TEST REPORT EQUIPOTENTIAL BONDING /

GROUNDING REPORT (AZO/KAHL TOWER L1)

Customer Order-No. Project


Household Waste Recycling
UBQ Materials NL B.V. 124712-00
Plant

All values were measured with the following measuring instrument:

Manufacturer Type Serial-No

Fluke 1587 FC 202306836

For measuring of the equipotential bonding you have to use an appropriated and licensed earth ground
tester.

Inspector: Name Signature Date

DUVOLT Daniel Massaqui 09-11-2023

Ubq Caio Santos 09-11-2023

Location of measured Resistance


No. Measured part: Reference point:
part: in Ω
P2-12-PEL-SI4570
1 Bunker MCC 0.2
(HP1221)
P2-12-PEL-SI4570
2 Bunker Structure MCC 0.2
(HP1221)
P2-12-PEL-SI4570
3 Scale 0111 MCC 0.2
(HP1221)
P2-12-PEL-SI4570
5 Scale 0211 MCC 0.2
(HP1221)
P2-12-PEL-SI4570
6 Scale frame 0111 MCC 0.2
(HP1221)
P2-12-PEL-SI4570
7 Scale frame 0211 MCC 0.2
(HP1221)
P2-12-PEL-SI4570
8 Piping MCC 0.3
(HP1221)
P2-12-PEL-SI4350
9 Storage MCC 0.2
(HP1212)
P2-12-PEL-SI4350
10 Piping MCC 0.2
(HP1212)
P2-12-PEL-SI4350
11 Tank MCC 0.3
(HP1212)
P2-12-PEL-SI4350
12 Filter 1 MCC 0.2
(HP1212)
P2-12-PEL-SI4350
13 Filter 2 MCC 0.2
(HP1212)
P2-12-PEL-SI4350
14 Pneumatic box 1212 MCC 0.2
(HP1212)
15 +L1207 Panel MCC 0.2

16 +L1208 Panel MCC 0.2

17 +Print 12 Panel MCC 0.2


SO-O-0074-01-EN

09.11.2023 / Kurzzeichen Page 1 from 2


TEST REPORT EQUIPOTENTIAL BONDING /
GROUNDING REPORT (AZO/KAHL TOWER L1)

Note: All measured values must be < 1 Ω !


SO-O-0074-01-EN

09.11.2023 / Kurzzeichen Page 2 from 2