AC 250 DC 440 DC
Rated operational current Ie A 400 400 400 400 400 630 630 630 630 630
Conv. free air thermal current with fuse-links, * Ith A 400 630
Conv. free air thermal current with solid-links, * Ith A 520 910
Rated frequency f Hz 40-60 40-60 40-60 / / 40-60 40-60 40-60 / /
Rated insulation voltage Ui V 1000 AC 1000 AC
Total power loss (without fuse) Pv W 1P - 9W, 3P - 28W 1P - 17W, 3P - 51W
Power loss at 80% Ith (without fuse-links), ** Pv W 1P - 6W, 3P - 17.9W 1P - 10.9W, 3P - 32,6W
Rated impulse withstand voltage Uimp kV 8 8
Utilisation category*** AC-23B AC-22B AC-21B DC-22B DC-21B AC-23B AC-22B AC-21B DC-22B DC-21B
Rated conditional short-circuit current, ***, **** kA 120 (500V), 100 (690V) 120 (500V), 100 (690V)
Rated short-time withstand current Icw kA 15/1s 15/1s
Fuse links
Size - DIN VDE 0636-2 - - 2 3
Max. rated current (gG) In A 400 400 400 400 400 630 630 630 630 630
Max. permissible power loss per fuse link Pa W 34 48
* Mounting of several units in low voltage switchgear-combinations, please think aboout rated diversity factors acc. to DIN EN 61439.
** Reference value for replacement of devices acc. to DIN EN 61439-1 clause 10.10.4.2.
*** minimum distance to earthed, conductive parts: Lateral: 20mm/Above: 50mm
*** A) Lateral: 50mm/Above: 100mm
**** Type tested with NH fuse-links characteristic gG
***** 35°C Normal temperature, at 55°C with reduced operating current
Table 10.
Battery array
Battery string 1 F1
Battery string 2 F2
Battery string n Fn
Figure 18.
17
Battery string n21
F
Figure 19.
2
500A
400A
200A
630A
350A
250A
100A
224A
425A
160A
315A
125A
40A
80A
50A
63A
35A
104
tv / s
6
4
103
6
4
2
102
6
4
2
101
6
4
2
100
6
4
2
101
6
4
2
102
6
4
4 6 102 2 4 6 103 2 4 6 104 2
Ip/A
Figure 20.
18
5.2.7 Conclusion: amount of current that the circuit breaker has to interrupt
yy A bigger fuse rated 250A, size 3 is the smaller rating during a fault could potentially exceed it's rating.
which can use size 3 fuse switch disconnector . It can 5.3 Case study Fuse #3
andle 440A for 5 minutes, but unfortunately it has a
5.3.1 UPS data (EXL-S1)
melting time of about 200ms, which is above the target
and not acceptable too (Tab. 9). yyRating: 400kVA; 336kW (PF=0.84)
yyRuntime: 5 minute
yy From the fuse data sheet, the power dissipation at rated
yyBattery type: P12V2130 86Ah @ 10h rate
nominal current is 43W. Considering the discharging
yyNumber of blocks/cells: 50/300
current ar 1.8V/cell and 300cells hence 257A, the
yyFloat voltage: 681V at 20°C ambient (2.27 V/cell)
power dissipation of the fuse calculated with the below
yyEoD voltage: 495V (1.65 V/cell)
formula is 45W.
yy The max power handled by the fuse switch disconnector 5.3.2 Battery data (Tab. 11)
size 3 is 48W, therefore it is ok (Tab. 10). 5.3.3 Battery Fault current
Power dissipation for 300Cells The battery fault current value is usually given by the
battery manufacturer and it is available on the product
Pd(IB) = (IB/In)2 x Pd (In)
datasheet. If it is not available, it can be requested to the
Pd(IB) = (257/250)2 x 43 battery manufacturer.
Pd(IB) = 45W For this specifc case see the above table 11:
For battery banks with parallel strings, a good practice is to yyShort circuit current: 2180A, not specified the duration.
include overcurrent protection for each battery string (Fig. Max current 2130A for 5 sec
18). This minimizes the potential of the bank backfeeding a yyThe available battery short circuit current is affected by
single shorted battery (Fig. 19), which can lead to fires and the state of charge and the aging of the battery. Another
property damage. important parameter that will reduce the available fault
current is the impedance of the connection.
Battery-string fusing is best accomplished with appropri-
yyThe final fault current to be considerd for the sizing of
ately sized dc-rated fuses secured in bolt-in fuse holders
the protection will be 60% of the nominal hence 1.3kA.
that are housed in a single enclosure. This arrangement
Using the same ratio the max current for 5 sec is 1.28kA
makes it easy to isolate one battery string for testing or
maintenance while allowing the system to continue opera- 5.3.4 Discharging data
tion. Individual battery-string fuses can provide protection
The battery protection device MUST NOT open during a
against catastrophic failure in the event of major fault in the
battery discharge at risk of losing the UPS basic functionality
main disconnect breaker panel or elsewhere in the battery
of the load supply in mains failure.
bank. Series fuses on each battery string also reduce the
Battery power = (Pn x PF) / (DC/AC)η = 336kW / 0.96 =
available short circuit current levels, allowing for the use of
350kW.
lower ampere interrupting current rated circuit breakers for
the inverter/ charger disconnects. Without the fuses, the
Specifications
Exide type Part number Nominal Nominal Power Lenght Width Height Weight Internal Short Max Therminal
designation Voltage Capacity 15 min. I b/w h1 approx. resistance circuit perm
V C10 1.60 max. max. max. kg mOhm current current
1.80 Vpc Vpc mm mm mm A 5
25°C 25°C secs.
A
P12V2130 NAPW122130HP0MA 12 86 2130 359.0 172.0 226.0 33.00 6 2180 2130 M-M8
19
Max discharge current at EoD = Battery Power / EoD voltage For this specifc case see the below table 13:
= 350kW / 495V = 707A. yyShort circuit current: 5000A, not specified the duration.
Number of strings Calculation yyThe available battery short circuit current is affected by
From the above table we can see that for 5 minutes the the state of charge and the aging of the battery. Another
battery power is 4kW/battery. important parameter that will reduce the available fault
Total power of one string 4kW x 50 = 200kW current is the impedance of the connection.
N.Strings => 350kW / 200kW = 1,75 therefore 2 strings yyThe final fault current to be considerd for the sizing of
needed. the protection will be 60% of the nominal hence 2 x 5kA
Current at the EoD is 707A / 2 = 354A. x 0.6 = 6kA.
Each string will have its own fuse. 5.4.3 Discharging data
5.3.5 Fuse sizing The battery protection device MUST NOT open during a
Since the EoD current is similar to the one calculated on battery discharge at risk of losing the UPS basic functionality
case study #2, for the fuse selection applies the same of the load supply in mains failure.
consideration as before. Battery power per core = (Pn x PF) / (DC/AC)η = 300kW /
0.962 = 312kW.
5.4 Case study #4
Max discharge current at EoD = Battery Power / EoD voltage
5.4.1 UPS data = 312kW / 496V = 788A.
yyTrinergy CUBE with 2 x 400kVA cores w/ distributed Number of strings Calculation
battery
From the below table we can see that for 5 minutes the
yyLoad size: 300kW
battery power is 4883W/battery, 814W/cell (Tab. 12)
yyRuntime: 5 minutes
312.000/240 = 1300W/cell
yyBattery type: Enersys – Genesis XE95 40 x 95Ah
1300W/814W = 1,6 strings> to strings per core
yyFloat voltage: 545V at 20°C ambient (2.27 V/cell)
2 strings per core.
yyEoD voltage: 396V (1.65 V/cell)
Battery Short Circuit Current Identification
5.4.2 Battery Fault current
The battery short circuit current value is usually given by
The battery fault current value is usually given by the the battery manufacturer and is available on the product
battery manufacturer and it is available on the product datasheet. If it is not available, it can be acquired and
datasheet. If it is not available, it can be requested to the requested from the battery manufacturer (CSB, YUASA,
battery manufacturer. FIAMM, etc.).
Constant Power Discharge Performance - Constant power discharge rate, watts per battery to 10.02V at 25°C (77°F)
Minutes Hours
Battery 5 10 15 30 1 5 8 10 20
XE13 701.0 443.0 330.0 195.0 111.0 27.0 17.0 14.0 7.0
XE16 857.0 546.0 412.0 247.0 143.0 36.0 24.0 19.0 10.0
XE30 1565.0 1017.0 767.0 455.0 258.0 62.0 41.0 33.0 18.0
XE40 2155.0 1426.0 1085.0 652.0 376.0 93.0 60.0 49.0 26.0
XE60 3337.2 2175.4 1644.2 976.8 556.3 137.1 90.3 74.2 40.7
XE70 3636.0 2411.0 1833.0 1091.0 615.0 142.0 90.0 73.0 37.0
XE95 4883.4 3241.0 2482.0 1494.0 861.6 212.4 139.8 114.0 61.2
Table 12.
Nominal Nominal Dimensions
Capacity (Ah)
10 hr rate to Overall Internal Typical
Nominal Length Width Height Torques
Type 1.67Vpc Weight Resistance Short Circuit
Voltage (V) (mΩ) Current (A)
@ 25°C/77°F mm in mm in mm in kg Ibs in-Ibs Nm
XE95 12 95 329.9 12.99 172.5 6.79 218.9 8.62 35.1 77.4 60 6.8 2.2 5000
Table 13.
20
5.4.4 CB selection ABB TMAX T6
Tmax T6 800A N type
Amp Rating Rated Service Voltage (DC) Rated Icu breaking capacity kA
800 750 16
Table 14.
1. Identification of Un, rated voltage of the system (Ue≥Un). 3. Coordination with the fault current
For 3 poles in series this CB is rated 750Vdc hence 750Vdc ≥ This Breaker has I3 = 4000A, designed for DC
545Vdc, usable in this specific application (Tab. 16). Km=1 hence 6000A (battery fault current) ≥ 4000A
2. Coordination with the EoD current (Tab. 14). (Tab. 15)
This is CB is rated 800A hence 800A ≥ 788A (EoD current)
T6 630/800 - TMA
I1 (400 Hz) I3 setting (MIN=5xln)
In MIN MED MAX I3 (50 HZ) Km I3 (400 HZ)
T6N 630 630 397 482 567 3150 1.5 4725
T6N 800 800 504 602 720 4000 1.5 6000
Table 15.
It is considered a TN power distribution, the minimum number of poles in series is 3 to get 750Vdc with a ultimate short circuit
current of 16kA (T6N) and a voltage umbalance between polarites and earth.
TMAX T6 (O)
Rated uninterrupted current (A) 630/800/1000
Poles (No.) 3/4
Rated service voltage, Ue (AC) 50-60 Hz (V) 690
(DC) (V) 750
Rated impulse withstand voltage voltage, Uimp (kV) 8
Rated insulation voltage, Ui (V) 1000
Test voltage at industrial frequency for 1 min. (V) 3500
Rated ultimate short-circuit breaking capacity, Icu N S H L V
(AC) 50-60 Hz 220/230 V (kA) 70 85 100 200 200
(AC) 50-60 Hz 380/400/415 V (kA) 36 50 70 100 150
(AC) 50-60 Hz 440 V (kA) 30 45 50 80 120
(AC) 50-60 Hz 500 V (kA) 25 35 50 65 85
(AC) 50-60 Hz 690 V (kA) 20 22 25 30 40
(DC) 250 V - 2 poles in series (kA) 36 50 70 100 -
(DC) 250 V - 3 poles in series (kA) - - - - -
(DC) 500 V - 2 poles in series (kA) 20 35 50 65 70
(DC) 500 V - 3 poles in series (kA) - - - - -
(DC) 750 V - 3 poles in series (kA) 16 20 36 50 50
Rated short-circuit breaking capacity, Ics
(AC) 50-60 Hz 220/230 V (%Icu) 100% 100% 100% 75% 100%
(AC) 50-60 Hz 380/400/415 V (%Icu) 100% 100% 100% 75% 75% (120)
(AC) 50-60 Hz 440 V (%Icu) 100% 100% 100% 75% 75% (100)
(AC) 50-60 Hz 500 V (%Icu) 100% 100% 100% 75% 75% (65)
(AC) 50-60 Hz 690 V (%Icu) 75% 75% 75% 75% 75%
Rated short-circuit breaking capacity, Icm
(AC) 50-60 Hz 220/230 V (kA) 154 187 220 440 440
(AC) 50-60 Hz 380/400/415 V (kA) 75.6 105 154 220 330
(AC) 50-60 Hz 440 V (kA) 63 94.5 105 176 264
(AC) 50-60 Hz 500 V (kA) 52.5 73.5 105 143 187
(AC) 50-60 Hz 690 V (kA) 40 46 52.5 63 84
Opening time 415 (V) (ms) 10 9 8 7 7
Utilisation category (IEC 60947-2) B (630A - 800A) (5) - A (1000A)
Reference Standard IEC 60947-2
Isolation behavior
Trip units Thermomagnetic
T fixed, M fixed TMF -
T adjustable, M fixed TMD -
T adjustable, M fixed, M adjustable (5...10 x In) TMA (up to 800A)(4)
T adjustable, M fixed (3 x In) TMG -
T adjustable, M fixed, M adjustable (2.5...5 x In) TMG
Magnetic only MA
Table 16.
21
TMA Releases ThermoMagnetic, Thermal adjustable Magnetic threshold Thermal threshold
(0,7-1 In), Magnetic adjustable (5-10 In) Fig. 21. (5 to 10 x In) Adjustable(0.7 to 1 x In)
T6 800 - TMA
In = 800 A
Figure 21.
t (s)
104
2h
1h
30'
103 20'
Thermal Cold Trip* @
10' 2In 900 sec
5'
Thermal Typical Trip*@
2In 200 sec
102 2'
1'
Thermal Hot Trip* @
2In 40 sec
10
10 -1 10 -1.05 10 102
x I,
Figure 22.
22
5.4.5 Conclusions (Fig. 22)
The Tmax T6 N type 800A 750Vdc model is suitable to
protect the battery against short circuit, the Magnetic
intervention time is below 100msec at 6-10kA.
The back up time of 5 minutes can be easily managed by
the breaker, with 2 strings in parallel the autonomy is even
larger, about 7 minutes without any risk of thermal tripping.
The Interrupting ratings for the N type is 16kA, considering
the worst case scenario for the short circuit current of 10kA,
the breaker can safely trip.
Another important consideration to be done is when one
string fail (open cell), OCV and impedance vary until only
one string remains active and able to supply the load for
only 1 minute. The breaker will be ineffective in this case
against short circuit, the current will be only 3kA and the
magnetic intervention time 10-200sec. During this period
the battery can burn, therefore is extremely important
to monitor the battery with BMS. Finally, It must be clear
that, on the basis of the conditions in which an overload is
presented, i.e. with the circuit breaker at thermal running or
not, the thermal relay trip varies considerably. For example,
for an overload current of 2 x In, the trip time is between 40
and 200sec. for hot trip, and between 200 and 900sec. for
cold trip.
23
VertivCo.com | Vertiv Infrastructure Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB188146827
© 2019 Vertiv Co. All rights reserved. Vertiv™, the Vertiv logo and Liebert® GXT4 are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While
every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. Assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change
without notice.