C1779 CALC-010 REV A iQ Costume

Store Windload calculations

issue date 05/05/2022


Structural Calculations

for

Wind Loading Assessment


for Façade Systems and Sub-grid

iQ Costume Store, 160 Victoria Road,


North Acton,
London W3 6EE

for

MK Façades

Document Number:
21-0609 C01 Issue 1.0

The Ley, 55a Melrose Avenue


Pedmore Stourbridge
West Midlands DY8 2LE

t. 01384 374046
e. info@pearce-design.co.uk

Project no. 21-0609

Author AP
Checked SP
Issue 1.0

Date 16 August 2021


Calculation Summary

The Ley, 55a Melrose Avenue Wind Loading Assessment,


Project
Pedmore Stourbridge iQ Costume Store, North Acton
West Midlands DY8 2LE
Project no. 21-0609
t. 01384 374046
e. info@pearce-design.co.uk Date Issue 1.0 August 2021

Design Information
Client MK Façades Ltd

PDC Engineers AP

Relevant British NA and BS EN 1990:2002+A1:2005 Eurocode – Basis of structural design


standards, NA and BS EN 1991-1-1:2002 Eurocode 1. Actions on structures. General actions. Densities, self-weight,
Codes of practice imposed loads for buildings
and design standards NA and BS EN 1991-1-4:2005+A1:2010 Eurocode 1. Actions on structures. General actions. Wind actions

Intended building usage Residential with Commercial Units

Subsoil conditions N/A

Special considerations

Programme / release N/A

Index
Pages Elements of structure Pages Elements of structure

1100-01 to 02 Design Philosophy 5000-01 Appendix A – Architect’s Elevations


2000-01 to 36 Wind Actions

Quality

Calculations Calculations

Rev Date Check Pages Rev Date Checked Pages


Issue 1.0 8.21 SP All

Design risk assessment


Date completed
Date issued
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Design Philosophy Calc. no. 1100-01

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Ref Calculation Output

Philosophy

General

The project is located in North Acton, London and comprises a replacement façade
cladding system for an existing building.

The building comprises a series of adjoining multi-storey blocks up to seventeen storeys tall
above ground level. The proposed use of the building is primarily residential
accommodation with commercial retail at ground floor level.

The primary structure is assumed to be a reinforced concrete frame with an inner leaf
assumed to comprises an SFS-type lightweight cold-rolled steel frame, or similar.

Scope

PDC were instructed by our client, MK Façades Ltd, to carry out a wind loading assessment
for the building to enable structural design of replacement façade systems to be carried out.

The assessment and associated calculation document is intended to be used by PDC to


enable design of façade system components to be carried out on behalf of MK Façades
Ltd. The document is also suitable to be used by competent and qualified third parties for
the same purpose.

It is important to note that the wind loading assessment is only suitable for façade and
cladding systems only. Furthermore, the assessment does not include internal wind
pressure or suction coefficients and therefore is not suitable for design of window systems,
curtain-walling systems or inner leaf secondary steelwork etc.

The assessment is not intended to provide wind loading data for the complete façade of all
of the blocks. A detailed assessment is carried out for the principal blocks which should
provide adequate information to be able to design rational and economic façade systems
for the whole facade.

Reference Documentation

Documentation issued to PDC includes the following:

· Architect’s proposal and elevation drawings by Scott Brownrigg


· Original Architect’s plan drawings by Amos Architecture and Design
· Building survey plan and elevation drawings by Origin Surveys
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Design Philosophy Calc. no. 1100-02

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Ref Calculation Output

Design

The wind load assessment carried out by PDC is in accordance with BS EN 1991-1-4. The
assessment uses MasterSeries software to generate basic design loading and external
coefficients for façade design.

The building comprises a series of separate blocks which are of varying heights and
connected at different levels. The assessment combines the group of north-eastern blocks
into a single structure and also combines the group of south-western blocks into a separate
single structure.

An assessment of the effects of wind funnelling is carried out as a separate exercise to the
isolation case data provided. This applies to funnelling between blocks of the development
and also due to buildings located adjacent to the development. Where appropriate, this
should also be considered and applied to the design of façade systems.

Parameters for façade design:


Cs = 1.0
Cd = 1.0

Cpi = +/-0.0 (External coefficients only used)


Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-01

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Ref Calculation Output

Variable Actions, (Q)

Wind Loading

Aerial Photo

Site Plan
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-02

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Ref Calculation Output

Survey Plan

Refer to Appendix A for Scott Brownrigg architect’s elevations


Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-03

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Calculation

WIND LOADING TO EN 1991-1-4 UK NA


Results for site at TQ208818 - Altitude 10 m
Wind Reference 1
USING THE EN 1991-4 STANDARD METHOD
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-04

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Calculation

Site Basic Data


Location and Base wind speed BREVe site data for TQ208818 - Base wind speed, Vb 20.5 m/s
Site Range 500 m
Altitude and Obstructions Site altitude 10 m - Shelter effect from obstructions is not included
Seasonal factor, Ss Season length is All year - Seasonal factor, Ss 1.000
Annual risk and probability factor Design annual risk 0.02 - Probability factor, Sp 1.000
Topographic Increments Site altitude only - Topography not significant - assumed to be flat
Heights (m) Heights above ground 54.9
Building height, h (m) For 0.6 h limit on hdis 54.9 m

Direction Factors - Using UK direction Factors


Direction (°N) 0 30 60 90 120 150 180 210 240 270 300 330
Direction factor, Cdir 0.780 0.730 0.730 0.740 0.730 0.800 0.850 0.930 1.000 0.990 0.910 0.820

EN 1991-1-4 STANDARD METHOD


Direction (°N) 0 30 60 90 120 150 180 210 240 270 300 330
Direction factor, Cdir 0.780 0.730 0.730 0.740 0.730 0.800 0.850 0.930 1.000 0.990 0.910 0.820
Distance to Sea (km) 200.0 179.9 166.0 114.0 114.0 92.0 80.0 126.0 200.0 200.0 200.0 200.0
Distance in Town (km) 10.5 17.5 15.5 14.5 27.5 23.5 4.5 11.5 4.5 9.5 13.5 11.5
Altitude factor, Sa 1.010 1.010 1.010 1.010 1.010 1.010 1.010 1.010 1.010 1.010 1.010 1.010
Obstructions Height, Have (m) 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
Obstructions Spacing, Xo (m) 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
Displacement Height, Hdis (m) 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0

Height Above Ground = 54.9 m


Direction (°N) 0 30 60 90 120 150 180 210 240 270 300 330
Effective height, Ze (m) 54.90 54.90 54.90 54.90 54.90 54.90 54.90 54.90 54.90 54.90 54.90 54.90
Orography factor, Co 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Exposure factor, Ce 3.447 3.447 3.447 3.447 3.447 3.455 3.467 3.447 3.447 3.447 3.447 3.447
Roughness factor, Cr 1.315 1.315 1.315 1.315 1.315 1.316 1.318 1.315 1.315 1.315 1.315 1.315
Rough. Correction, CrT 0.859 0.849 0.851 0.852 0.846 0.846 0.879 0.857 0.879 0.861 0.854 0.857
Effective wind speed, Ve (m/s) 30.7 28.4 28.5 28.9 28.3 31.1 34.3 36.5 40.2 39.1 35.6 32.2
Dynamic Pressure, q (N/m²) 578.4 494.4 497.2 512.5 491.5 591.4 721.3 818.5 992.8 936.5 777.6 636.3

MASTERFRAME WIND PRESSURE VALUES


Dynamic Pressure Values, q (N/m²)
Wind Direction to X Axis 0 90 180 270
q (N/m²) for H = 54.9 936.5 992.8 591.4 578.4

Ground level
Ground Level has been set by the user as always being at the bottom of the model
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-05

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

A) South-Western Block

X Coordinates

Y Coordinates
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-06

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Z Coordinates
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-07

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 1

Wind Zones
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-08

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 1

Wind Coefficients
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-09

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 1

Wind Pressures
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-10

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 2

Wind Zones
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-11

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 2

Wind Coefficients
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-12

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 2

Wind Pressures
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-13

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 3

Wind Zones
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-14

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 3

Wind Coefficients
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-15

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 3

Wind Pressures
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-16

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 4

Wind Zones
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-17

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 4

Wind Coefficients
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-18

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 4

Wind Pressures
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-19

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

B) North-Eastern Block

X Coordinates

Y Coordinates
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-20

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Z Coordinates
Project IQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-21

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 1

Wind Zones
Project IQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-22

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 1

Wind Coefficients
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-23

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 1

Wind Pressures
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-24

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 2

Wind Zones
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-25

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 2

Wind Coefficients
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-26

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 2

Wind Pressures
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-27

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 3

Wind Zones
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-28

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 3

Wind Coefficients
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-29

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 3

Wind Pressures
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-30

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 4

Wind Zones
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-31

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 4

Wind Coefficients
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-32

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Wind Direction 4

Wind Pressures
Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-33

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Ref Calculation Output

Wind Funnelling

1) Consider funnelling between north-eastern block and south-western block:

This occurs in 2no. locations:

a) Between blocks on western elevation:

i) Lower Level

Width, b = 13.9, 28.8m


Height, h = 40.4, 21.9m

Therefore, e = 13.9m

Distance between block = 9.5m < e – therefore funnelling could occur

Use Cpe = -1.6 as worst case in Zone A

Wind Direction 1 governs

Therefore, maximum design suction load = -0.993 x 1.6 = -1.59kN/m2


Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-34

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Ref Calculation Output

ii) Upper Level

Width, b = 13.9, 16.6m


Height, h = 40.4, 41.0m

Therefore, e = 13.9m

Distance between block = 21.7m > e – funnelling will not occur

b) Between blocks on southern elevation

Width, b = 29.8, 18.7m


Height, h = 47.7, 38.3m

Therefore, e = 18.7m

Distance between block = 10.0m < e – therefore funnelling could occur

Use Cpe = -1.6 as worst case in Zone A

Wind Direction 2 governs

Therefore, maximum design suction load = -0.937 x 1.6 = -1.50kN/m2


Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-35

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Ref Calculation Output

2) Consider funnelling between western elevation and adjacent building to west:

Potential funnelling only at northern end:

Min. distance between buildings = 11.5m est.

Adjacent building is similar height to block therefore by inspection funnelling could occur:

Use Cpe = -1.6 as worst case in Zone A

Wind Direction 2 governs

Therefore, maximum design suction load = -0.937 x 1.6 = -1.50kN/m2


Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Actions Calc. no. 2000-36

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Ref Calculation Output

Inset Storey

‘Zone E’ in Green:

Wind Direction 2

b1 = 6.0m

Inset dim = 1.6m

0.2b1 = 1.2m therefore no further consideration required


Project iQ Costume Store, North Acton
Project no. 21-0609
Façade Wind Loading Assessment
Section Appendix A Calc. no. 5000-01

Eng. AP Date 8.21 Check SP Date 8.21 Rev Date

Ref Calculation Output

Appendix A
Architect’s Elevation Drawings
1:200 0 5m 10m 15m 20m

14th Floor

13th Floor

12th Floor

11th Floor

10th Floor

9th Floor
Existing vent grille, to be replicated

8th Floor
Valcan Vitradual 3mm aluminium panel
(colour to match existing)

7th Floor

Metal finish infill panel


6th Floor

5th Floor
Brickwork

4th Floor

3rd Floor

2nd Floor

NORTH ELEVATION
1:200 0 5m 10m 15m 20m

Top of Parapet

14th Floor

13th Floor

12th Floor

11th Floor

10th Floor

Existing vent grille, to be replicated

9th Floor
Valcan Vitradual 3mm aluminium panel
(colour to match existing)

8th Floor

Metal finish infill panel


7th Floor

6th Floor

Brickwork

5th Floor

4th Floor

3rd Floor

2nd Floor

1st Floor

EAST ELEVATION
Top of Parapet

17th Floor

1:200 0 5m 10m 15m 20m

16th Floor

15th Floor

14th Floor

13th Floor

12th Floor

11th Floor

10th Floor
Existing vent grille, to be replicated

9th Floor
Valcan Vitradual 3mm aluminium panel
(colour to match existing)

8th Floor

Metal finish infill panel


7th Floor

6th Floor
Brickwork

5th Floor

4th Floor

3rd Floor

2nd Floor

1st Floor

SOUTH ELEVATION
17th Floor

16th Floor
1:200 0 5m 10m 15m 20m

15th Floor

14th Floor

13th Floor

12th Floor

11th Floor

10th Floor

9th Floor
Existing vent grille, to be replicated

8th Floor Valcan Vitradual 3mm aluminium panel


(colour to match existing)

7th Floor

Metal finish infill panel

6th Floor

5th Floor Brickwork

4th Floor

3rd Floor

2nd Floor

1st Floor

WEST ELEVATION
17th Floor

16th Floor
1:200 0 5m 10m 15m 20m

15th Floor

14th Floor

13th Floor

12th Floor

11th Floor

10th Floor

9th Floor Existing vent grille, to be replicated

8th Floor
Valcan Vitradual 3mm aluminium panel
(colour to match existing)

7th Floor

Metal finish infill panel

6th Floor

5th Floor Brickwork

4th Floor

3rd Floor

2nd Floor

1st Floor

INNER NORTH ELEVATION


17th Floor

16th Floor
1:200 0 5m 10m 15m 20m

15th Floor

14th Floor

13th Floor

12th Floor

11th Floor

10th Floor

9th Floor Existing vent grille, to be replicated

Valcan Vitradual 3mm aluminium panel


8th Floor
(colour to match existing)

7th Floor

Metal finish infill panel

6th Floor

5th Floor Brickwork

4th Floor

3rd Floor

2nd Floor

1st Floor

INNER EAST ELEVATION


1:200 0 5m 10m 15m 20m

12th Floor

11th Floor

10th Floor

9th Floor

8th Floor
Existing vent grille, to be replicated

7th Floor Valcan Vitradual 3mm aluminium panel


(colour to match existing)

6th Floor

Metal finish infill panel

5th Floor

4th Floor
Brickwork

3rd Floor

2nd Floor

INNER SOUTH ELEVATION


1:200 0 5m 10m 15m 20m
Top of Parapet

14th Floor

13th Floor

12th Floor

11th Floor

10th Floor

9th Floor

Existing vent grille, to be replicated

8th Floor
Valcan Vitradual 3mm aluminium panel
(colour to match existing)

7th Floor

Metal finish infill panel


6th Floor

5th Floor
Brickwork

4th Floor

3rd Floor

2nd Floor

1st Floor

INNER WEST ELEVATION