Project:

Uzbekistan Sherabad 500MW Solar Power Plant Project

Owner: PMC: EPC Contractor:


Main consultant

Masdar Clean Energy GOPA International Energy


Consultant GmbH China Machinery Engineering
Sub-consultant Corporation

“NUR SHERABAD SOLAR PV” Juru Energy Consulting LLC.

LVDC, LVAC and MV Circuits Calculation Report


CMEC Document
SHB-CMEC-PV-ELE-CAR-0004
Number

Rev. 02

Date Submitted 2023-10-28

Prepared by Name Zhang Xian Sign

Approved by Name Li Ming Sign

Issued by Name Guo Weipeng Sign

Issued Purpose For Review For Info ✓

Document Revision Box

02 2023-10-28 Zhang Xian Li Ming Revised as per CRS

01 2023-09-29 Zhang Xian Li Ming Revised as per CRS

00 2023-07-17 Zhang Xian Li Ming First Issue

Rev. Date Originator Approver Status


LVDC, LVAC and MV Circuits Calculation Report

Part 1: LVDC Circuits Calculation Report (560W)

Part 2: LVDC Circuits Calculation Report (565W)

Part 3: LVAC Circuits Calculation Report (560W)

Part 4: LVAC Circuits Calculation Report (565W)

Part 5: MV Circuits Calculation Report

Part 6: LVDC, LVAC and MV Circuits Calculation


Report(By CYMCAP)

Part 7: Cyclic daily load factor


Part 1

LVDC Circuits Calculation Report (560W)


CONTENT

1. GENERAL

2. INPUT DATA

3. MINIMUM CURRENT CARRYING

4. VOLTAGE DROP & POWER LOSS

5. CONCLUSION

6. REFERENCE

7. ANNEX

A CURRENT-CARRYING CAPACITIES & DERATING FACTORS

B DETAIL CALCULATE OF EACH STRING


1. GENERAL

1.1 Project

SHERABAD 500MW SOLAR POWER PLANT PROJECT


IN UZBEKISTAN

1.2 Purpose

This calculation report is aimed to determine the sizing of LVDC Cable in PV area,

which shall be used between modules and string inverters.

1.3 Methodology

1) Approach method based on IEC 60364-5-52 standards are adopted.

2) The minimum cable sizing shall be based upon a overcurrent rating from
Table 5, IEC 62548:2016.

3) The specified laying conditions, including ground temperature, soil thermal


resistance, groups of circuits, and buried depth of cables would be considered.

4) The worst laying conditions shall be considered for cable derating.

5) Voltage drop and Power loss would be calculated.


2. INPUT DATA

2.1 Electrical Parameters

System frequency = 50 Hz
Voltage level of LVDC cable = DC 1.5 kV

Copper 1Cx6 sqmm solar cable are proposed to be used, and the following
parameters are obtained from IEC 60228:
DC resistance of conductor at 20°C = 3.390 Ω/km
Temperature coefficient of electrical resistivity = 0.00393 1/K
Normal operating temperature of conductor = 75 °C
DC resistance of conductor at 75°C = 4.123 Ω/km

Copper 1Cx4 sqmm solar cable are proposed to be used, and the following
parameters are obtained from IEC 60228:
DC resistance of conductor at 20°C = 5.090 Ω/km
Temperature coefficient of electrical resistivity = 0.00393 1/K
Normal operating temperature of conductor = 75 °C
DC resistance of conductor at 75°C = 6.190 Ω/km

Following parameters are to be considered for Modules:


Module Serie = JW-HD144N
Module Type = BIFACIAL
Peak Power (Pmax) @ STC condition = 560 Wp
MPP Voltage (Vmp) @ STC condition = 42.40 V
MPP Current (Imp) @ STC condition = 13.21 A
Open Circuit Voltage (Voc) = 50.68 V
Short Circuit Current (Isc) = 14.12 A
No. of Modules per string = 28

2.2 Method of installation

Ambient air temperature, air = 45 °C


Ground temperature, soil = 20 °C
Soil thermal resistivity = 1.5 K.m/W
Burried deepth, approx. = 0.8 m
3. MINIMUM CURRENT CARRYING

MAX. MAX.
CURRENT CURRENT CHECK
CASE VOLTAGE CABLE TYPE PERMISSIBLE k1 k2 k3 PERMISSIBLE
Imp STC 1.25ISC STC Iz' > 1.25Imp STC
CURRENT Iz CURRENT Iz'

(kV) (A) (A) (A) (A)

A DC 1.5 CO., 1X6 sqmm 13.21 16.51 53 1.00 1.0 0.45 23.85 YES

B DC 1.5 CO., 1X6 sqmm 13.21 16.51 72 1.00 0.38 27.36 YES

C DC 1.5 CO., 1X4 sqmm 13.21 16.51 57 1.00 1.00 57.00 YES

NOTE:

1. Derating factors k1, k2, k3 are obtained from "Annex A. Current-carrying capacities & derating factors".

I Z'  I Z  k1  k2  k3
k1: derating factor of ambient or ground temperature

k2: derating factor of soil thermal resistivity (NOT for cables in air)

k3: derating factor of grouping circuits

2. Max. permissible current Iz for Copper,1C x 6 sqmm cable are from "Annex A. Current-carrying capacities & derating factors".

3. Worst cases for derating to be considered:

CASE - A: Groups of 12 (twelve) circuits of DC cable through one single ducts directly burried.

CASE - B: Groups of 20 (twenty) circuits of DC cable lead up to inverter in air.

CASE - C: Single circuit of DC cable connect modules.


4. VOLTAGE DROP & POWER LOSS

1X6 1X4
SINGLE MPP CURRE MODULE TOTAL STRING 1X6,RAC 1X4,RAC 1X6 1X4 % %
CABLE CABLE CABLE POWER
MODULE VOL. NT NO. PER STRING VOL. AT AT FROM TO VOL. VOL. VOL. POWER
TYPE LENGTH LENGTH LOSS
POWER Vmp Imp STRING POWER Ump 75 Deg C 75 Deg C DROP DROP DROP LOSS
(+ & -) (+ & -)
(Wp) (V) (A) (Wp) (V) (Ω/km) (Ω/km) (m) (m) (V) (V) (%) (W) (%)
Co., 1X6
Avg. 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR INV 79 8.40 4.3 0.7 0.42 65.7 0.42
Co., 1X4
Co., 1X6
Max. 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR INV 169 8.40 9.2 0.7 0.83 130.5 0.83
Co., 1X4
Co., 1X6
Min. 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4

MAXIMUM VOLTAGE DROP PERCENTAGE 0.83 %


COEFFICIENT OF LAYING 1.03
TOTAL POWER LOSS OF LVDC CABLE 41555 W
TOTAL POWER IN TYPICAL INVERTER BLOCK 9690240 W
TOTAL POWER LOSS PERCENTAGE IN TYPICAL INVERTER BLOCK 0.43 %

NOTE: Detail caculate for each strings shown in annex B.


5. CONCLUSION

5 Conclusion

The sizing of LVDC Cable between modules and string inverters in PV area

would be selected as copper,1C x 6 sqmm.

The sizing of LVDC Cable connect modules in PV area

would be selected as copper,1C x 4 sqmm.

Also, IEC 62930 are specificed in Contract in this project.

So, this cable would be selected as following type:

- 62930 IEC 131 1500V DC 1x6


6. REFERENCE

1 IEC 60287-1-1, Edition 2.1, Electric cables – Calculation of the current


rating – Part 1-1: Current rating equations (100 % load factor) and
calculation of losses – General

2 IEC 60287-2-1, Edition 2.0, Electric cables – Calculation of the current


rating – Part 2-1: Thermal resistance – Calculation of thermal resistance

IEC 60364-5-52, Edition 3.0, Low-voltage electrical installations – Part 5-


3
52: Selection and erection of electrical equipment – Wiring systems

IEC 60364-5-54, Edition 3.0, Low-voltage electrical installations – Part 5-


4 54: Selection and erection of electrical equipment – Earthing
arrangements and protective conductors

5 IEC 62548, Edition 1.0, Photovoltaic (PV) arrays – Design requirements

6 IEC 62930, Edition 1.0 Electric cables for photovoltaic systems with a
voltage rating of 1,5 kV DC
IEC 60502-1, Edition 2.1, Power cables with extruded insulation and their
7
accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um =
36 kV) – Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV
(Um = 3 6 kV)
8 IEC 60364-7-712, Edition 2.0, Low voltage electrical installations – Part 7-
712: Requirements for special installations or locations – Solar
photovoltaic (PV) power supply systems

9 IEC 60228, Third edition, Conductors of insulated cables


7. ANNEX

7 Annex

A Current-carrying Capacities & Derating Factors

B Detail calculate of each string


ANNEX - A
ANNEX - B

1X6 1X4
SINGLE MPP CURRE MODULE TOTAL STRING 1X6,RAC 1X4,RAC 1X6 1X4 % %
FEEDE CABLE CABLE CABLE POWER
INV NO. MODULE VOL. NT NO. PER STRING VOL. AT AT FROM TO VOL. VOL. VOL. POWER
R NO. TYPE LENGTH LENGTH LOSS
POWER Vmp Imp STRING POWER Ump 75 Deg C 75 Deg C DROP DROP DROP LOSS
(+ & -) (+ & -)
(Wp) (V) (A) (Wp) (V) (Ω/km) (Ω/km) (m) (m) (V) (V) (%) (W) (%)
Co., 1X6
1 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-01 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
2 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-02 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
3 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-03 INV 142 8.40 7.7 0.7 0.71 111.4 0.71
Co., 1X4
Co., 1X6
4 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-04 INV 68 8.40 3.7 0.7 0.37 48.6 0.31
Co., 1X4
Co., 1X6
5 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-05 INV 68 8.40 3.7 0.7 0.37 48.6 0.31
Co., 1X4
Co., 1X6
6 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-06 INV 132 8.40 7.2 0.7 0.66 94.7 0.60
Co., 1X4
Co., 1X6
7 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-07 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
8 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-08 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
01、02、 Co., 1X6
9 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-09 INV 121 8.40 6.6 0.7 0.61 96.2 0.61
03、04、 Co., 1X4
05、06、 Co., 1X6
10 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
07、08、 Co., 1X4
09、10、 Co., 1X6
11 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
20、21、 Co., 1X4
22、23、 Co., 1X6
24 12 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-12 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
Co., 1X6
13 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-13 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
14 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-14 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
15 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-15 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
Co., 1X6
16 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-16 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
17 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-17 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
18 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-18 INV 121 8.40 6.6 0.7 0.61 96.2 0.61
Co., 1X4
Co., 1X6
19 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
20 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
21 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-20 INV 132 8.40 7.2 0.7 0.66 103.8 0.66
Co., 1X4

Co., 1X6
1 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-01 INV 99 8.40 5.4 0.7 0.51 80.4 0.51
Co., 1X4
Co., 1X6
2 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-02 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4
Co., 1X6
3 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-03 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4
Co., 1X6
4 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-04 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
5 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-05 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
6 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-06 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
7 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-07 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
8 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-08 INV 57 8.40 3.1 0.7 0.32 40.9 0.26
Co., 1X4
Co., 1X6
9 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-09 INV 57 8.40 3.1 0.7 0.32 40.9 0.26
Co., 1X4
Co., 1X6
10 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 33.2 0.21
Co., 1X4
16
Co., 1X6
11 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 33.2 0.21
Co., 1X4
Co., 1X6
12 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-12 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
13 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-13 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
14 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-14 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
15 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-15 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
16 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-16 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
17 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-17 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
18 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-18 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
19 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
20 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4
Co., 1X6
21 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-20 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4

Co., 1X6
1 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-01 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
2 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-02 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
3 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-03 INV 132 8.40 7.2 0.7 0.66 103.8 0.66
Co., 1X4
Co., 1X6
4 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-04 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
5 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-05 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
6 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-06 INV 121 8.40 6.6 0.7 0.61 96.2 0.61
Co., 1X4
Co., 1X6
7 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-07 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
8 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-08 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
9 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-09 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
Co., 1X6
10 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
25
Co., 1X6
11 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
12 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-12 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
Co., 1X6
13 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-13 INV 73 8.40 4.0 0.7 0.39 61.5 0.39
Co., 1X4
Co., 1X6
14 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-14 INV 137 8.40 7.5 0.7 0.69 107.7 0.69
Co., 1X4
Co., 1X6
15 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-15 INV 84 8.40 4.5 0.7 0.44 69.1 0.44
Co., 1X4
Co., 1X6
16 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-16 INV 148 8.40 8.0 0.7 0.74 115.3 0.74
Co., 1X4
Co., 1X6
17 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-17 INV 94 8.40 5.1 0.7 0.49 76.7 0.49
Co., 1X4
Co., 1X6
18 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-18 INV 158 8.40 8.6 0.7 0.78 122.9 0.78
Co., 1X4
Co., 1X6
19 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 105 8.40 5.7 0.7 0.54 84.3 0.54
Co., 1X4
Co., 1X6
20 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 105 8.40 5.7 0.7 0.54 84.3 0.54
Co., 1X4
Co., 1X6
21 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-20 INV 169 8.40 9.2 0.7 0.83 130.5 0.83
Co., 1X4

Co., 1X6
1 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-01 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4
Co., 1X6
2 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-02 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4
Co., 1X6
3 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-03 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
4 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-04 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
5 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-05 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
6 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-06 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
7 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-07 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
8 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-08 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
9 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-09 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
Co., 1X6
10 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
29
Co., 1X6
11 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
12 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-12 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
Co., 1X6
13 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-13 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
14 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-14 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
15 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-15 INV 121 8.40 6.6 0.7 0.61 96.2 0.61
Co., 1X4
Co., 1X6
16 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-16 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
17 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-17 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
18 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-18 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
19 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
20 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-20 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
21 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-21 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4

Co., 1X6
1 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-01 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4
Co., 1X6
2 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-02 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4
Co., 1X6
3 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-03 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
4 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-04 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
5 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-05 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
6 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-06 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
7 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-07 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
8 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-08 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
9 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-09 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
12、13、 10 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
14、16、
Co., 1X6
17 11 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
12 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-12 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
13 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-13 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
14 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-14 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
15 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-15 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
16 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-16 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
17 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-17 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
18 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-18 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
19 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4
Co., 1X6
20 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-21 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4

Co., 1X6
1 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-01 INV 142 8.40 7.7 0.7 0.71 111.4 0.71
Co., 1X4
Co., 1X6
2 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-02 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
3 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-03 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
4 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-04 INV 132 8.40 7.2 0.7 0.66 103.8 0.66
Co., 1X4
Co., 1X6
5 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-05 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
6 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-06 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
7 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-07 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
Co., 1X6
8 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-08 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
9 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-09 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
10 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-10 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
11、19
Co., 1X6
11 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
12 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-12 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
13 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-13 INV 121 8.40 6.6 0.7 0.61 96.2 0.61
Co., 1X4
Co., 1X6
14 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-14 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
15 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-15 INV 132 8.40 7.2 0.7 0.66 103.8 0.66
Co., 1X4
Co., 1X6
16 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-16 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
17 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-17 INV 132 8.40 7.2 0.7 0.66 103.8 0.66
Co., 1X4
Co., 1X6
18 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-18 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
19 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 142 8.40 7.7 0.7 0.71 111.4 0.71
Co., 1X4
Co., 1X6
20 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-21 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4

Co., 1X6
1 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-01 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
2 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-02 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
3 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-03 INV 132 8.40 7.2 0.7 0.66 103.8 0.66
Co., 1X4
Co., 1X6
4 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-04 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
5 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-05 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
6 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-06 INV 121 8.40 6.6 0.7 0.61 96.2 0.61
Co., 1X4
Co., 1X6
7 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-07 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
8 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-08 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
9 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-09 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
Co., 1X6
10 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
26、27、 Co., 1X4
28 Co., 1X6
11 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
12 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-12 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
Co., 1X6
13 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-13 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
14 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-14 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
15 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-15 INV 121 8.40 6.6 0.7 0.61 96.2 0.61
Co., 1X4
Co., 1X6
16 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-16 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
17 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-17 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
18 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-18 INV 132 8.40 7.2 0.7 0.66 103.8 0.66
Co., 1X4
Co., 1X6
19 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
20 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-21 INV 142 8.40 7.7 0.7 0.71 111.4 0.71
Co., 1X4

Co., 1X6
1 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-01 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4
Co., 1X6
2 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-02 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4
Co., 1X6
3 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-03 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
4 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-04 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
5 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-05 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
6 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-06 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
7 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-07 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
8 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-08 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
9 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-09 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
10 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
15
Co., 1X6
11 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
12 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-12 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
13 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-13 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
14 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-14 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
15 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-15 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
16 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-16 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
17 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-17 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
18 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-18 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
19 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 105 8.40 5.7 0.7 0.54 84.3 0.54
Co., 1X4
Co., 1X6
20 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-21 INV 115 8.40 6.3 0.7 0.59 92.0 0.59
Co., 1X4

Co., 1X6
1 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-01 INV 89 8.40 4.8 0.7 0.46 72.8 0.46
Co., 1X4
Co., 1X6
2 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-02 INV 78 8.40 4.2 0.7 0.42 65.2 0.42
Co., 1X4
Co., 1X6
3 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-03 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
4 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-04 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
5 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-05 INV 132 8.40 7.2 0.7 0.66 103.8 0.66
Co., 1X4
Co., 1X6
6 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-06 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
7 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-07 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
8 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-08 INV 121 8.40 6.6 0.7 0.61 96.2 0.61
Co., 1X4
Co., 1X6
9 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-09 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
10 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
30
Co., 1X6
11 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-11 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
Co., 1X6
12 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-12 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
13 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-13 INV 46 8.40 2.5 0.7 0.27 42.3 0.27
Co., 1X4
Co., 1X6
14 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-14 INV 110 8.40 6.0 0.7 0.56 88.5 0.56
Co., 1X4
Co., 1X6
15 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-15 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
16 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-16 INV 57 8.40 3.1 0.7 0.32 50.0 0.32
Co., 1X4
Co., 1X6
17 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-17 INV 121 8.40 6.6 0.7 0.61 96.2 0.61
Co., 1X4
Co., 1X6
18 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-18 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
19 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-19 INV 68 8.40 3.7 0.7 0.37 57.6 0.37
Co., 1X4
Co., 1X6
20 560 42.4 13.21 28 15680 1187.2 4.123 6.190 STR-21 INV 132 8.40 7.2 0.7 0.66 103.8 0.66
Co., 1X4

MAXIMUM VOLTAGE DROP PERCENTAGE 0.83 %

COEFFICIENT OF LAYING 1.03

TOTAL POWER LOSS OF LVDC CABLE 41555 W

TOTAL POWER IN TYPICAL INVERTER BLOCK 9690240 W

TOTAL POWER LOSS PERCENTAGE IN TYPICAL INVERTER BLOCK 0.43 %


Part 2

LVDC Circuits Calculation Report (565W)


CONTENT

1. GENERAL

2. INPUT DATA

3. MINIMUM CURRENT CARRYING

4. VOLTAGE DROP & POWER LOSS

5. CONCLUSION

6. REFERENCE

7. ANNEX

A CURRENT-CARRYING CAPACITIES & DERATING FACTORS

B DETAIL CALCULATE OF EACH STRING


1. GENERAL

1.1 Project

SHERABAD 500MW SOLAR POWER PLANT PROJECT


IN UZBEKISTAN

1.2 Purpose

This calculation report is aimed to determine the sizing of LVDC Cable in PV area,

which shall be used between modules and string inverters.

1.3 Methodology

1) Approach method based on IEC 60364-5-52 standards are adopted.

2) The minimum cable sizing shall be based upon a overcurrent rating from
Table 5, IEC 62548:2016.

3) The specified laying conditions, including ground temperature, soil thermal


resistance, groups of circuits, and buried depth of cables would be considered.

4) The worst laying conditions shall be considered for cable derating.

5) Voltage drop and Power loss would be calculated.


2. INPUT DATA

2.1 Electrical Parameters

System frequency = 50 Hz
Voltage level of LVDC cable = DC 1.5 kV

Copper 1Cx6 sqmm solar cable are proposed to be used, and the following
parameters are obtained from IEC 60228:
DC resistance of conductor at 20°C = 3.390 Ω/km
Temperature coefficient of electrical resistivity = 0.00393 1/K
Normal operating temperature of conductor = 75 °C
DC resistance of conductor at 75°C = 4.123 Ω/km

Copper 1Cx4 sqmm solar cable are proposed to be used, and the following
parameters are obtained from IEC 60228:
DC resistance of conductor at 20°C = 5.090 Ω/km
Temperature coefficient of electrical resistivity = 0.00393 1/K
Normal operating temperature of conductor = 75 °C
DC resistance of conductor at 75°C = 6.190 Ω/km

Following parameters are to be considered for Modules:


Module Serie = JW-HD144N
Module Type = BIFACIAL
Peak Power (Pmax) @ STC condition = 565 Wp
MPP Voltage (Vmp) @ STC condition = 42.60 V
MPP Current (Imp) @ STC condition = 13.27 A
Open Circuit Voltage (Voc) = 50.88 V
Short Circuit Current (Isc) = 14.18 A
No. of Modules per string = 28

2.2 Method of installation

Ambient air temperature, air = 45 °C


Ground temperature, soil = 20 °C
Soil thermal resistivity = 1.5 K.m/W
Burried deepth, approx. = 0.8 m
3. MINIMUM CURRENT CARRYING

MAX. MAX.
CURRENT CURRENT CHECK
CASE VOLTAGE CABLE TYPE PERMISSIBLE k1 k2 k3 PERMISSIBLE
Imp STC 1.25ISC STC Iz' > 1.25Imp STC
CURRENT Iz CURRENT Iz'

(kV) (A) (A) (A) (A)

A DC 1.5 CO., 1X6 sqmm 13.27 16.59 53 1.00 1.0 0.45 23.85 YES

B DC 1.5 CO., 1X6 sqmm 13.27 16.59 72 1.00 0.38 27.36 YES

C DC 1.5 CO., 1X4 sqmm 13.27 16.59 57 1.00 1.00 57.00 YES

NOTE:

1. Derating factors k1, k2, k3 are obtained from "Annex A. Current-carrying capacities & derating factors".

I Z'  I Z  k1  k2  k3
k1: derating factor of ambient or ground temperature

k2: derating factor of soil thermal resistivity (NOT for cables in air)

k3: derating factor of grouping circuits

2. Max. permissible current Iz for Copper,1C x 6 sqmm cable are from "Annex A. Current-carrying capacities & derating factors".

3. Worst cases for derating to be considered:

CASE - A: Groups of 6 (six) circuits of DC cable through one single ducts directly burried.

CASE - B: Groups of 20 (twenty) circuits of DC cable lead up to inverter in air.

CASE - C: Single circuit of DC cable connect modules.


4. VOLTAGE DROP & POWER LOSS

1X6 1X4
SINGLE MPP CURRE MODULE TOTAL STRING 1X6,RAC 1X4,RAC 1X6 1X4 % %
CABLE CABLE CABLE POWER
MODULE VOL. NT NO. PER STRING VOL. AT AT FROM TO VOL. VOL. VOL. POWER
TYPE LENGTH LENGTH LOSS
POWER Vmp Imp STRING POWER Ump 75 Deg C 75 Deg C DROP DROP DROP LOSS
(+ & -) (+ & -)
(Wp) (V) (A) (Wp) (V) (Ω/km) (Ω/km) (m) (m) (V) (V) (%) (W) (%)
Co., 1X6
Avg. 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR INV 69 8.40 3.8 0.7 0.38 59.5 0.38
Co., 1X4
Co., 1X6
Max. 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR INV 153 8.40 8.4 0.7 0.76 120.1 0.76
Co., 1X4
Co., 1X6
Min. 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR INV 39 8.40 2.2 0.7 0.24 37.8 0.24
Co., 1X4

MAXIMUM VOLTAGE DROP PERCENTAGE 0.76 %


COEFFICIENT OF LAYING 1.08
TOTAL POWER LOSS OF LVDC CABLE 35289 W
TOTAL POWER IN TYPICAL INVERTER BLOCK 9523640 W
TOTAL POWER LOSS PERCENTAGE IN TYPICAL INVERTER BLOCK 0.40 %

NOTE: Detail caculate for each strings shown in annex B.


5. CONCLUSION

5 Conclusion

The sizing of LVDC Cable between modules and string inverters in PV area

would be selected as copper,1C x 6 sqmm.

The sizing of LVDC Cable connect modules in PV area

would be selected as copper,1C x 4 sqmm.

Also, IEC 62930 are specificed in Contract in this project.

So, this cable would be selected as following type:

- 62930 IEC 131 1500V DC 1x6


6. REFERENCE

1 IEC 60287-1-1, Edition 2.1, Electric cables – Calculation of the current


rating – Part 1-1: Current rating equations (100 % load factor) and
calculation of losses – General

2 IEC 60287-2-1, Edition 2.0, Electric cables – Calculation of the current


rating – Part 2-1: Thermal resistance – Calculation of thermal resistance

IEC 60364-5-52, Edition 3.0, Low-voltage electrical installations – Part 5-


3
52: Selection and erection of electrical equipment – Wiring systems

IEC 60364-5-54, Edition 3.0, Low-voltage electrical installations – Part 5-


4 54: Selection and erection of electrical equipment – Earthing
arrangements and protective conductors

5 IEC 62548, Edition 1.0, Photovoltaic (PV) arrays – Design requirements

6 IEC 62930, Edition 1.0 Electric cables for photovoltaic systems with a
voltage rating of 1,5 kV DC
IEC 60502-1, Edition 2.1, Power cables with extruded insulation and their
7
accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um =
36 kV) – Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV
(Um = 3 6 kV)
8 IEC 60364-7-712, Edition 2.0, Low voltage electrical installations – Part 7-
712: Requirements for special installations or locations – Solar
photovoltaic (PV) power supply systems

9 IEC 60228, Third edition, Conductors of insulated cables


7. ANNEX

7 Annex

A Current-carrying Capacities & Derating Factors

B Detail calculate of each string


ANNEX - A
ANNEX - B

1X6 1X4
SINGLE MPP CURRE MODULE TOTAL STRING 1X6,RAC 1X4,RAC 1X6 1X4 % %
FEEDE CABLE CABLE CABLE POWER
INV NO. MODULE VOL. NT NO. PER STRING VOL. AT AT FROM TO VOL. VOL. VOL. POWER
R NO. TYPE LENGTH LENGTH LOSS
POWER Vmp Imp STRING POWER Ump 75 Deg C 75 Deg C DROP DROP DROP LOSS
(+ & -) (+ & -)
(Wp) (V) (A) (Wp) (V) (Ω/km) (Ω/km) (m) (m) (V) (V) (%) (W) (%)
Co., 1X6
1 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-01 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
2 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-02 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
3 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-03 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
4 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-04 INV 78 8.40 4.3 0.7 0.42 56.6 0.36
Co., 1X4
Co., 1X6
5 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-05 INV 68 8.40 3.7 0.7 0.37 49.0 0.31
Co., 1X4
Co., 1X6
6 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-06 INV 68 8.40 3.7 0.7 0.37 49.0 0.31
Co., 1X4
Co., 1X6
7 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-07 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
01、02、 8 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-08 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
03、04、
Co., 1X6
05、06、 9 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-09 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
07、09、
Co., 1X6
10、11、 10 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
12、13、
Co., 1X6
14、16、 11 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
17、19、
23、24、 Co., 1X6
12 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-12 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
27、28、 Co., 1X4
29、30 Co., 1X6
13 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-13 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
14 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-14 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
15 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-15 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
16 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-16 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
17 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-17 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
18 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-18 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
19 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-19 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
20 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-20 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4

Co., 1X6
1 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-01 INV 153 8.40 8.4 0.7 0.76 120.1 0.76
Co., 1X4
Co., 1X6
2 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-02 INV 142 8.40 7.8 0.7 0.71 112.4 0.71
Co., 1X4
Co., 1X6
3 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-03 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
4 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-04 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
5 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-05 INV 132 8.40 7.2 0.7 0.66 104.8 0.66
Co., 1X4
Co., 1X6
6 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-06 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
7 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-07 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
8 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-08 INV 121 8.40 6.6 0.7 0.61 87.9 0.56
Co., 1X4
Co., 1X6
9 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-09 INV 46 8.40 2.5 0.7 0.27 33.5 0.21
Co., 1X4
Co., 1X6
10 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 33.5 0.21
Co., 1X4
08
Co., 1X6
11 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-11 INV 110 8.40 6.0 0.7 0.56 80.1 0.51
Co., 1X4
Co., 1X6
12 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-12 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
13 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-13 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
14 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-14 INV 110 8.40 6.0 0.7 0.56 89.3 0.56
Co., 1X4
Co., 1X6
15 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-15 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
16 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-16 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
17 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-17 INV 121 8.40 6.6 0.7 0.61 97.1 0.61
Co., 1X4
Co., 1X6
18 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-18 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
19 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-19 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
20 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-20 INV 132 8.40 7.2 0.7 0.66 104.8 0.66
Co., 1X4

Co., 1X6
1 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-01 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
2 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-02 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
3 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-03 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
4 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-04 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
5 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-05 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
6 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-06 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
7 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-07 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
8 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-08 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
9 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-09 INV 110 8.40 6.0 0.7 0.56 89.3 0.56
Co., 1X4
Co., 1X6
10 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
22
Co., 1X6
11 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
12 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-12 INV 121 8.40 6.6 0.7 0.61 97.1 0.61
Co., 1X4
Co., 1X6
13 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-13 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
14 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-14 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
15 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-15 INV 132 8.40 7.2 0.7 0.66 104.8 0.66
Co., 1X4
Co., 1X6
16 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-16 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
17 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-17 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
18 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-18 INV 142 8.40 7.8 0.7 0.71 112.4 0.71
Co., 1X4
Co., 1X6
19 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-19 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
20 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-20 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4

Co., 1X6
1 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-01 INV 96 8.40 5.3 0.7 0.50 79.1 0.50
Co., 1X4
Co., 1X6
2 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-02 INV 96 8.40 5.3 0.7 0.50 79.1 0.50
Co., 1X4
Co., 1X6
3 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-03 INV 86 8.40 4.7 0.7 0.45 71.4 0.45
Co., 1X4
Co., 1X6
4 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-04 INV 86 8.40 4.7 0.7 0.45 71.4 0.45
Co., 1X4
Co., 1X6
5 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-05 INV 75 8.40 4.1 0.7 0.40 63.7 0.40
Co., 1X4
Co., 1X6
6 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-06 INV 75 8.40 4.1 0.7 0.40 63.7 0.40
Co., 1X4
Co., 1X6
7 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-07 INV 65 8.40 3.5 0.7 0.35 56.1 0.35
Co., 1X4
Co., 1X6
8 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-08 INV 65 8.40 3.5 0.7 0.35 56.1 0.35
Co., 1X4
Co., 1X6
9 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-09 INV 54 8.40 3.0 0.7 0.31 48.3 0.31
Co., 1X4
Co., 1X6
10 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-10 INV 54 8.40 3.0 0.7 0.31 48.3 0.31
Co., 1X4
Co., 1X6
20、21 11 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-11 INV 39 8.40 2.2 0.7 0.24 37.8 0.24
Co., 1X4
Co., 1X6
12 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-12 INV 39 8.40 2.2 0.7 0.24 37.8 0.24
Co., 1X4
Co., 1X6
13 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-13 INV 54 8.40 3.0 0.7 0.31 48.3 0.31
Co., 1X4
Co., 1X6
14 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-14 INV 54 8.40 3.0 0.7 0.31 48.3 0.31
Co., 1X4
Co., 1X6
15 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-15 INV 65 8.40 3.5 0.7 0.35 56.1 0.35
Co., 1X4
Co., 1X6
16 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-16 INV 65 8.40 3.5 0.7 0.35 56.1 0.35
Co., 1X4
Co., 1X6
17 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-17 INV 75 8.40 4.1 0.7 0.40 63.7 0.40
Co., 1X4
Co., 1X6
18 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-18 INV 75 8.40 4.1 0.7 0.40 63.7 0.40
Co., 1X4
Co., 1X6
19 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-19 INV 86 8.40 4.7 0.7 0.45 71.4 0.45
Co., 1X4
Co., 1X6
20 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-20 INV 86 8.40 4.7 0.7 0.45 71.4 0.45
Co., 1X4
Co., 1X6
21 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-21 INV 96 8.40 5.3 0.7 0.50 79.1 0.50
Co., 1X4

Co., 1X6
1 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-01 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
2 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-02 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
3 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-03 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
4 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-04 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
5 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-05 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
6 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-06 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
7 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-07 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
8 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-08 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
9 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-09 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
10 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
15
Co., 1X6
11 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
12 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-12 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
13 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-13 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
14 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-14 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
15 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-15 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
16 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-16 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
17 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-17 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
18 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-18 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
19 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-19 INV 99 8.40 5.4 0.7 0.51 81.2 0.51
Co., 1X4
Co., 1X6
20 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-20 INV 110 8.40 6.0 0.7 0.56 88.9 0.56
Co., 1X4

Co., 1X6
1 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-01 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
2 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-02 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
3 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-03 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
4 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-04 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
5 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-05 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
6 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-06 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
7 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-07 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
8 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-08 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
9 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-09 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
10 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
25
Co., 1X6
11 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
12 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-12 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
13 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-13 INV 121 8.40 6.6 0.7 0.61 97.1 0.61
Co., 1X4
Co., 1X6
14 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-14 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
15 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-15 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
16 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-16 INV 132 8.40 7.2 0.7 0.66 104.8 0.66
Co., 1X4
Co., 1X6
17 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-17 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
18 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-18 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
19 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-19 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
20 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-20 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4

Co., 1X6
1 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-01 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
2 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-02 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
3 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-03 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
4 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-04 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
5 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-05 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
6 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-06 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
7 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-07 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
8 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-08 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
9 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-09 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
10 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-10 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
18
Co., 1X6
11 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
12 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-12 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
13 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-13 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
14 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-14 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
15 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-15 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
16 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-16 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
17 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-17 INV 99 8.40 5.4 0.7 0.51 81.2 0.51
Co., 1X4
Co., 1X6
18 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-18 INV 110 8.40 6.0 0.7 0.56 88.9 0.56
Co., 1X4
Co., 1X6
19 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-19 INV 120 8.40 6.6 0.7 0.61 96.6 0.61
Co., 1X4
Co., 1X6
20 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-20 INV 131 8.40 7.2 0.7 0.66 104.3 0.66
Co., 1X4

Co., 1X6
1 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-01 INV 89 8.40 4.8 0.7 0.46 73.5 0.46
Co., 1X4
Co., 1X6
2 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-02 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
3 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-03 INV 78 8.40 4.3 0.7 0.42 65.8 0.42
Co., 1X4
Co., 1X6
4 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-04 INV 142 8.40 7.8 0.7 0.71 112.4 0.71
Co., 1X4
Co., 1X6
5 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-05 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
6 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-06 INV 68 8.40 3.7 0.7 0.37 58.2 0.37
Co., 1X4
Co., 1X6
7 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-07 INV 132 8.40 7.2 0.7 0.66 104.8 0.66
Co., 1X4
Co., 1X6
8 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-08 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
9 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-09 INV 57 8.40 3.1 0.7 0.32 50.5 0.32
Co., 1X4
Co., 1X6
10 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-10 INV 121 8.40 6.6 0.7 0.61 97.1 0.61
Co., 1X4
26
Co., 1X6
11 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-11 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
12 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-12 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
13 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-13 INV 110 8.40 6.0 0.7 0.56 89.3 0.56
Co., 1X4
Co., 1X6
14 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-14 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
15 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-15 INV 46 8.40 2.5 0.7 0.27 42.7 0.27
Co., 1X4
Co., 1X6
16 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-16 INV 110 8.40 6.0 0.7 0.56 89.3 0.56
Co., 1X4
Co., 1X6
17 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-17 INV 73 8.40 4.0 0.7 0.39 62.1 0.39
Co., 1X4
Co., 1X6
18 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-18 INV 73 8.40 4.0 0.7 0.39 62.1 0.39
Co., 1X4
Co., 1X6
19 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-19 INV 84 8.40 4.6 0.7 0.44 69.8 0.44
Co., 1X4
Co., 1X6
20 565 42.6 13.27 28 15820 1192.8 4.123 6.190 STR-20 INV 84 8.40 4.6 0.7 0.44 69.8 0.44
Co., 1X4

MAXIMUM VOLTAGE DROP PERCENTAGE 0.76 %

COEFFICIENT OF LAYING 1.08

TOTAL POWER LOSS OF LVDC CABLE 35289 W

TOTAL POWER IN TYPICAL INVERTER BLOCK 9523640 W

TOTAL POWER LOSS PERCENTAGE IN TYPICAL INVERTER BLOCK 0.40 %


Part 3

LVAC Circuits Calculation Report (560W)


CONTENT

1. GENERAL

2. INPUT DATA

3. SHORT-CIRCUIT PROTECTION CHECK

4. PERMISSIBLE CURRENT CARRYING CAPACITIES

5. VOLTAGE DROP & POWER LOSS CALCULATION

6. MAX.VOLTAGE DROP

7. CONCLUSION

8. REFERENCE

9. ANNEX

A CURRENT-CARRYING CAPACITIES & DERATING FACTORS


1. GENERAL

1.1 Project

SHERABAD 500MW SOLAR POWER PLANT PROJECT


IN UZBEKISTAN

1.2 Purpose

This calculation report is aimed to determine the sizing of LVAC Cable in PV area.

which shall be used between string inverters and MV transformers.

1.3 Methodology

1) Approach method based on IEC 60364-5-52 standards are adopted.

2) The specified laying conditions, including ground temperature, soil thermal


resistance, groups of circuits, and buried depth of cables would be considered.

3) The worst laying conditions shall be considered for cable derating.

4) Overcurrent protection equipment would be considered for cable selection.

5) Short circuit capability and maximum permissible voltage drop shall be checked.

6) Cable electrical parameters need to be submitted by manufacturer.

7) LVAC Cable length are estimated on the current layout drawings.


2. INPUT DATA

2.1 Electrical Parameters

System frequency = 50 Hz
Voltage level = 0.8 kV

Aluminium 3Cx300 sqmm XPLE cable are proposed to be used, and the following
parameters are obtained from IEC 60228:

DC resistance of conductor at 20°C = 0.1 Ω/km


Maximum operating temperature of conductor = 90 °C
Normal operating temperature of conductor = 75 °C
Maximum fault temperature of conductor, for XLPE = 250 °C
Temperature coefficient of electrical resistivity = 0.00403 1/K
DC resistance of conductor at 90°C = 0.128 Ω/km
DC resistance of conductor at Normal operating
= 0.122165 Ω/km
temperature(75°C)
AC resistance of conductor at Normal operating
= 0.123 Ω/km
temperature(75°C)

Capacity of inverter (Sungrow SG350HX):


- @30°C = 350 kVA
- @43°C = 312.00 kVA
Maximum AC output current = 252.6 A
Nominal AC output current = 225.2 A

2.2 Method of installation

Method of installation, as per IEC 60364-5-52 = Method D1

Cable cores = Three-core


Ambient air temperature, air = 43 °C
Ground temperature, soil = 20 °C
Covered Sand thermal resistivity = 2.5 K.m/W
Number of circuits laying in groups = 2 layer x 4
Depth of laying, to cable axis or centre of trefoil = 0.8 m
Distance between cables = 0.4 m
3. SHORT-CIRCUIT PROTECTION CHECK

3.1 Short Circuit Currents

In a simplified approach, the impedance of the MV system is assumed to be

negligibly small, so that the maximum short circuit current from inverter to

MV transformer:

Isc = In*100/Usc

= S/1.732/U*100/Ud

= 4.7/1.732/0.8*100/9.5 = 35.6 kA

where,

S capcity of MV transformer, split winding = 4.688 MVA

U LV side voltage of MV transformer = 0.8 kV

Ud impedance voltage of the transformer in % = 9.5%

3.2 Short Circuit Capability

where,

= 94.5 °C

initial temperature of conductor = 90 °C

final temperature of conductor = 250 °C

reciprocal of temperature coefficient of resistivity at 0 °C = 228 °C


for the conductor, as per Table A.54.1, IEC 60364-5-54

as per Table A.54.1, IEC 60364-5-54 = 148

operating time in seconds of the protective device = 0.6 s


for automatic disconnection, it would be used here as
instantaneous time from Tripping Curve of MCCB

so that:

the minimum cross-sectional area = 292 mm2


4. PERMISSIBLE CURRENT CARRYING CAPACITIES

Load MAX. MAX. MAX.


MAX. LOAD CYCLIC
VOLTAG CABLE MAX. switch or PERMISSIB PERMISSIBL PERMISSIBL CHECK
CASE CURRENT k1 k2 k3 k4 FACTOR
E TYPE LOAD MCCB LE E CURRENT E CURRENT Iz' > Ib
Ib SM
In CURRENT Iz' Iz''
(kV) (kVA) (A) (A) (A)
A - In AL., 3C x
buried 0.8 300 312.00 225 260 286 1.00 1.10 0.66 1.0 208 1.70 353 YES
duct sqmm
AL., 3C x
B - Directly
0.8 300 312.00 225 260 326 1.00 1.00 0.66 1.0 215 1.70 366 YES
buried
sqmm

NOTE:

1. Derating factors k1, k2, k3, k4 are obtained from "Annex A. Current-carrying capacities & derating factors".

I Z'  I Z  k1  k2  k3  k4 I Z''  I Z'  M

k1: derating factor of ground temperature

k2: derating factor of soil thermal resistivity

k3: derating factor of grouping circuits

k4: derating factor of buried depth

M: cyclic factor are obtained from CYMCAP Results

2. Max. permissible current Iz for XLPE, AL.,3C x 300 sqmm, 1.8/3kV cable are from "Annex A. Current-carrying capacities & derating factors".

which shall be reviewed and checked by manufacture.


5. VOLTAGE DROP & POWER LOSS CALCULATION

MAX.
FEEDER MAX. RAC AT CABLE POWER % POWER
VOLTAGE CABLE TYPE LOAD FROM TO COS φ
NO. LOAD 75 Deg C LENGTH LOSS LOSS
CURRENT

(kV) (kVA) (A) (Ω/km) (m) (kVA) (%)


1 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-01 MV TR 297 1.00 5.52 1.771
2 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-02 MV TR 258 1.00 4.80 1.539
3 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-03 MV TR 220 1.00 4.08 1.308
4 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-04 MV TR 182 1.00 3.38 1.083
5 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-05 MV TR 143 1.00 2.66 0.851
6 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-06 MV TR 110 1.00 2.05 0.658
7 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-07 MV TR 125 1.00 2.32 0.745
8 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-08 MV TR 165 1.00 3.07 0.983
9 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-09 MV TR 204 1.00 3.79 1.214
10 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-10 MV TR 242 1.00 4.49 1.439
11 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-11 MV TR 281 1.00 5.21 1.671
12 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-12 MV TR 228 1.00 4.24 1.358
13 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-13 MV TR 172 1.00 3.20 1.026
14 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-14 MV TR 114 1.00 2.11 0.676
15 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-15 MV TR 59 1.00 1.10 0.351
16 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-16 MV TR 68 1.00 1.27 0.407
17 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-17 MV TR 124 1.00 2.31 0.739
18 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-18 MV TR 174 1.00 3.24 1.039
19 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-19 MV TR 222 1.00 4.12 1.320
20 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-20 MV TR 242 1.00 4.49 1.439
21 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-21 MV TR 202 1.00 3.75 1.202
22 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-22 MV TR 163 1.00 3.03 0.970
23 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-23 MV TR 125 1.00 2.32 0.745
24 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-24 MV TR 85 1.00 1.58 0.507
25 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-25 MV TR 63 1.00 1.17 0.376
26 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-26 MV TR 73 1.00 1.35 0.432
27 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-27 MV TR 113 1.00 2.09 0.670
28 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-28 MV TR 151 1.00 2.81 0.901
29 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-29 MV TR 230 1.00 4.28 1.370
30 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-30 MV TR 235 1.00 4.37 1.402

Avg. 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV MV TR 169 1.00 3.14 1.006
Max. 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV MV TR 297 1.00 5.52 1.771
Min. 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV MV TR 59 1.00 1.10 0.351
TOTAL POWER LOSS OF LVAC CABLE 94 kVA
TOTAL POWER IN TYPICAL P TYPE BLOCK 9360 kVA
COEFFICIENT OF ANOMALY 1.13
TOTAL POWER LOSS PERCENTAGE 1.14%

NOTE: Typical PV block are considered for estimation.


5. VOLTAGE DROP & POWER LOSS CALCULATION

MAX.
FEEDER MAX. RAC AT CABLE POWER % POWER
VOLTAGE CABLE TYPE LOAD FROM TO COS φ
NO. LOAD 75 Deg C LENGTH LOSS LOSS
CURRENT

(kV) (kVA) (A) (Ω/km) (m) (kVA) (%)


1 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-01 MV TR 297 1.00 5.37 1.745
2 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-02 MV TR 258 1.00 4.67 1.517
3 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-03 MV TR 220 1.00 3.96 1.289
4 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-04 MV TR 182 1.00 3.28 1.067
5 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-05 MV TR 143 1.00 2.58 0.839
6 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-06 MV TR 110 1.00 1.99 0.648
7 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-07 MV TR 125 1.00 2.26 0.734
8 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-08 MV TR 165 1.00 2.98 0.969
9 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-09 MV TR 204 1.00 3.68 1.197
10 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-10 MV TR 242 1.00 4.36 1.418
11 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-11 MV TR 281 1.00 5.06 1.647
12 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-12 MV TR 228 1.00 4.12 1.338
13 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-13 MV TR 172 1.00 3.11 1.012
14 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-14 MV TR 114 1.00 2.05 0.667
15 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-15 MV TR 59 1.00 1.06 0.346
16 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-16 MV TR 68 1.00 1.23 0.402
17 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-17 MV TR 124 1.00 2.24 0.728
18 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-18 MV TR 174 1.00 3.15 1.024
19 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-19 MV TR 222 1.00 4.00 1.301
20 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-20 MV TR 242 1.00 4.36 1.418
21 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-21 MV TR 202 1.00 3.64 1.184
22 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-22 MV TR 163 1.00 2.94 0.956
23 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-23 MV TR 125 1.00 2.26 0.734
24 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-24 MV TR 85 1.00 1.54 0.500
25 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-25 MV TR 63 1.00 1.14 0.371
26 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-26 MV TR 73 1.00 1.31 0.426
27 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-27 MV TR 113 1.00 2.03 0.660
28 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-28 MV TR 151 1.00 2.73 0.888
29 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-29 MV TR 230 1.00 4.15 1.351
30 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV-30 MV TR 235 1.00 4.25 1.382

Avg. 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV MV TR 169 1.00 3.05 0.992
Max. 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV MV TR 297 1.00 5.37 1.745
Min. 0.8 AL., 3C x 300 sqmm 307.50 221.9 0.122 INV MV TR 59 1.00 1.06 0.346
TOTAL POWER LOSS OF LVAC CABLE 92 kVA
TOTAL POWER IN TYPICAL P TYPE BLOCK 9360 kVA
COEFFICIENT OF ANOMALY 1.13
TOTAL POWER LOSS PERCENTAGE 1.10%

NOTE: Typical PV block are considered for estimation.


6. MAX.VOLTAGE DROP

%
MAX.
CASE MAX. RAC AT LIMIT CABLE VOLTAG VOLTA
VOLTAGE CABLE TYPE LOAD COS φ
NO. LOAD 75 Deg C LENGTH E DROP GE
CURRENT
DROP
(kV) (mm2) (kVA) (A) (Ω/km) (m) (V) (%)
1 0.8 AL., 3C x 300 312.00 225.2 0.117 420 1.00 24.0 3.0%

NOTE:

1. Voltage drop:

2. The length range from the inverters to MV transformer has been considered from voltage drop.

3. Power factor are assumed to be 1.0.

4. The maximum % voltage drop is considered less than 3% normally, refer to Table G.52.1, IEC 60364-5-52
7. CONCLUSION

7 Conclusion

The sizing of LVAC Cable between inverters to MV transformers in PV area

would be selected as follows:

XLPE, AL.,3C x 300 sqmm, 1.8/3kV

The maximum length of the LVAC cable should not exceed 420m.
8. REFERENCE

1 IEC 60287-1-1, Edition 2.1, Electric cables – Calculation of the current


rating – Part 1-1: Current rating equations (100 % load factor) and
calculation of losses – General

2 IEC 60287-2-1, Edition 2.0, Electric cables – Calculation of the current


rating – Part 2-1: Thermal resistance – Calculation of thermal resistance

IEC 60364-5-52, Edition 3.0, Low-voltage electrical installations – Part 5-


3
52: Selection and erection of electrical equipment – Wiring systems

IEC 60364-5-54, Edition 3.0, Low-voltage electrical installations – Part 5-


4 54: Selection and erection of electrical equipment – Earthing
arrangements and protective conductors

5 IEC 62548, Edition 1.0, Photovoltaic (PV) arrays – Design requirements


IEC 60502-1, Edition 2.1, Power cables with extruded insulation and their
6
accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um =
36 kV) – Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV
(Um = 3 6 kV)
7 IEC 60364-7-712, Edition 2.0, Low voltage electrical installations – Part 7-
712: Requirements for special installations or locations – Solar
photovoltaic (PV) power supply systems

8 IEC 60228, Third edition, Conductors of insulated cables

IEC 60853-1, First Edition, Calculation of the cyclic and emergency


9
current rating of cables
9. ANNEX

9 Annex

A Current-carrying capacities & derating factors


ANNEX - A
Note: as per Table B.52.5, IEC 60364-5-52
Note: as per Table B.52.18, IEC 60364-5-52
Note: as per Table B.12, IEC 60502-2, for reference
Part 4

LVAC Circuits Calculation Report (565W)


CONTENT

1. GENERAL

2. INPUT DATA

3. SHORT-CIRCUIT PROTECTION CHECK

4. PERMISSIBLE CURRENT CARRYING CAPACITIES

5. VOLTAGE DROP & POWER LOSS CALCULATION

6. MAX.VOLTAGE DROP

7. CONCLUSION

8. REFERENCE

9. ANNEX

A CURRENT-CARRYING CAPACITIES & DERATING FACTORS


1. GENERAL

1.1 Project

SHERABAD 500MW SOLAR POWER PLANT PROJECT


IN UZBEKISTAN

1.2 Purpose

This calculation report is aimed to determine the sizing of LVAC Cable in PV area.

which shall be used between string inverters and MV transformers.

1.3 Methodology

1) Approach method based on IEC 60364-5-52 standards are adopted.

2) The specified laying conditions, including ground temperature, soil thermal


resistance, groups of circuits, and buried depth of cables would be considered.

3) The worst laying conditions shall be considered for cable derating.

4) Overcurrent protection equipment would be considered for cable selection.

5) Short circuit capability and maximum permissible voltage drop shall be checked.

6) Cable electrical parameters need to be submitted by manufacturer.

7) LVAC Cable length are estimated on the current layout drawings.


2. INPUT DATA

2.1 Electrical Parameters

System frequency = 50 Hz
Voltage level = 0.8 kV

Aluminium 3Cx300 sqmm XPLE cable are proposed to be used, and the following
parameters are obtained from IEC 60228:

DC resistance of conductor at 20°C = 0.1 Ω/km


Maximum operating temperature of conductor = 90 °C
Normal operating temperature of conductor = 75 °C
Maximum fault temperature of conductor, for XLPE = 250 °C
Temperature coefficient of electrical resistivity = 0.00403 1/K
DC resistance of conductor at 90°C = 0.128 Ω/km
DC resistance of conductor at Normal operating
= 0.122165 Ω/km
temperature(75°C)
AC resistance of conductor at Normal operating
= 0.123 Ω/km
temperature(75°C)

Capacity of inverter (Sungrow SG350HX):


- @30°C = 350 kVA
- @43°C = 312.00 kVA
Maximum AC output current = 252.6 A
Nominal AC output current = 225.2 A

2.2 Method of installation

Method of installation, as per IEC 60364-5-52 = Method D1

Cable cores = Three-core


Ambient air temperature, air = 43 °C
Ground temperature, soil = 20 °C
Covered Sand thermal resistivity = 2.5 K.m/W
Number of circuits laying in groups = 2 layer x 4
Depth of laying, to cable axis or centre of trefoil = 0.8 m
Distance between cables = 0.4 m
3. SHORT-CIRCUIT PROTECTION CHECK

3.1 Short Circuit Currents

In a simplified approach, the impedance of the MV system is assumed to be

negligibly small, so that the maximum short circuit current from inverter to

MV transformer:

Isc = In*100/Usc

= S/1.732/U*100/Ud

= 4.7/1.732/0.8*100/9.5 = 35.6 kA

where,

S capcity of MV transformer, split winding = 4.688 MVA

U LV side voltage of MV transformer = 0.8 kV

Ud impedance voltage of the transformer in % = 9.5%

3.2 Short Circuit Capability

where,

= 94.5 °C

initial temperature of conductor = 90 °C

final temperature of conductor = 250 °C

reciprocal of temperature coefficient of resistivity at 0 °C = 228 °C


for the conductor, as per Table A.54.1, IEC 60364-5-54

as per Table A.54.1, IEC 60364-5-54 = 148

operating time in seconds of the protective device = 0.6 s


for automatic disconnection, it would be used here as
instantaneous time from Tripping Curve of MCCB

so that:

the minimum cross-sectional area = 292 mm2


4. PERMISSIBLE CURRENT CARRYING CAPACITIES

Load MAX. MAX. MAX.


MAX. LOAD CYCLIC
VOLTAG CABLE MAX. switch or PERMISSIB PERMISSIBL PERMISSIBL CHECK
CASE CURRENT k1 k2 k3 k4 FACTOR
E TYPE LOAD MCCB LE E CURRENT E CURRENT Iz' > Ib
Ib SM
In CURRENT Iz' Iz''
(kV) (kVA) (A) (A) (A)
A - In AL., 3C x
buried 0.8 300 312.00 225 260 286 1.00 1.10 0.66 1.0 208 1.70 353 YES
duct sqmm
AL., 3C x
B - Directly
0.8 300 312.00 225 260 326 1.00 1.00 0.66 1.0 215 1.70 366 YES
buried
sqmm

NOTE:

1. Derating factors k1, k2, k3, k4 are obtained from "Annex A. Current-carrying capacities & derating factors".

I Z'  I Z  k1  k2  k3  k4 I Z''  I Z'  M

k1: derating factor of ground temperature

k2: derating factor of soil thermal resistivity

k3: derating factor of grouping circuits

k4: derating factor of buried depth

M: cyclic factor are obtained from CYMCAP Results

2. Max. permissible current Iz for XLPE, AL.,3C x 300 sqmm, 1.8/3kV cable are from "Annex A. Current-carrying capacities & derating factors".

which shall be reviewed and checked by manufacture.


5. VOLTAGE DROP & POWER LOSS CALCULATION

MAX.
FEEDER MAX. RAC AT CABLE POWER % POWER
VOLTAGE CABLE TYPE LOAD FROM TO COS φ
NO. LOAD 75 Deg C LENGTH LOSS LOSS
CURRENT

(kV) (kVA) (A) (Ω/km) (m) (kVA) (%)


1 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-01 MV TR 300 1.00 5.58 1.789
2 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-02 MV TR 245 1.00 4.55 1.458
3 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-03 MV TR 189 1.00 3.51 1.127
4 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-04 MV TR 141 1.00 2.62 0.839
5 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-05 MV TR 195 1.00 3.63 1.164
6 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-06 MV TR 252 1.00 4.69 1.502
7 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-07 MV TR 308 1.00 5.72 1.833
8 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-08 MV TR 350 1.00 6.50 2.083
9 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-09 MV TR 233 1.00 4.33 1.389
10 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-10 MV TR 178 1.00 3.30 1.058
11 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-11 MV TR 122 1.00 2.27 0.726
12 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-12 MV TR 71 1.00 1.31 0.420
13 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-13 MV TR 121 1.00 2.25 0.720
14 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-14 MV TR 176 1.00 3.26 1.045
15 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-15 MV TR 231 1.00 4.30 1.377
16 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-16 MV TR 180 1.00 3.34 1.070
17 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-17 MV TR 124 1.00 2.31 0.739
18 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-18 MV TR 67 1.00 1.25 0.401
19 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-19 MV TR 50 1.00 0.92 0.295
20 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-20 MV TR 105 1.00 1.95 0.626
21 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-21 MV TR 167 1.00 3.11 0.995
22 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-22 MV TR 223 1.00 4.14 1.327
23 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-23 MV TR 236 1.00 4.39 1.408
24 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-24 MV TR 180 1.00 3.34 1.070
25 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-25 MV TR 124 1.00 2.31 0.739
26 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-26 MV TR 120 1.00 2.23 0.714
27 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-27 MV TR 126 1.00 2.34 0.751
28 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-28 MV TR 176 1.00 3.26 1.045
29 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-29 MV TR 231 1.00 4.30 1.377
30 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV-30 MV TR 287 1.00 5.33 1.708

Avg. 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV MV TR 184 1.00 3.41 1.093
Max. 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV MV TR 350 1.00 6.50 2.083
Min. 0.8 AL., 3C x 300 sqmm 312.00 225.2 0.122 INV MV TR 50 1.00 0.92 0.295
TOTAL POWER LOSS OF LVAC CABLE 102 kVA
TOTAL POWER IN TYPICAL P TYPE BLOCK 9360 kVA
COEFFICIENT OF ANOMALY 1.13
TOTAL POWER LOSS PERCENTAGE 1.24%

NOTE: Typical PV block are considered for estimation.


6. MAX.VOLTAGE DROP

%
MAX.
CASE MAX. RAC AT LIMIT CABLE VOLTAG VOLTA
VOLTAGE CABLE TYPE LOAD COS φ
NO. LOAD 75 Deg C LENGTH E DROP GE
CURRENT
DROP
(kV) (mm2) (kVA) (A) (Ω/km) (m) (V) (%)
1 0.8 AL., 3C x 300 307.50 221.9 0.117 426 1.00 24.0 3.0%

NOTE:

1. Voltage drop:

2. The length range from the inverters to MV transformer has been considered from voltage drop.

3. Power factor are assumed to be 1.0.

4. The maximum % voltage drop is considered less than 3% normally, refer to Table G.52.1, IEC 60364-5-52
7. CONCLUSION

7 Conclusion

The sizing of LVAC Cable between inverters to MV transformers in PV area

would be selected as follows:

XLPE, AL.,3C x 300 sqmm, 1.8/3kV

The maximum length of the LVAC cable should not exceed 426m.
8. REFERENCE

1 IEC 60287-1-1, Edition 2.1, Electric cables – Calculation of the current


rating – Part 1-1: Current rating equations (100 % load factor) and
calculation of losses – General

2 IEC 60287-2-1, Edition 2.0, Electric cables – Calculation of the current


rating – Part 2-1: Thermal resistance – Calculation of thermal resistance

IEC 60364-5-52, Edition 3.0, Low-voltage electrical installations – Part 5-


3
52: Selection and erection of electrical equipment – Wiring systems

IEC 60364-5-54, Edition 3.0, Low-voltage electrical installations – Part 5-


4 54: Selection and erection of electrical equipment – Earthing
arrangements and protective conductors

5 IEC 62548, Edition 1.0, Photovoltaic (PV) arrays – Design requirements


IEC 60502-1, Edition 2.1, Power cables with extruded insulation and their
6
accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um =
36 kV) – Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV
(Um = 3 6 kV)
7 IEC 60364-7-712, Edition 2.0, Low voltage electrical installations – Part 7-
712: Requirements for special installations or locations – Solar
photovoltaic (PV) power supply systems

8 IEC 60228, Third edition, Conductors of insulated cables

IEC 60853-1, First Edition, Calculation of the cyclic and emergency


9
current rating of cables
9. ANNEX

9 Annex

A Current-carrying capacities & derating factors


ANNEX - A
Note: as per Table B.52.5, IEC 60364-5-52
Note: as per Table B.52.18, IEC 60364-5-52
Note: as per Table B.12, IEC 60502-2, for reference
Part 5

MV Circuits Calculation Report


CONTENT

1. GENERAL

2. INPUT DATA

3. CURRENT CARRYING CAPACITIES (100% LOAD FACTOR)

4. SHORT-CIRCUIT CAPABILITY CHECK

5. MAXIMUM VOLTAGE DROP CALCULATION

6. POWER LOSS CALCULATION

7. CONCLUSION

8. REFERENCE

9. ANNEX

A CURRENT-CARRYING CAPACITIES & DERATING FACTORS


1. GENERAL

1.1 Project

SHERABAD 500MW SOLAR POWER PLANT PROJECT


IN UZBEKISTAN

1.2 Purpose

This calculation report is aimed to determine the sizing of MV Cable in PV area.

which shall be used between MV transformers and step-up substations.

1.3 Methodology

1) Theoretical methods based on IEC 60502-2 and IEC 60287 standards are adopted.

2) Continuous current carrying capacity under the specified laying conditions,


including ambient temperature, buried depth, soil thermal resistance, laying shape,
and groups of circuits shall be considered.

3) The worst laying conditions shall be considered for cable derating.

4) Short circuit capability and maximum permissible voltage drop shall be checked.

5) Cable structure parameters are provided by manufacturer.

6) MV Cable length are referenced on 35kV cable lying drawings.


2. INPUT DATA

2.1 Electrical Parameters

System frequency = 50 Hz
Voltage level = 35 kV
Voltage to earth = 18000 V
Maximum operating temperature of conductor = 90 °C
Maximum fault temperature of conductor = 250 °C

Capacity of single MV transformer = 9375 kVA


Maximum load current of circuit per one MV transformer = 164.0 A
Maximum load current of circuit per two MV transformers = 328.0 A

2.3 Method of installation

Method of installation = In a buried duct

Ambient air temperature, air = 43 °C


Ambient temperature, soil = 20 °C
Covered Sand thermal resistivity = 2.5 K.m/W
Number of circuits laying in groups
- for main circuit (max.) = 2 layer x 4
- for branch circuits (max.) = 8
Depth of laying, to cable axis or centre of trefoil = 0.8 m
Distance between circuits (outer to outer) = 0.4 m
3. CURRENT CARRYING CAPACITIES (100% LOAD FACTOR)

MAX.
MAX. MAX. MAX.
CYCLIC PERMISSI
CABLE MAX. LOAD PERMI. PERMI. CHECK
CASE VOLTAGE k1 k2 k3 k4 FACTOR BLE
TYPE LOAD CURRENT CURRENT CURRENT Iz'' > Ib
SM CURRENT
Ib Iz Iz'
Iz''
(kV) (kVA) (A) (A)
A - In AL., 3C x
35 9375 154.7 231 1.00 1.00 0.67 1.0 154.8 1.70 263 YES
buried duct 150 sqmm
B - Directly AL., 3C x
35 9375 154.7 259 1.00 0.83 0.67 1.0 144.0 1.70 245 YES
buried 150 sqmm
C - In AL., 3C x
35 18750 309.3 393 1.00 1.00 0.67 1.0 263.3 1.70 448 YES
buried duct 400 sqmm
D - Directly AL., 3C x
35 18750 309.3 432 1.00 0.82 0.67 1.0 237.3 1.70 403 YES
buried 400 sqmm
NOTE:

1. Derating factors k1, k2, k3, k4 are from "Annex A. Current-carrying capacities & derating factors".
𝐼 𝐼 ⋅𝑘 ⋅𝑘 ⋅𝑘 ⋅𝑘 I Z''  I Z'  M
k1: derating factor of ground temperature

k2: derating factor of soil thermal resistivity

k3: derating factor of grouping circuits

k4: derating factor of buried depth

M: cyclic factor are obtained from CYMCAP Results

2. Max. permissible current Iz for MV cable are from "Annex A. Current-carrying capacities & derating factors" and Reports by
4. SHORT-CIRCUIT CAPABILITY CHECK

4.1 Short Circuit Currents

The short circuit currents has been calculated by Juru in report.

The maximum short circuit current between pannels are as following:

- from SS FEEDER to RMU A Pannel = 16 kA

- from RMU A Pannel to RMU B Pannel = 16 kA

Duration time of fault current = 0.72 s

4.2 Short Circuit Capability

The permissible short-circuit current:

Factor to allow for heat loss into the adjacent components = 1


for adiabatic calculations (conservative method)

The form of the adiabatic temperature rise formula is given by IEC 949:

where,

Final conductor temperature after the fault = 250 °C

Initial conductor temperature before the fault = 90 °C

Constant depending on the conductor material = 148


for Aluminium, as per Table I, IEC 949

Reciprocal of temperature coefficient of resistance at 0 °C = 228 K


for Aluminium, as per Table I, IEC 949

4.3 Results

For the three types of MV cable between different sections,


the minimum cross-sections S :

- from S/S Main Pannel to RMU A Pannel > 144 Sqmm

- from RMU A Pannel to RMU B Pannel > 144 Sqmm


5. MAXIMUM VOLTAGE DROP CALCULATION

MAX.
FEEDER MAX. MAX. ZAC AT VOLTAGE % VOLTAGE
VOLTAGE CABLE TYPE FROM TO CABLE COS φ
NO. LOAD CURRENT 75 Deg C DROP DROP
LENGTH

(kV) (kVA) (A) (Ω/km) (m) (V) (%)

16 35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-16 SS-FEEDER 4582 1.00 165.8 0.82

18 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-13 SS-FEEDER 3766 1.00 102.5 0.51

NOTE:

1. The maximum cable length for different cross sections has been considered.

2. Power factor are assumed to be 1.0.

3. The maximum % voltage drop is less than 5%, and fulfill the requirements.
6. POWER LOSS CALCULATION

FEEDER MAX. MAX. RAC AT CABLE POWER % POWER


VOLTAGE CABLE TYPE FROM TO COS φ
NO. LOAD CURRENT 75 Deg C LENGTH LOSS LOSS

(kV) (kVA) (A) (Ω/km) (m) (kVA) (%)


1 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-03 SS FEEDER 2679 1.0 67.66 0.361
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-01 RMU-03 1224 1.0 20.55 0.219
2 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-04 SS FEEDER 2963 1.0 74.84 0.399
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-05 RMU-04 420 1.0 7.05 0.075
3 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-06 SS FEEDER 1858 1.0 46.93 0.250
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-02 RMU-06 884 1.0 14.84 0.158
4 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-07 SS FEEDER 2118 1.0 53.49 0.285
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-08 RMU-07 320 1.0 5.37 0.057
5 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-09 SS FEEDER 2660 1.0 67.18 0.358
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-10 RMU-09 320 1.0 5.37 0.057
6 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-11 SS FEEDER 3203 1.0 80.90 0.431
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-12 RMU-11 320 1.0 5.37 0.057
7 35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-15 SS FEEDER 4289 1.0 72.01 0.768
8 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-13 SS FEEDER 3766 1.0 95.12 0.507
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-14 RMU-13 320 1.0 5.37 0.057
9 35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-16 SS FEEDER 4582 1.0 76.93 0.821
10 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-17 SS FEEDER 1557 1.0 39.32 0.210
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-18 RMU-17 319 1.0 5.36 0.057
11 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-19 SS FEEDER 2099 1.0 53.01 0.283
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-20 RMU-19 321 1.0 5.39 0.057
12 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-21 SS FEEDER 2641 1.0 66.70 0.356
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-22 RMU-21 321 1.0 5.39 0.057
13 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-27 SS FEEDER 950 1.0 23.99 0.128
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-28 RMU-27 319 1.0 5.36 0.057
14 35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-29 SS FEEDER 1503 1.0 25.24 0.269
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-30 RMU-29 320 1.0 5.37 0.057
15 35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-24 SS FEEDER 3443 1.0 57.81 0.617
16 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-39 SS FEEDER 1061 1.0 26.80 0.143
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-40 RMU-39 288 1.0 4.84 0.052
17 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-25 SS FEEDER 3713 1.0 93.78 0.500
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-26 RMU-25 320 1.0 5.37 0.057
18 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-31 SS FEEDER 1921 1.0 48.52 0.259
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-32 RMU-31 321 1.0 5.39 0.057
19 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-33 SS FEEDER 2568 1.0 64.86 0.346
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-34 RMU-33 253 1.0 4.25 0.045
20 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-35 SS FEEDER 3111 1.0 78.57 0.419
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-36 RMU-35 455 1.0 7.64 0.081
21 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-37 SS FEEDER 519 1.0 13.11 0.070
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-38 RMU-37 320 1.0 5.37 0.057
22 35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-23 SS FEEDER 3087 1.0 51.83 0.553
23 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-41 SS FEEDER 1867 1.0 47.15 0.251
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-42 RMU-41 791 1.0 13.28 0.142
24 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-43 SS FEEDER 493 1.0 12.45 0.066
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-44 RMU-43 458 1.0 7.69 0.082
25 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-45 SS FEEDER 1296 1.0 32.73 0.175
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-46 RMU-45 1133 1.0 19.02 0.203
26 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-47 SS FEEDER 1153 1.0 29.12 0.155
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-52 RMU-47 1055 1.0 17.71 0.189
27 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-48 SS FEEDER 1424 1.0 35.97 0.192
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-49 RMU-48 322 1.0 5.41 0.058
28 35 AL., 3C x 400 sqmm 18750 309.3 0.0880 RMU-50 SS FEEDER 1957 1.0 49.43 0.264
35 AL., 3C x 150 sqmm 9375 154.7 0.2340 RMU-51 RMU-50 397 1.0 6.67 0.071

TOTAL POWER LOSS OF MV CABLE 1679 kVA

TOTAL POWER IN PV PLANT 487500 kVA

TOTAL POWER LOSS PERCENTAGE 0.34 %


7. CONCLUSION

7 Conclusion

The MV Cable in PV area would be selected as follows:

- from S/S FEEDER to RMU A Pannel : XLPE, 18/30(36) kV, 3C x 400 Sqmm

- from RMU A Panel to RMU B Pannel : XLPE, 18/30(36) kV, 3C x 150 Sqmm
8. REFERENCE

1 IEC 60287-1-1, Edition 2.1, Electric cables – Calculation of the current


rating – Part 1-1: Current rating equations (100 % load factor) and
calculation of losses – General

2 IEC 60287-2-1, Edition 2.0, Electric cables – Calculation of the current


rating – Part 2-1: Thermal resistance – Calculation of thermal resistance

3 IEC 60853-1, First Edition, Calculation of the cyclic and emergency


current rating of cables

4 IEC 60502-2, Edition 3.0, Power cables with extruded insulation and their
accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um =
36 kV) – Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to
30 kV (Um = 36 kV)

5 IEC 60949, First edition, Calculation of thermally permissible short-circuit


currents, taking into account non-adiabatic heating effects

6 IEC 60228, Third edition, Conductors of insulated cables


9. ANNEX

9 Annex

A Current-carrying Capacities & Derating Factors


ANNEX - A
Part 6

LVDC, LVAC and MV Circuits Calculation


Report(By CYMCAP)
Study Summary
CYMCAP Version 7.2 Revision 3

Study: HANHE1

Execution: HANHE1

Date: 2023/9/27 13:17:32

General Simulation Data


Steady State Option Equally Loaded

Consider Electrical interaction between circuits No

Induced currents in metallic layers as a fraction of conductor current (applied to all single phase circuits) : 0.0

Conductor Resistances Computation Option: IEC-228

Installation Type:Ductbank
Ambient Soil Temperature at Installation Depth [°C] 20.0

Native Soil Thermal Resistivity [K.m/W] 1.5

Cyclic Loading Option IEC 60853

Thermal Resistivity of Duct Bank [K.m/W] 1.0

Depth of Center of Duct Bank [m] 0.87

Duct Bank Width [m] 1.67

Duct Bank Height [m] 0.77

Results Summary
Conductor Factor M for Correspondin
Cable Daily Load X coordinate Y coordinate
Cable No. Cable ID Circuit No. Feeder ID Cable Phase temperature Ampacity [A] cyclic loading g cyclic
Frequency Factor [m] [m]
[°C] (as per IEC) current [A]

1 HANHE 1 ABC 50.0 0.46 -0.6 0.75 79.8 165.2 1.669818909 275.9

2 HANHE 2 ABC 50.0 0.46 -0.2 0.75 85.6 165.2 1.669818909 275.9

3 HANHE 3 ABC 50.0 0.46 0.2 0.75 85.6 165.2 1.669818909 275.9

4 HANHE 4 ABC 50.0 0.46 0.6 0.75 79.8 165.2 1.669818909 275.9

5 HANHE 5 ABC 50.0 0.46 -0.6 1.05 83.9 165.2 1.669818909 275.9

6 HANHE 6 ABC 50.0 0.46 -0.2 1.05 90.0 165.2 1.669818909 275.9

7 HANHE 7 ABC 50.0 0.46 0.2 1.05 90.0 165.2 1.669818909 275.9

8 HANHE 8 ABC 50.0 0.46 0.6 1.05 83.9 165.2 1.669818909 275.9
Steady State Summary
CYMCAP Version 7.2 Revision 3

Study: HANHE1

Execution: HANHE1

Date: 2023/9/27 13:17:32

Simulation Data
Installation type: Ductbank

Steady State Option Equally Loaded

Ambient temperature [°C] 20

Native Soil Thermal Resistivity [K.m/W] 1.5

Consider Non-Isothermal Earth Surface No

Consider effect of soil dry out No

Consider Electrical interaction between circuits No

Induced current in metallic layers as a fraction of conductor current


0
(applied to all single phase circuits)

Variable Description Unit Cables


Cable No. Cable Index Number 1 2 3 4 5 6 7 8

General Input Data

Cable ID Cable Equipment ID HANHE HANHE HANHE HANHE HANHE HANHE HANHE HANHE

Circuit No. Circuit No. 1 2 3 4 5 6 7 8

Phase Cable Phase ABC ABC ABC ABC ABC ABC ABC ABC

Fq Operating Frequency [Hz] 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0

x X coordinate [m] -0.6 -0.2 0.2 0.6 -0.6 -0.2 0.2 0.6

y Y coordinate [m] 0.75 0.75 0.75 0.75 1.05 1.05 1.05 1.05

DLF Daily Load Factor [p.u.] 0.46 0.46 0.46 0.46 0.46 0.46 0.46 0.46
SL type 2 Point SL type 2 Point SL type 2 Point SL type 2 Point SL type 2 Point SL type 2 Point SL type 2 Point SL type 2 Point
Bonding Type
Bonded Bonded Bonded Bonded Bonded Bonded Bonded Bonded
Ampacity

I Steady State Ampacity [A] 165.2 165.2 165.2 165.2 165.2 165.2 165.2 165.2

M Factor M for cyclic loading (as per IEC) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

Corresponding cyclic current [A] 275.9 275.9 275.9 275.9 275.9 275.9 275.9 275.9

Temperatures

θc Conductor temperature [°C] 79.8 85.6 85.6 79.8 83.9 90.0 90.0 83.9

θs Sheath/Shield temperature [°C] 76.0 81.7 81.7 76.0 80.0 86.1 86.1 80.0

θa Armour temperature [°C] 75.0 80.6 80.6 75.0 79.0 85.0 85.0 79.0

θsurf Cable surface temperature [°C] 75.0 80.6 80.6 75.0 79.0 85.0 85.0 79.0

θduct Duct surface temperature [°C] 68.6 74.3 74.3 68.6 72.7 78.7 78.7 72.7

Resistances

R₀ DC Resistance of the conductor at 20°C [Ω/km] 0.206 0.206 0.206 0.206 0.206 0.206 0.206 0.206
AC Resistance of the Conductor at Operating
R [Ω/km] 0.25609 0.26086 0.26086 0.25609 0.25949 0.26453 0.26453 0.25949
Temperature
ys Skin Effect Factor 0.00126 0.00121 0.00121 0.00126 0.00122 0.00118 0.00118 0.00122

yp Proximity Effect Factor 0.0005 0.00048 0.00048 0.0005 0.00048 0.00047 0.00047 0.00048

Losses

Wc Conductor Losses [W/m] 19.49074 19.85353 19.85342 19.49042 19.74962 20.13316 20.13308 19.74937

Wd Dielectric Losses [W/m] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Ws Metallic Screen Losses [W/m] 0.12665 0.12438 0.12438 0.12666 0.12502 0.12268 0.12268 0.12503

Wa Armor/Pipe Losses [W/m] 0.10138 0.10138 0.10138 0.10138 0.10138 0.10138 0.10138 0.10138

Wt Total Losses [W/m] 59.15631 60.23786 60.23753 59.15537 59.92806 61.07169 61.07145 59.92733

ƛ₁ Screen Loss Factor 0.0065 0.00626 0.00627 0.0065 0.00633 0.00609 0.00609 0.00633

ƛ₂ Armour Loss Factor + Pipe Loss Factor 0.0052 0.00511 0.00511 0.0052 0.00513 0.00504 0.00504 0.00513

Thermal resistances

T1 Thermal resistance of insulation [K.m/W] 0.54445 0.54445 0.54445 0.54445 0.54445 0.54445 0.54445 0.54445

T2 Thermal resistance of bedding/medium inside pipe-type [K.m/W] 0.04793 0.04793 0.04793 0.04793 0.04793 0.04793 0.04793 0.04793

T3 Thermal resistance of outer covering [K.m/W] n/a n/a n/a n/a n/a n/a n/a n/a

T4 External thermal resistance [K.m/W] 2.59111 3.33352 3.70189 3.7943 4.61976 5.63287 6.08128 6.06382

Others

Temperature Rise at the Surface of the Cable Due to


Δθint [°C] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Other Surrounding Elements

Induced Voltage (standing) on Sheath [V/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Induced Voltage (standing) on Armour [V/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Induced current on Metallic Screen [A] 8.6 8.4 8.4 8.6 8.5 8.3 8.3 8.5
Cables Report
CYMCAP Version 7.2 Revision 3

Study: HANHE1

Execution: HANHE1

Date: 2023/9/27 13:17:32

No. Description Unit 1

General Cable Information


1 Cable Equipment ID HANHE

2 Number of Cores Three Core

3 Voltage [kV] 35

4 Conductor Area [mm²] 150.0

5 Cable Overall Diameter [mm] 101.03

6 Maximum Steady-State Conductor Temperature [°C] 90

7 Maximum Emergency Conductor Temperature [°C] 90

Conductor
8 Material Aluminum

9 Electrical Resistivity at 20°C [µΩ.cm] 2.8264

10 Temperature Coefficient at 20°C [1/K] 0.00403


Reciprocal of Temperature Coefficient of Resistance
11 [K] 228
(BETA)

12 Volumetric Specific Heat (SH) [J/(K*cm³)] 2.5

13 Construction Round Stranded

14 Number of Wires Composing Stranded Conductor n/a

15 Conductor Insulation System Extruded

16 Milliken Wires Construction n/a

17 Ks (Skin Effect Coefficient) 1

18 Kp (Proximity Effect Coefficient) 0.8

19 Diameter [mm] 14.6

Conductor Shield
20 Thickness [mm] 0.8

21 Diameter [mm] 16.2

Insulation
22 Material XLPE Unfilled

23 Thermal Resistivity [K.m/W] 3.5

24 Dielectric Loss Factor - ( tan delta ) 0.004

25 Relative Permittivity - ( epsilon ) 2.5

26 Specific Insulation Resistance Constant at 60°F - ( K ) [㏁.km] 65617.

27 Thickness [mm] 10.5

28 Diameter [mm] 37.2

Insulation Screen
29 Material Semi Conducting Screen

30 Thickness [mm] 0.8

31 Diameter [mm] 38.8

Sheath
32 Is Sheath Around Each Core? Yes

33 Material Copper

34 Electrical Resistivity at 20°C [µΩ.cm] 1.7241

35 Temperature Coefficient at 20°C [1/K] 0.00393


Reciprocal of Temperature Coefficient of Resistance
36 [K] 234.5
(BETA)

37 Volumetric Specific Heat (SH) [J/(K*cm³)] 3.45

38 Corrugation Type Non Corrugated

39 Thickness [mm] 0.1

40 Diameter [mm] 39.0

Armour Bedding
Compounded Jute And Fibrous
41 Material
Material

42 Thermal Resistivity [K.m/W] 6

43 Thickness [mm] 0.5

44 Diameter [mm] 85.03

Armour
45 Material Steel Tape

46 Electrical Resistivity at 20°C [µΩ.cm] 13.8

47 Temperature Coefficient at 20°C [1/K] 0.0045


Reciprocal of Temperature Coefficient of Resistance
48 [K] 202
(BETA)

49 Volumetric Specific Heat (SH) [J/(K*cm³)] 3.8

50 Cross Sectionnal Area of Tape Armour [mm²] 145.0

51 Tape lay Long Lay

52 Longitudinal Relative Permeability 10

53 Transverse Relative Permeability 300

54 Angular Time Delay [°] 45

55 Thickness [mm] 3.9

56 Diameter [mm] 92.83

No. Description Unit 1

Specific Installation Data


57 Cable Equipment ID HANHE

58 Cable Frequency [Hz] 50

59 Sheath / Shield Bonding SL type 2 Point Bonded

60 Loss Factor Constant (ALOS) 0.3

61 Duct construction Polyethylene in Concrete


62 Duct material thermal resistivity [K.m/W] 3.5

63 Inside Diameter of the Duct/Pipe [mm] 160.0

64 Outside Diameter of the Duct/Pipe [mm] 168.0

Cable ID : HANHE
Cable Title FS-ZRC-YJLV22 26_35kV 3*150mm2
Electrical Parameters
CYMCAP Version 7.2 Revision 3

Study: HANHE1

Execution: HANHE1

Date: 2023/9/27 13:17:32

No. Description Unit Cable No.1 Cable No.2 Cable No.3 Cable No.4 Cable No.5 Cable No.6 Cable No.7 Cable No.8

1 Cable Equipment ID HANHE HANHE HANHE HANHE HANHE HANHE HANHE HANHE

Resistances
DC Resistance of the conductor at 20°C
2 [Ω/km] 0.206 0.206 0.206 0.206 0.206 0.206 0.206 0.206

DC Resistance of Conductor at Operating


3 Temperature [Ω/km] 0.25564 0.26042 0.26042 0.25564 0.25905 0.2641 0.2641 0.25905

4 AC Resistance of Conductor at 20°C [Ω/km] 0.20656 0.20656 0.20656 0.20656 0.20656 0.20656 0.20656 0.20656
AC Resistance of Conductor at Operating Temperature
5 [Ω/km] 0.25609 0.26086 0.26086 0.25609 0.25949 0.26453 0.26453 0.25949

6 DC Resistance of Sheath at 20°C [Ω/km] 1.41079 1.41079 1.41079 1.41079 1.41079 1.41079 1.41079 1.41079
DC Resistance of Sheath at Operating Temperature
7 [Ω/km] 1.72125 1.75274 1.75273 1.72122 1.74372 1.77702 1.77701 1.7437

8 DC Resistance of Armor at 20°C [Ω/km] 0.95172 0.95172 0.95172 0.95172 0.95172 0.95172 0.95172 0.95172
DC Resistance of Armor at Operating Temperature
9 [Ω/km] 1.1872 1.21145 1.21144 1.18718 1.20451 1.23014 1.23014 1.20449

Losses
Conductor Losses
10 [W/m] 19.49074 19.85353 19.85342 19.49042 19.74962 20.13316 20.13308 19.74937

Dielectric Losses
11 [W/m] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Metallic Screen Losses


12 [W/m] 0.12665 0.12438 0.12438 0.12666 0.12502 0.12268 0.12268 0.12503

Armor/Pipe Losses
13 [W/m] 0.10138 0.10138 0.10138 0.10138 0.10138 0.10138 0.10138 0.10138

Total Losses
14 [W/m] 59.15631 60.23786 60.23753 59.15537 59.92806 61.07169 61.07145 59.92733

Capacitance, Inductance, Impedance


Capacitance
15 [µF/km] 0.167 0.167 0.167 0.167 0.167 0.167 0.167 0.167

Inductance of Conductor
16 [mH/km] 0.38514 0.38514 0.38514 0.38514 0.38514 0.38514 0.38514 0.38514

Reactance of Conductor
17 [Ω/km] 0.12099 0.12099 0.12099 0.12099 0.12099 0.12099 0.12099 0.12099

Inductance of Metallic Sheath


18 [mH/km] 0.13914 0.13914 0.13914 0.13914 0.13914 0.13914 0.13914 0.13914

Reactance of Metallic Sheath


19 [Ω/km] 0.04371 0.04371 0.04371 0.04371 0.04371 0.04371 0.04371 0.04371

Positive Sequence Impedance 0.256090 + 0.260860 + 0.260860 + 0.256090 + 0.259490 + 0.264530 + 0.264530 + 0.259490 +
20 [Ω/km]
j0.120990 j0.120990 j0.120990 j0.120990 j0.120990 j0.120990 j0.120990 j0.120990

Negative Sequence Impedance 0.256090 + 0.260860 + 0.260860 + 0.256090 + 0.259490 + 0.264530 + 0.264530 + 0.259490 +
21 [Ω/km]
j0.120990 j0.120990 j0.120990 j0.120990 j0.120990 j0.120990 j0.120990 j0.120990

Zero Sequence Impedance 4.438630 + 4.438630 + 4.438630 + 4.438630 + 4.438630 + 4.438620 + 4.438620 + 4.438630 +
22 [Ω/km]
j0.043710 j0.043710 j0.043710 j0.043710 j0.043710 j0.043710 j0.043710 j0.043710

Surge Impedance
23 [Ω] 48.01228 48.01228 48.01228 48.01228 48.01228 48.01228 48.01228 48.01228

Others
Dielectric Stress at Conductor Surface
24 [kV/mm] 3.001 3.001 3.001 3.001 3.001 3.001 3.001 3.001

25 Dielectric Stress at Insulation Surface [kV/mm] 1.30689 1.30689 1.30689 1.30689 1.30689 1.30689 1.30689 1.30689
Insulation Resistance at 60°F (15.8°C)
26 [㏁.km] 23689.49641 23689.49641 23689.49641 23689.49641 23689.49641 23689.49641 23689.49641 23689.49641

Reduction Factor (2pt bonded & single metallic screen)


27 n/a n/a n/a n/a n/a n/a n/a n/a

Charging Current for One Phase


28 [A/km] 1.06064 1.06064 1.06064 1.06064 1.06064 1.06064 1.06064 1.06064

Charging Capacity of three phase system at Uo


29 [kvar/km] 64.29793 64.29793 64.29793 64.29793 64.29793 64.29793 64.29793 64.29793

Voltage drop for Three Phase System


30 [V/A/km] 0.44357 0.45182 0.45182 0.44356 0.44946 0.45819 0.45818 0.44945

31 Induced Voltage (standing) on Sheath [V/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
32 Induced Voltage (standing) on Armour [V/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Induced current on Metallic Screen
33 [A] 8.6 8.4 8.4 8.6 8.5 8.3 8.3 8.5
Cable Parameters under Normal Operation
CYMCAP Version 7.2 Revision 3

Study: HANHE1

Execution: HANHE1

Date: 2023/9/27 13:17:32

No. Symbol Description Unit Cable No.1 Cable No.2 Cable No.3 Cable No.4 Cable No.5 Cable No.6 Cable No.7 Cable No.8

1 Cable Equipment ID HANHE HANHE HANHE HANHE HANHE HANHE HANHE HANHE

Normal Operation IEC 60287-1-1

Conductor AC Resistance
DC Resistance of the conductor at 20°C
2 R₀ [Ω/km] 0.206 0.206 0.206 0.206 0.206 0.206 0.206 0.206

DC Resistance of Conductor at Operating Temperature


3 R' [Ω/km] 0.25564 0.26042 0.26042 0.25564 0.25905 0.2641 0.2641 0.25905

4 dc Conductor Diameter [mm] 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6
5 s Distance Between Conductor Axes [mm] 39.0 39.0 39.0 39.0 39.0 39.0 39.0 39.0
6 ks Factor Used for xs Calculation (Skin Effect) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
7 kp Factor Used for xp Calculation (Proximity Effect) 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
Component of Ys Calculation (Skin Effect)
8 xs 0.70111 0.69465 0.69465 0.70112 0.69648 0.6898 0.6898 0.69649

Component of Yp Calculation (Proximity Effect)


9 xp 0.62709 0.62132 0.62132 0.6271 0.62295 0.61697 0.61697 0.62296

Skin Effect Factor


10 ys 0.00126 0.00121 0.00121 0.00126 0.00122 0.00118 0.00118 0.00122

Proximity Effect Factor


11 yp 0.0005 0.00048 0.00048 0.0005 0.00048 0.00047 0.00047 0.00048

12 Fmag Multiplying factor due to magnetic layers 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
AC Resistance of Conductor at Operating Temperature
13 R [Ω/km] 0.25609 0.26086 0.26086 0.25609 0.25949 0.26453 0.26453 0.25949

Dielectric Losses
14 tanδ Dielectric Loss Factor 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004
15 ε Insulation Relative Permitivity 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Cable Capacitance
16 C [µF/km] 0.167 0.167 0.167 0.167 0.167 0.167 0.167 0.167

17 U₀ Voltage [kV] 20.20726 20.20726 20.20726 20.20726 20.20726 20.20726 20.20726 20.20726
Cable Dielectric Losses Per Phase
18 Wd [W/m] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Circulating Loss Factor


19 Rs AC Resistance used for Circulating Loss Factor [Ω/km] 1.72125 1.75274 1.75273 1.72122 1.74372 1.77702 1.77701 1.7437
20 d Mean diameter used for Circulating Loss Factor [mm] 38.9 38.9 38.9 38.9 38.9 38.9 38.9 38.9
Reactance used for Circulating Loss Factor computation
21 X [Ω/km] 0.04371 0.04371 0.04371 0.04371 0.04371 0.04371 0.04371 0.04371

Spacing Factor (applied when spacing between cable


22 Fspacing uneven or non-equal minor section length) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

Magnetic effect factor due to pipe


23 Fpipe 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

Magnetic effect factor due to armour


24 Farmour 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

Screen Loss Factor Caused by Circulating Current


25 ƛ'₁ 0.0065 0.00626 0.00627 0.0065 0.00633 0.00609 0.00609 0.00633

Eddy Loss Factor


Screen Loss Factor Caused by Eddy Current
26 ƛ''₁ 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Metallic Screen Loss factor


Screen Loss Factor
27 ƛ₁ 0.0065 0.00626 0.00627 0.0065 0.00633 0.00609 0.00609 0.00633

Armour and Pipe Loss Factor


Magnetic effect factor due to pipe
28 Fpipe 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

Screening effect factor


29 Fscreen 0.99903 0.99907 0.99907 0.99903 0.99906 0.99909 0.99909 0.99906

Component for Armour Loss Factor Formula (Clause


30 k 0.61891 0.61891 0.61891 0.61891 0.61891 0.61891 0.61891 0.61891

Armour Loss Factor


31 ƛ₂a 0.0052 0.00511 0.00511 0.0052 0.00513 0.00504 0.00504 0.00513

Pipe Loss Factor


32 ƛ₂pipe 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Armour Loss Factor + Pipe Loss Factor


33 ƛ₂ 0.0052 0.00511 0.00511 0.0052 0.00513 0.00504 0.00504 0.00513

Normal Operation IEC 60287-2-1


Thermal Resistance Between Conductor and Screen
35 T₁ [K.m/W] 0.54445 0.54445 0.54445 0.54445 0.54445 0.54445 0.54445 0.54445

36 t₁ Insulation Thickness Between Conductor and Screen [mm] 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1
37 ρTi Thermal Resistivity of Insulation [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Thermal Resistance Between Sheath and Armour
38 T₂ [K.m/W] 0.04793 0.04793 0.04793 0.04793 0.04793 0.04793 0.04793 0.04793

39 t₂ Thickness Between Sheath and Armour [mm] 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
40 ρTB Thermal Resistivity Between Screen and Armour [K.m/W] 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0
Cable in Ducts
41 U Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1 1.87 1.87 1.87 1.87 1.87 1.87 1.87 1.87
42 V Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1 0.312 0.312 0.312 0.312 0.312 0.312 0.312 0.312
43 Y Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1 0.0037 0.0037 0.0037 0.0037 0.0037 0.0037 0.0037 0.0037
44 θm Mean Temperature of the Medium Filling the Space [°C] 72.1 77.8 77.8 72.1 76.2 82.2 82.2 76.1
45 T₄' Thermal Resistance of the Medium Inside the Duct/Pipe [K.m/W] 0.27311 0.26487 0.26488 0.27312 0.26718 0.25886 0.25886 0.26719
46 Do Outside Diameter of the Duct/Pipe [mm] 168.0 168.0 168.0 168.0 168.0 168.0 168.0 168.0
47 Di Inside Diameter of the Duct/Pipe [mm] 160.0 160.0 160.0 160.0 160.0 160.0 160.0 160.0
48 ρT Thermal Resistivity of the Duct/Pipe Material [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
49 T₄'' Thermal Resistance of the Duct/Pipe [K.m/W] 0.02718 0.02718 0.02718 0.02718 0.02718 0.02718 0.02718 0.02718
50 T₄''' Thermal Resistance of the Surrounding Medium [K.m/W] 2.29082 3.04147 3.40983 3.494 4.3254 5.34684 5.79525 5.76945
Cable in a Duct Bank/Backfill installation
51 x Shorter Side of the Duct Bank/Backfill [m] 0.768 0.768 0.768 0.768 0.768 0.768 0.768 0.768
52 y Longer Side of the Duct Bank/Backfill [m] 1.668 1.668 1.668 1.668 1.668 1.668 1.668 1.668
Equivalent Radius of Duct Bank/Backfill
53 rb [m] 0.53213 0.53213 0.53213 0.53213 0.53213 0.53213 0.53213 0.53213

54 LG Depth of Laying to the Centre of Duct Bank/Backfill [m] 0.866 0.866 0.866 0.866 0.866 0.866 0.866 0.866
Coefficient Used in IEC 60287-2-1 Clause 2.2.7.3
55 u 1.62744 1.62744 1.62744 1.62744 1.62744 1.62744 1.62744 1.62744

56 N Number of Loaded Cables in the Duct Bank/Backfill 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
57 ρe Thermal Resistivity of Earth Around the Duct Bank/Backfill [K.m/W] 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
58 ρc Thermal Resistivity of the Duct Bank/Backfill [K.m/W] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Thermal Resistance of the Surrounding Medium
59 T₄''' [K.m/W] 2.29082 3.04147 3.40983 3.494 4.3254 5.34684 5.79525 5.76945

Total External Thermal Resistance


60 T₄ [K.m/W] 2.59111 3.33352 3.70189 3.7943 4.61976 5.63287 6.08128 6.06382

Temperature Rise at the Surface of the Cable Due to


61 Δθint [°C] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Other Surrounding Elements
Cable Core Current Ampacity
62 I [A] 275.9 275.9 275.9 275.9 275.9 275.9 275.9 275.9
Study Summary
CYMCAP Version 7.2 Revision 3

Study: HANHE2

Execution: HANHE2

Date: 2023/9/27 13:19:20

General Simulation Data


Steady State Option Equally Loaded

Consider Electrical interaction between circuits No

Induced currents in metallic layers as a fraction of conductor current (applied to all single phase circuits) : 0.0

Conductor Resistances Computation Option: IEC-228

Installation Type:Ductbank
Ambient Soil Temperature at Installation Depth [°C] 20.0

Native Soil Thermal Resistivity [K.m/W] 1.5

Cyclic Loading Option IEC 60853

Thermal Resistivity of Duct Bank [K.m/W] 1.0

Depth of Center of Duct Bank [m] 0.87

Duct Bank Width [m] 1.67

Duct Bank Height [m] 0.77

Results Summary
Conductor Factor M for Correspondin
Cable Daily Load X coordinate Y coordinate
Cable No. Cable ID Circuit No. Feeder ID Cable Phase temperature Ampacity [A] cyclic loading g cyclic
Frequency Factor [m] [m]
[°C] (as per IEC) current [A]

1 HANHE2 1 ABC 50.0 0.46 -0.6 0.73 79.5 269.3 1.697998917 457.3

2 HANHE2 2 ABC 50.0 0.46 -0.2 0.73 85.4 269.3 1.697998917 457.3

3 HANHE2 3 ABC 50.0 0.46 0.2 0.73 85.4 269.3 1.697998917 457.3

4 HANHE2 4 ABC 50.0 0.46 0.6 0.73 79.5 269.3 1.697998917 457.3

5 HANHE2 5 ABC 50.0 0.46 -0.6 1.03 83.7 269.3 1.697998917 457.3

6 HANHE2 6 ABC 50.0 0.46 -0.2 1.03 90.0 269.3 1.697998917 457.3

7 HANHE2 7 ABC 50.0 0.46 0.2 1.03 90.0 269.3 1.697998917 457.3

8 HANHE2 8 ABC 50.0 0.46 0.6 1.03 83.7 269.3 1.697998917 457.3
Steady State Summary
CYMCAP Version 7.2 Revision 3

Study: HANHE2

Execution: HANHE2

Date: 2023/9/27 13:19:20

Simulation Data
Installation type: Ductbank

Steady State Option Equally Loaded

Ambient temperature [°C] 20

Native Soil Thermal Resistivity [K.m/W] 1.5

Consider Non-Isothermal Earth Surface No

Consider effect of soil dry out No

Consider Electrical interaction between circuits No

Induced current in metallic layers as a fraction of conductor current


0
(applied to all single phase circuits)

Variable Description Unit Cables


Cable No. Cable Index Number 1 2 3 4 5 6 7 8

General Input Data

Cable ID Cable Equipment ID HANHE2 HANHE2 HANHE2 HANHE2 HANHE2 HANHE2 HANHE2 HANHE2

Circuit No. Circuit No. 1 2 3 4 5 6 7 8

Phase Cable Phase ABC ABC ABC ABC ABC ABC ABC ABC

Fq Operating Frequency [Hz] 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0

x X coordinate [m] -0.6 -0.2 0.2 0.6 -0.6 -0.2 0.2 0.6

y Y coordinate [m] 0.73 0.73 0.73 0.73 1.03 1.03 1.03 1.03

DLF Daily Load Factor [p.u.] 0.46 0.46 0.46 0.46 0.46 0.46 0.46 0.46
SL type 2 Point SL type 2 Point SL type 2 Point SL type 2 Point SL type 2 Point SL type 2 Point SL type 2 Point SL type 2 Point
Bonding Type
Bonded Bonded Bonded Bonded Bonded Bonded Bonded Bonded
Ampacity

I Steady State Ampacity [A] 269.3 269.3 269.3 269.3 269.3 269.3 269.3 269.3

M Factor M for cyclic loading (as per IEC) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

Corresponding cyclic current [A] 457.3 457.3 457.3 457.3 457.3 457.3 457.3 457.3

Temperatures

θc Conductor temperature [°C] 79.5 85.4 85.4 79.5 83.7 90.0 90.0 83.7

θs Sheath/Shield temperature [°C] 76.7 82.6 82.5 76.7 80.9 87.1 87.1 80.9

θa Armour temperature [°C] 75.8 81.7 81.7 75.8 80.0 86.2 86.2 80.0

θsurf Cable surface temperature [°C] 75.8 81.7 81.7 75.8 80.0 86.2 86.2 80.0

θduct Duct surface temperature [°C] 70.2 76.1 76.1 70.2 74.4 80.7 80.7 74.4

Resistances

R₀ DC Resistance of the conductor at 20°C [Ω/km] 0.0778 0.0778 0.0778 0.0778 0.0778 0.0778 0.0778 0.0778
AC Resistance of the Conductor at Operating
R [Ω/km] 0.09787 0.0997 0.09969 0.09786 0.09919 0.10112 0.10112 0.09918
Temperature
ys Skin Effect Factor 0.00878 0.00845 0.00845 0.00878 0.00854 0.00821 0.00821 0.00854

yp Proximity Effect Factor 0.00596 0.00574 0.00574 0.00596 0.0058 0.00558 0.00558 0.0058

Losses

Wc Conductor Losses [W/m] 20.46627 20.84845 20.84808 20.46515 20.74194 21.14665 21.14625 20.74068

Wd Dielectric Losses [W/m] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Ws Metallic Screen Losses [W/m] 0.42771 0.41982 0.41982 0.42773 0.42198 0.41386 0.41387 0.42201

Wa Armor/Pipe Losses [W/m] 0.2812 0.28121 0.28121 0.2812 0.28121 0.28123 0.28123 0.28121

Wt Total Losses [W/m] 63.52553 64.64843 64.64735 63.52223 64.33541 65.52522 65.52402 64.33172

ƛ₁ Screen Loss Factor 0.0209 0.02014 0.02014 0.0209 0.02034 0.01957 0.01957 0.02035

ƛ₂ Armour Loss Factor + Pipe Loss Factor 0.01374 0.01349 0.01349 0.01374 0.01356 0.0133 0.0133 0.01356

Thermal resistances

T1 Thermal resistance of insulation [K.m/W] 0.39196 0.39196 0.39196 0.39196 0.39196 0.39196 0.39196 0.39196

T2 Thermal resistance of bedding/medium inside pipe-type [K.m/W] 0.03998 0.03998 0.03998 0.03998 0.03998 0.03998 0.03998 0.03998

T3 Thermal resistance of outer covering [K.m/W] n/a n/a n/a n/a n/a n/a n/a n/a

T4 External thermal resistance [K.m/W] 2.5318 3.29963 3.68406 3.78813 4.65045 5.70507 6.17451 6.16255

Others

Temperature Rise at the Surface of the Cable Due to


Δθint [°C] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Other Surrounding Elements

Induced Voltage (standing) on Sheath [V/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Induced Voltage (standing) on Armour [V/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Induced current on Metallic Screen [A] 17.5 17.2 17.2 17.5 17.3 16.9 16.9 17.3
Cables Report
CYMCAP Version 7.2 Revision 3

Study: HANHE2

Execution: HANHE2

Date: 2023/9/27 13:19:20

No. Description Unit 1

General Cable Information


1 Cable Equipment ID HANHE2

2 Number of Cores Three Core

3 Voltage [kV] 35

4 Conductor Area [mm²] 400.0

5 Cable Overall Diameter [mm] 122.64

6 Maximum Steady-State Conductor Temperature [°C] 90

7 Maximum Emergency Conductor Temperature [°C] 90

Conductor
8 Material Aluminum

9 Electrical Resistivity at 20°C [µΩ.cm] 2.8264

10 Temperature Coefficient at 20°C [1/K] 0.00403


Reciprocal of Temperature Coefficient of Resistance
11 [K] 228
(BETA)

12 Volumetric Specific Heat (SH) [J/(K*cm³)] 2.5

13 Construction Round Stranded

14 Number of Wires Composing Stranded Conductor n/a

15 Conductor Insulation System Extruded

16 Milliken Wires Construction n/a

17 Ks (Skin Effect Coefficient) 1

18 Kp (Proximity Effect Coefficient) 0.8

19 Diameter [mm] 23.7

Conductor Shield
20 Thickness [mm] 0.8

21 Diameter [mm] 25.3

Insulation
22 Material XLPE Unfilled

23 Thermal Resistivity [K.m/W] 3.5

24 Dielectric Loss Factor - ( tan delta ) 0.004

25 Relative Permittivity - ( epsilon ) 2.5

26 Specific Insulation Resistance Constant at 60°F - ( K ) [㏁.km] 65617.

27 Thickness [mm] 10.5

28 Diameter [mm] 46.3

Insulation Screen
29 Material Semi Conducting Screen

30 Thickness [mm] 0.8

31 Diameter [mm] 47.9

Sheath
32 Is Sheath Around Each Core? Yes

33 Material Copper

34 Electrical Resistivity at 20°C [µΩ.cm] 1.7241

35 Temperature Coefficient at 20°C [1/K] 0.00393


Reciprocal of Temperature Coefficient of Resistance
36 [K] 234.5
(BETA)

37 Volumetric Specific Heat (SH) [J/(K*cm³)] 3.45

38 Corrugation Type Non Corrugated

39 Thickness [mm] 0.1

40 Diameter [mm] 48.1

Armour Bedding
Compounded Jute And Fibrous
41 Material
Material

42 Thermal Resistivity [K.m/W] 6

43 Thickness [mm] 0.5

44 Diameter [mm] 104.64

Armour
45 Material Steel Tape

46 Electrical Resistivity at 20°C [µΩ.cm] 13.8

47 Temperature Coefficient at 20°C [1/K] 0.0045


Reciprocal of Temperature Coefficient of Resistance
48 [K] 202
(BETA)

49 Volumetric Specific Heat (SH) [J/(K*cm³)] 3.8

50 Cross Sectionnal Area of Tape Armour [mm²] 560.0

51 Tape lay Long Lay

52 Longitudinal Relative Permeability 10

53 Transverse Relative Permeability 300

54 Angular Time Delay [°] 45

55 Thickness [mm] 4.2

56 Diameter [mm] 113.04

No. Description Unit 1

Specific Installation Data


57 Cable Equipment ID HANHE2

58 Cable Frequency [Hz] 50

59 Sheath / Shield Bonding SL type 2 Point Bonded

60 Loss Factor Constant (ALOS) 0.3

61 Duct construction Polyethylene in Concrete


62 Duct material thermal resistivity [K.m/W] 3.5

63 Inside Diameter of the Duct/Pipe [mm] 160.0

64 Outside Diameter of the Duct/Pipe [mm] 168.0

Cable ID : HANHE2
Cable Title FS-ZRC-YJLV22 26_35kV3*400mm2
Electrical Parameters
CYMCAP Version 7.2 Revision 3

Study: HANHE2

Execution: HANHE2

Date: 2023/9/27 13:19:20

No. Description Unit Cable No.1 Cable No.2 Cable No.3 Cable No.4 Cable No.5 Cable No.6 Cable No.7 Cable No.8

1 Cable Equipment ID HANHE2 HANHE2 HANHE2 HANHE2 HANHE2 HANHE2 HANHE2 HANHE2

Resistances
DC Resistance of the conductor at 20°C
2 [Ω/km] 0.0778 0.0778 0.0778 0.0778 0.0778 0.0778 0.0778 0.0778

DC Resistance of Conductor at Operating Temperature


3 [Ω/km] 0.09645 0.0983 0.0983 0.09644 0.09778 0.09975 0.09975 0.09778

4 AC Resistance of Conductor at 20°C [Ω/km] 0.07955 0.07955 0.07955 0.07955 0.07955 0.07955 0.07955 0.07955
AC Resistance of Conductor at Operating Temperature
5 [Ω/km] 0.09787 0.0997 0.09969 0.09786 0.09919 0.10112 0.10112 0.09918

6 DC Resistance of Sheath at 20°C [Ω/km] 1.14333 1.14333 1.14333 1.14333 1.14333 1.14333 1.14333 1.14333
DC Resistance of Sheath at Operating Temperature
7 [Ω/km] 1.39807 1.4244 1.42438 1.39799 1.41706 1.44494 1.44491 1.41698

8 DC Resistance of Armor at 20°C [Ω/km] 0.24643 0.24643 0.24643 0.24643 0.24643 0.24643 0.24643 0.24643
DC Resistance of Armor at Operating Temperature
9 [Ω/km] 0.30833 0.31481 0.31481 0.30831 0.31301 0.31987 0.31986 0.31299

Losses
Conductor Losses
10 [W/m] 20.46627 20.84845 20.84808 20.46515 20.74194 21.14665 21.14625 20.74068

Dielectric Losses
11 [W/m] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Metallic Screen Losses


12 [W/m] 0.42771 0.41982 0.41982 0.42773 0.42198 0.41386 0.41387 0.42201

Armor/Pipe Losses
13 [W/m] 0.2812 0.28121 0.28121 0.2812 0.28121 0.28123 0.28123 0.28121

Total Losses
14 [W/m] 63.52553 64.64843 64.64735 63.52223 64.33541 65.52522 65.52402 64.33172

Capacitance, Inductance, Impedance


Capacitance
15 [µF/km] 0.23 0.23 0.23 0.23 0.23 0.23 0.23 0.23

Inductance of Conductor
16 [mH/km] 0.33019 0.33019 0.33019 0.33019 0.33019 0.33019 0.33019 0.33019

Reactance of Conductor
17 [Ω/km] 0.10373 0.10373 0.10373 0.10373 0.10373 0.10373 0.10373 0.10373

Inductance of Metallic Sheath


18 [mH/km] 0.13905 0.13905 0.13905 0.13905 0.13905 0.13905 0.13905 0.13905

Reactance of Metallic Sheath


19 [Ω/km] 0.04368 0.04368 0.04368 0.04368 0.04368 0.04368 0.04368 0.04368

Positive Sequence Impedance 0.097870 + 0.099700 + 0.099690 + 0.097860 + 0.099190 + 0.101120 + 0.101120 + 0.099180 +
20 [Ω/km]
j0.103730 j0.103730 j0.103730 j0.103730 j0.103730 j0.103730 j0.103730 j0.103730

Negative Sequence Impedance 0.097870 + 0.099700 + 0.099690 + 0.097860 + 0.099190 + 0.101120 + 0.101120 + 0.099180 +
21 [Ω/km]
j0.103730 j0.103730 j0.103730 j0.103730 j0.103730 j0.103730 j0.103730 j0.103730

Zero Sequence Impedance 3.508470 + 3.508450 + 3.508450 + 3.508470 + 3.508450 + 3.508430 + 3.508430 + 3.508450 +
22 [Ω/km]
j0.043680 j0.043680 j0.043680 j0.043680 j0.043680 j0.043680 j0.043680 j0.043680

Surge Impedance
23 [Ω] 37.90431 37.90431 37.90431 37.90431 37.90431 37.90431 37.90431 37.90431

Others
Dielectric Stress at Conductor Surface
24 [kV/mm] 2.64324 2.64324 2.64324 2.64324 2.64324 2.64324 2.64324 2.64324

25 Dielectric Stress at Insulation Surface [kV/mm] 1.44436 1.44436 1.44436 1.44436 1.44436 1.44436 1.44436 1.44436
Insulation Resistance at 60°F (15.8°C)
26 [㏁.km] 17221.81561 17221.81561 17221.81561 17221.81561 17221.81561 17221.81561 17221.81561 17221.81561

Reduction Factor (2pt bonded & single metallic screen)


27 n/a n/a n/a n/a n/a n/a n/a n/a

Charging Current for One Phase


28 [A/km] 1.45897 1.45897 1.45897 1.45897 1.45897 1.45897 1.45897 1.45897

Charging Capacity of three phase system at Uo


29 [kvar/km] 88.44512 88.44512 88.44512 88.44512 88.44512 88.44512 88.44512 88.44512

Voltage drop for Three Phase System


30 [V/A/km] 0.16951 0.17268 0.17268 0.16951 0.1718 0.17515 0.17515 0.17179

31 Induced Voltage (standing) on Sheath [V/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
32 Induced Voltage (standing) on Armour [V/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Induced current on Metallic Screen
33 [A] 17.5 17.2 17.2 17.5 17.3 16.9 16.9 17.3
Cable Parameters under Normal Operation
CYMCAP Version 7.2 Revision 3

Study: HANHE2

Execution: HANHE2

Date: 2023/9/27 13:19:20

No. Symbol Description Unit Cable No.1 Cable No.2 Cable No.3 Cable No.4 Cable No.5 Cable No.6 Cable No.7 Cable No.8

1 Cable Equipment ID HANHE2 HANHE2 HANHE2 HANHE2 HANHE2 HANHE2 HANHE2 HANHE2

Normal Operation IEC 60287-1-1

Conductor AC Resistance
DC Resistance of the conductor at 20°C
2 R₀ [Ω/km] 0.0778 0.0778 0.0778 0.0778 0.0778 0.0778 0.0778 0.0778

DC Resistance of Conductor at Operating Temperature


3 R' [Ω/km] 0.09645 0.0983 0.0983 0.09644 0.09778 0.09975 0.09975 0.09778

4 dc Conductor Diameter [mm] 23.7 23.7 23.7 23.7 23.7 23.7 23.7 23.7
5 s Distance Between Conductor Axes [mm] 48.1 48.1 48.1 48.1 48.1 48.1 48.1 48.1
6 ks Factor Used for xs Calculation (Skin Effect) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
7 kp Factor Used for xp Calculation (Proximity Effect) 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
Component of Ys Calculation (Skin Effect)
8 xs 1.14146 1.13064 1.13065 1.14149 1.13362 1.12242 1.12243 1.13366

Component of Yp Calculation (Proximity Effect)


9 xp 1.02095 1.01128 1.01129 1.02098 1.01394 1.00392 1.00393 1.01398

Skin Effect Factor


10 ys 0.00878 0.00845 0.00845 0.00878 0.00854 0.00821 0.00821 0.00854

Proximity Effect Factor


11 yp 0.00596 0.00574 0.00574 0.00596 0.0058 0.00558 0.00558 0.0058

12 Fmag Multiplying factor due to magnetic layers 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
AC Resistance of Conductor at Operating Temperature
13 R [Ω/km] 0.09787 0.0997 0.09969 0.09786 0.09919 0.10112 0.10112 0.09918

Dielectric Losses
14 tanδ Dielectric Loss Factor 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004
15 ε Insulation Relative Permitivity 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Cable Capacitance
16 C [µF/km] 0.23 0.23 0.23 0.23 0.23 0.23 0.23 0.23

17 U₀ Voltage [kV] 20.20726 20.20726 20.20726 20.20726 20.20726 20.20726 20.20726 20.20726
Cable Dielectric Losses Per Phase
18 Wd [W/m] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Circulating Loss Factor


19 Rs AC Resistance used for Circulating Loss Factor computation [Ω/km] 1.39807 1.4244 1.42438 1.39799 1.41706 1.44494 1.44491 1.41698
20 d Mean diameter used for Circulating Loss Factor computation [mm] 48.0 48.0 48.0 48.0 48.0 48.0 48.0 48.0
Reactance used for Circulating Loss Factor computation
21 X [Ω/km] 0.04368 0.04368 0.04368 0.04368 0.04368 0.04368 0.04368 0.04368

Spacing Factor (applied when spacing between cable uneven


22 Fspacing or non-equal minor section length) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

Magnetic effect factor due to pipe


23 Fpipe 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

Magnetic effect factor due to armour


24 Farmour 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

Screen Loss Factor Caused by Circulating Current


25 ƛ'₁ 0.0209 0.02014 0.02014 0.0209 0.02034 0.01957 0.01957 0.02035

Eddy Loss Factor


Screen Loss Factor Caused by Eddy Current
26 ƛ''₁ 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Metallic Screen Loss factor


Screen Loss Factor
27 ƛ₁ 0.0209 0.02014 0.02014 0.0209 0.02034 0.01957 0.01957 0.02035

Armour and Pipe Loss Factor


Magnetic effect factor due to pipe
28 Fpipe 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

Screening effect factor


29 Fscreen 0.99854 0.99859 0.99859 0.99854 0.99858 0.99863 0.99863 0.99858

Component for Armour Loss Factor Formula (Clause 2.4.2.4)


30 k 0.8115 0.8115 0.8115 0.8115 0.8115 0.8115 0.8115 0.8115

Armour Loss Factor


31 ƛ₂a 0.01374 0.01349 0.01349 0.01374 0.01356 0.0133 0.0133 0.01356

Pipe Loss Factor


32 ƛ₂pipe 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Armour Loss Factor + Pipe Loss Factor


33 ƛ₂ 0.01374 0.01349 0.01349 0.01374 0.01356 0.0133 0.0133 0.01356

Normal Operation IEC 60287-2-1


Thermal Resistance Between Conductor and Screen
35 T₁ [K.m/W] 0.39196 0.39196 0.39196 0.39196 0.39196 0.39196 0.39196 0.39196

36 t₁ Insulation Thickness Between Conductor and Screen [mm] 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1
37 ρTi Thermal Resistivity of Insulation [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Thermal Resistance Between Sheath and Armour
38 T₂ [K.m/W] 0.03998 0.03998 0.03998 0.03998 0.03998 0.03998 0.03998 0.03998

39 t₂ Thickness Between Sheath and Armour [mm] 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
40 ρTB Thermal Resistivity Between Screen and Armour [K.m/W] 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0
Cable in Ducts
41 U Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1 1.87 1.87 1.87 1.87 1.87 1.87 1.87 1.87
42 V Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1 0.312 0.312 0.312 0.312 0.312 0.312 0.312 0.312
43 Y Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1 0.0037 0.0037 0.0037 0.0037 0.0037 0.0037 0.0037 0.0037
44 θm Mean Temperature of the Medium Filling the Space [°C] 73.3 79.2 79.2 73.3 77.5 83.8 83.8 77.5
45 T₄' Thermal Resistance of the Medium Inside the Duct/Pipe [K.m/W] 0.22938 0.22211 0.22212 0.2294 0.22409 0.21675 0.21676 0.22411
46 Do Outside Diameter of the Duct/Pipe [mm] 168.0 168.0 168.0 168.0 168.0 168.0 168.0 168.0
47 Di Inside Diameter of the Duct/Pipe [mm] 160.0 160.0 160.0 160.0 160.0 160.0 160.0 160.0
48 ρT Thermal Resistivity of the Duct/Pipe Material [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
49 T₄'' Thermal Resistance of the Duct/Pipe [K.m/W] 0.02718 0.02718 0.02718 0.02718 0.02718 0.02718 0.02718 0.02718
50 T₄''' Thermal Resistance of the Surrounding Medium [K.m/W] 2.27524 3.05034 3.43477 3.53155 4.39919 5.46114 5.93058 5.91126
Cable in a Duct Bank/Backfill installation
51 x Shorter Side of the Duct Bank/Backfill [m] 0.768 0.768 0.768 0.768 0.768 0.768 0.768 0.768
52 y Longer Side of the Duct Bank/Backfill [m] 1.668 1.668 1.668 1.668 1.668 1.668 1.668 1.668
Equivalent Radius of Duct Bank/Backfill
53 rb [m] 0.53213 0.53213 0.53213 0.53213 0.53213 0.53213 0.53213 0.53213

54 LG Depth of Laying to the Centre of Duct Bank/Backfill [m] 0.866 0.866 0.866 0.866 0.866 0.866 0.866 0.866
Coefficient Used in IEC 60287-2-1 Clause 2.2.7.3
55 u 1.62744 1.62744 1.62744 1.62744 1.62744 1.62744 1.62744 1.62744

56 N Number of Loaded Cables in the Duct Bank/Backfill 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
57 ρe Thermal Resistivity of Earth Around the Duct Bank/Backfill [K.m/W] 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
58 ρc Thermal Resistivity of the Duct Bank/Backfill [K.m/W] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Thermal Resistance of the Surrounding Medium
59 T₄''' [K.m/W] 2.27524 3.05034 3.43477 3.53155 4.39919 5.46114 5.93058 5.91126

Total External Thermal Resistance


60 T₄ [K.m/W] 2.5318 3.29963 3.68406 3.78813 4.65045 5.70507 6.17451 6.16255

Temperature Rise at the Surface of the Cable Due to Other


61 Δθint [°C] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Surrounding Elements
Cable Core Current Ampacity
62 I [A] 457.3 457.3 457.3 457.3 457.3 457.3 457.3 457.3
Study Summary
CYMCAP Version 7.2 Revision 02
Study: YJLV22-1.8_3KV-3X300-8.25
Execution: YJLV22-1.8_3KV-3X300-8.25
Date: 2023/9/19 16:02:26

General Simulation Data


Steady State Option Equally Loaded
Consider Electrical interaction between circuits No

Induced currents in metallic layers as a fraction of conductor current (applied to all single phase circuits) : 0.0

Conductor Resistances Computation Option: IEC-228

Installation Type:Buried Ducts


Ambient Soil Temperature at Installation Depth [°C] 20.0
Native Soil Thermal Resistivity [K.m/W] 1.5
Cyclic Loading Option IEC 60853
Consider Non-Isothermal Earth Surface No

Results Summary

Conductor Factor M for Corresponding


Cable Daily Load X coordinate Y coordinate
Cable No. Cable ID Circuit No. Feeder ID Cable Phase temperature [° Ampacity [A] cyclic loading cyclic current
Frequency Factor [m] [m]
C] (as per IEC) [A]

1 V22-1.8-3-3X300- 1 ABC 50.0 0.46 -0.6 0.8 76.6 211.0 1.716858264 362.2
2 V22-1.8-3-3X300- 2 ABC 50.0 0.46 -0.2 0.8 83.4 211.0 1.716858264 362.2
3 V22-1.8-3-3X300- 3 ABC 50.0 0.46 0.2 0.8 83.4 211.0 1.716858264 362.2
4 V22-1.8-3-3X300- 4 ABC 50.0 0.46 0.6 0.8 76.6 211.0 1.716858264 362.2
5 V22-1.8-3-3X300- 5 ABC 50.0 0.46 -0.6 1.2 82.8 211.0 1.716858264 362.2
6 V22-1.8-3-3X300- 6 ABC 50.0 0.46 -0.2 1.2 90.0 211.0 1.716858264 362.2
7 V22-1.8-3-3X300- 7 ABC 50.0 0.46 0.2 1.2 90.0 211.0 1.716858264 362.2
8 V22-1.8-3-3X300- 8 ABC 50.0 0.46 0.6 1.2 82.8 211.0 1.716858264 362.2
Steady State Summary
CYMCAP Version 7.2 Revision 02
Study: YJLV22-1.8_3KV-3X300-8.25
Execution: YJLV22-1.8_3KV-3X300-8.25
Date: 2023/9/19 16:02:26

Simulation Data
Installation type: Buried Ducts
Steady State Option Equally Loaded
Ambient temperature [°C] 20
Native Soil Thermal Resistivity [K.m/W] 1.5
Consider Non-Isothermal Earth Surface No
Consider effect of soil dry out No
Consider Electrical interaction between circuits No

Induced current in metallic layers as a fraction of conductor current (applied to


0
all single phase circuits)

Variable Description Unit Cables


Cable No. Cable Index Number 1 2 3 4 5 6 7 8
General Input Data
YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3-
Cable ID Cable Equipment ID
3X300-8.25 3X300-8.25 3X300-8.25 3X300-8.25 3X300-8.25 3X300-8.25 3X300-8.25 3X300-8.25
Circuit No. Circuit No. 1 2 3 4 5 6 7 8
Phase Cable Phase ABC ABC ABC ABC ABC ABC ABC ABC
Fq Operating Frequency [Hz] 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0
x X coordinate [m] -0.6 -0.2 0.2 0.6 -0.6 -0.2 0.2 0.6
y Y coordinate [m] 0.8 0.8 0.8 0.8 1.2 1.2 1.2 1.2
DLF Daily Load Factor [p.u.] 0.46 0.46 0.46 0.46 0.46 0.46 0.46 0.46

3 Conductor Steel 3 Conductor Steel 3 Conductor Steel 3 Conductor Steel 3 Conductor Steel 3 Conductor Steel 3 Conductor Steel 3 Conductor Steel
Bonding Type
Tape Armour Tape Armour Tape Armour Tape Armour Tape Armour Tape Armour Tape Armour Tape Armour

Ampacity
I Steady State Ampacity [A] 211.0 211.0 211.0 211.0 211.0 211.0 211.0 211.0

M Factor M for cyclic loading (as per IEC) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

Corresponding cyclic current [A] 362.2 362.2 362.2 362.2 362.2 362.2 362.2 362.2
Temperatures
θc Conductor temperature [°C] 76.6 83.4 83.4 76.6 82.8 90.0 90.0 82.8
θs Sheath/Shield temperature [°C] n/a n/a n/a n/a n/a n/a n/a n/a
θa Armour temperature [°C] 72.6 79.3 79.3 72.6 78.7 85.8 85.8 78.7
θsurf Cable surface temperature [°C] 71.3 78.0 78.0 71.3 77.4 84.5 84.5 77.4
θduct Duct surface temperature [°C] 63.7 70.5 70.5 63.7 69.9 77.1 77.1 69.9
Resistances

R₀ DC Resistance of the conductor at 20°C [Ω/km] 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

R AC Resistance of the Conductor at Operating Temperature [Ω/km] 0.12582 0.12849 0.12849 0.12581 0.12825 0.13109 0.13109 0.12824

ys Skin Effect Factor 0.00543 0.0052 0.0052 0.00543 0.00522 0.00498 0.00498 0.00522
yp Proximity Effect Factor 0.01088 0.01042 0.01042 0.01088 0.01046 0.00999 0.00999 0.01046
Losses
Wc Conductor Losses [W/m] 16.50346 16.85393 16.85375 16.50288 16.82212 17.19528 17.19503 16.82134
Wd Dielectric Losses [W/m] 0.00282 0.00282 0.00282 0.00282 0.00282 0.00282 0.00282 0.00282
Ws Metallic Screen Losses [W/m] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Wa Armor/Pipe Losses [W/m] 0.2136 0.2136 0.2136 0.2136 0.2136 0.2136 0.2136 0.2136
Wt Total Losses [W/m] 50.15963 51.21106 51.21052 50.1579 51.11563 52.2351 52.23436 51.11329
ƛ₁ Screen Loss Factor 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

ƛ₂ Armour Loss Factor + Pipe Loss Factor 0.01294 0.01267 0.01267 0.01294 0.0127 0.01242 0.01242 0.0127

Thermal resistances
T1 Thermal resistance of insulation [K.m/W] 0.58174 0.58174 0.58174 0.58174 0.58174 0.58174 0.58174 0.58174

T2 Thermal resistance of bedding/medium inside pipe-type [K.m/W] 0.04549 0.04549 0.04549 0.04549 0.04549 0.04549 0.04549 0.04549

T3 Thermal resistance of outer covering [K.m/W] 0.0739 0.0739 0.0739 0.0739 0.0739 0.0739 0.0739 0.0739

T4 External thermal resistance [K.m/W] 3.01391 3.98105 4.36089 4.30536 5.32761 6.74147 7.2831 7.10603
Others

Temperature Rise at the Surface of the Cable Due to Other


Δθint [°C] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Surrounding Elements

Induced Voltage (standing) on Armour [V/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Cables Report
CYMCAP Version 7.2 Revision 02
Study: YJLV22-1.8_3KV-3X300-8.25
Execution: YJLV22-1.8_3KV-3X300-8.25
Date: 2023/9/19 16:02:26

No. Description Unit 1


General Cable Information
1 Cable Equipment ID YJLV22-1.8-3-3X300-8.25

2 Number of Cores Three Core

3 Voltage [kV] 3

4 Conductor Area [mm²] 300.0

5 Cable Overall Diameter [mm] 65.4

6 Maximum Steady-State Conductor Temperature [°C] 90

7 Maximum Emergency Conductor Temperature [°C] 110

Conductor
8 Material Aluminum

9 Electrical Resistivity at 20°C [µΩ.cm] 2.8264

10 Temperature Coefficient at 20°C [1/K] 0.00403

11 Reciprocal of Temperature Coefficient of Resistance (BETA) [K] 228

12 Volumetric Specific Heat (SH) [J/(K*cm³)] 2.5

13 Construction Round Compact

14 Conductor Insulation System Extruded

15 Milliken Wires Construction n/a

16 Ks (Skin Effect Coefficient) 1

17 Kp (Proximity Effect Coefficient) 0.8

18 Diameter [mm] 20.6

Insulation
19 Material XLPE Unfilled

20 Thermal Resistivity [K.m/W] 3.5

21 Dielectric Loss Factor - ( tan delta ) 0.004

22 Relative Permittivity - ( epsilon ) 2.5

23 Specific Insulation Resistance Constant at 60°F - ( K ) [㏁.km] 65617.

24 Thickness [mm] 2.1

25 Diameter [mm] 24.8

Insulation Screen
26 Material Belted Cable Screen

27 Thickness [mm] 0.48

28 Diameter [mm] n/a

Armour Bedding
29 Material User Defined

30 Thermal Resistivity [K.m/W] 5

31 Thickness [mm] 1.6

32 Diameter [mm] 59.06

Armour
33 Material Magnetic Tapes User Defined

34 Electrical Resistivity at 20°C [µΩ.cm] 13.8

35 Temperature Coefficient at 20°C [1/K] 0.0045

36 Reciprocal of Temperature Coefficient of Resistance (BETA) [K] 202

37 Volumetric Specific Heat (SH) [J/(K*cm³)] 3.8

38 Cross Sectionnal Area of Tape Armour [mm²] 50.0

39 Tape lay Wound At 54 Degrees

40 Longitudinal Relative Permeability 10

41 Transverse Relative Permeability 400

42 Angular Time Delay [°] 45

43 Thickness [mm] 0.27

44 Diameter [mm] 59.6

Armour Serving
45 Material User Defined

46 Thermal Resistivity [K.m/W] 5

47 Thickness [mm] 2.9

48 Diameter [mm] 65.4

No. Description Unit 1


Specific Installation Data
49 Cable Equipment ID YJLV22-1.8-3-3X300-8.25

50 Cable Frequency [Hz] 50

51 Sheath / Shield Bonding 3 Conductor Steel Tape Armour

52 Loss Factor Constant (ALOS) 0.3

53 Duct construction Polyethylene in Concrete

54 Duct material thermal resistivity [K.m/W] 3.5

55 Inside Diameter of the Duct/Pipe [mm] 92.0

56 Outside Diameter of the Duct/Pipe [mm] 100.0

Cable ID : YJLV22-1.8-3-3X300-8.25
Cable Title YJLV22-1.8-3-3X300-8.25
Electrical Parameters
CYMCAP Version 7.2 Revision 02
Study: YJLV22-1.8_3KV-3X300-8.25
Execution: YJLV22-1.8_3KV-3X300-8.25
Date: 2023/9/19 16:02:26

No. Description Unit Cable No.1 Cable No.2 Cable No.3 Cable No.4 Cable No.5 Cable No.6 Cable No.7 Cable No.8
YJLV22-1.8- YJLV22-1.8- YJLV22-1.8- YJLV22-1.8- YJLV22-1.8- YJLV22-1.8- YJLV22-1.8- YJLV22-1.8-
1 Cable Equipment ID
3-3X300-8.25 3-3X300-8.25 3-3X300-8.25 3-3X300-8.25 3-3X300-8.25 3-3X300-8.25 3-3X300-8.25 3-3X300-8.25
Resistances

2 DC Resistance of the conductor at 20°C [Ω/km] 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

3 DC Resistance of Conductor at Operating Temperature [Ω/km] 0.12281 0.12555 0.12555 0.12281 0.1253 0.12821 0.12821 0.1253

4 AC Resistance of Conductor at 20°C [Ω/km] 0.10245 0.10234 0.10234 0.10245 0.10235 0.10225 0.10225 0.10235

5 AC Resistance of Conductor at Operating Temperature [Ω/km] 0.12582 0.12849 0.12849 0.12581 0.12825 0.13109 0.13109 0.12824

6 DC Resistance of Armor at 20°C [Ω/km] 5.52 5.52 5.52 5.52 5.52 5.52 5.52 5.52

7 DC Resistance of Armor at Operating Temperature [Ω/km] 6.82633 6.99285 6.99277 6.82606 6.97775 7.15487 7.15476 6.97738

Losses
8 Conductor Losses [W/m] 16.50346 16.85393 16.85375 16.50288 16.82212 17.19528 17.19503 16.82134

9 Dielectric Losses [W/m] 0.00282 0.00282 0.00282 0.00282 0.00282 0.00282 0.00282 0.00282

10 Metallic Screen Losses [W/m] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

11 Armor/Pipe Losses [W/m] 0.2136 0.2136 0.2136 0.2136 0.2136 0.2136 0.2136 0.2136

12 Total Losses [W/m] 50.15963 51.21106 51.21052 50.1579 51.11563 52.2351 52.23436 51.11329

Capacitance, Inductance, Impedance


13 Capacitance [µF/km] 0.749 0.749 0.749 0.749 0.749 0.749 0.749 0.749

14 Inductance of Conductor [mH/km] 0.22574 0.22574 0.22574 0.22574 0.22574 0.22574 0.22574 0.22574

15 Reactance of Conductor [Ω/km] 0.07092 0.07092 0.07092 0.07092 0.07092 0.07092 0.07092 0.07092

16 Inductance of Metallic Sheath [mH/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

17 Reactance of Metallic Sheath [Ω/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

0.125820 + 0.128490 + 0.128490 + 0.125810 + 0.128250 + 0.131090 + 0.131090 + 0.128240 +


18 Positive Sequence Impedance [Ω/km]
j0.070920 j0.070920 j0.070920 j0.070920 j0.070920 j0.070920 j0.070920 j0.070920

0.125820 + 0.128490 + 0.128490 + 0.125810 + 0.128250 + 0.131090 + 0.131090 + 0.128240 +


19 Negative Sequence Impedance [Ω/km]
j0.070920 j0.070920 j0.070920 j0.070920 j0.070920 j0.070920 j0.070920 j0.070920

0.100540 + 0.100520 + 0.100520 + 0.100540 + 0.100520 + 0.100500 + 0.100500 + 0.100520 +


20 Zero Sequence Impedance [Ω/km]
j0.000000 j0.000000 j0.000000 j0.000000 j0.000000 j0.000000 j0.000000 j0.000000

21 Surge Impedance [Ω] 17.36617 17.36617 17.36617 17.36617 17.36617 17.36617 17.36617 17.36617

Others

22 Dielectric Stress at Conductor Surface [kV/mm] n/a n/a n/a n/a n/a n/a n/a n/a

23 Dielectric Stress at Insulation Surface [kV/mm] n/a n/a n/a n/a n/a n/a n/a n/a

24 Insulation Resistance at 60°F (15.8°C) [㏁.km] 5287.69426 5287.69426 5287.69426 5287.69426 5287.69426 5287.69426 5287.69426 5287.69426

25 Reduction Factor 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

26 Charging Current for One Phase [A/km] 0.4073 0.4073 0.4073 0.4073 0.4073 0.4073 0.4073 0.4073

27 Charging Capacity of three phase system at Uo [kvar/km] 2.11638 2.11638 2.11638 2.11638 2.11638 2.11638 2.11638 2.11638

28 Voltage drop for Three Phase System [V/A/km] 0.21792 0.22255 0.22255 0.21792 0.22213 0.22706 0.22706 0.22212

29 Induced Voltage (standing) on Armour [V/km] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Cable Parameters under Normal Operation
CYMCAP Version 7.2 Revision 02
Study: YJLV22-1.8_3KV-3X300-8.25
Execution: YJLV22-1.8_3KV-3X300-8.25
Date: 2023/9/19 16:02:26

No. Symbol Description Unit Cable No.1 Cable No.2 Cable No.3 Cable No.4 Cable No.5 Cable No.6 Cable No.7 Cable No.8

YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3- YJLV22-1.8-3-


1 Cable Equipment ID
3X300-8.25 3X300-8.25 3X300-8.25 3X300-8.25 3X300-8.25 3X300-8.25 3X300-8.25 3X300-8.25

Normal Operation IEC 60287-1-1


Conductor AC Resistance
2 R₀ DC Resistance of the conductor at 20°C [Ω/km] 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

3 R' DC Resistance of Conductor at Operating Temperature [Ω/km] 0.12281 0.12555 0.12555 0.12281 0.1253 0.12821 0.12821 0.1253

4 dc Conductor Diameter [mm] 20.6 20.6 20.6 20.6 20.6 20.6 20.6 20.6

5 s Distance Between Conductor Axes [mm] 24.8 24.8 24.8 24.8 24.8 24.8 24.8 24.8

6 ks Factor Used for xs Calculation (Skin Effect) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

7 kp Factor Used for xp Calculation (Proximity Effect) 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

8 xs Component of Ys Calculation (Skin Effect) 1.01153 1.00045 1.00046 1.01155 1.00144 0.99001 0.99002 1.00146

9 xp Component of Yp Calculation (Proximity Effect) 0.90474 0.89483 0.89483 0.90476 0.89572 0.88549 0.8855 0.89574

10 ys Skin Effect Factor 0.00543 0.0052 0.0052 0.00543 0.00522 0.00498 0.00498 0.00522

11 yp Proximity Effect Factor 0.01088 0.01042 0.01042 0.01088 0.01046 0.00999 0.00999 0.01046
12 Fmag Multiplying factor due to magnetic layers 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

13 R AC Resistance of Conductor at Operating Temperature [Ω/km] 0.12582 0.12849 0.12849 0.12581 0.12825 0.13109 0.13109 0.12824

Dielectric Losses
14 tanδ Dielectric Loss Factor 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004
15 ε Insulation Relative Permitivity 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

16 C Cable Capacitance [µF/km] 0.749 0.749 0.749 0.749 0.749 0.749 0.749 0.749

17 U₀ Voltage [kV] 1.73205 1.73205 1.73205 1.73205 1.73205 1.73205 1.73205 1.73205
18 Wd Cable Dielectric Losses Per Phase [W/m] 0.00282 0.00282 0.00282 0.00282 0.00282 0.00282 0.00282 0.00282
Circulating Loss Factor

19 ƛ'₁ Screen Loss Factor Caused by Circulating Current 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Eddy Loss Factor

20 ƛ''₁ Screen Loss Factor Caused by Eddy Current 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Metallic Screen Loss factor


21 ƛ₁ Screen Loss Factor 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Armour and Pipe Loss Factor
22 Fpipe Magnetic effect factor due to pipe 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

23 Fscreen Screening effect factor 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

24 k Component for Armour Loss Factor Formula (Clause 2.4.2.4) 0.64395 0.64395 0.64395 0.64395 0.64395 0.64395 0.64395 0.64395

25 ƛ₂a Armour Loss Factor 0.01294 0.01267 0.01267 0.01294 0.0127 0.01242 0.01242 0.0127

26 ƛ₂pipe Pipe Loss Factor 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

28 ƛ₂ Armour Loss Factor + Pipe Loss Factor 0.01294 0.01267 0.01267 0.01294 0.0127 0.01242 0.01242 0.0127
Normal Operation IEC 60287-2-1

29 T₁ Thermal Resistance Between Conductor and Screen [K.m/W] 0.58174 0.58174 0.58174 0.58174 0.58174 0.58174 0.58174 0.58174

30 t₁ Insulation Thickness Between Conductor and Screen [mm] 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

31 ρTi Thermal Resistivity of Insulation [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

32 T₂ Thermal Resistance Between Sheath and Armour [K.m/W] 0.04549 0.04549 0.04549 0.04549 0.04549 0.04549 0.04549 0.04549

33 t₂ Thickness Between Sheath and Armour [mm] 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

34 ρTB Thermal Resistivity Between Screen and Armour [K.m/W] 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

35 T₃ Thermal resistance of outer covering [K.m/W] 0.0739 0.0739 0.0739 0.0739 0.0739 0.0739 0.0739 0.0739

36 t₃ Thickness of Outer Covering [mm] 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

37 ρTS Thermal Resistivity of Serving [K.m/W] 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

Cable in Ducts

38 U Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1 1.87 1.87 1.87 1.87 1.87 1.87 1.87 1.87

39 V Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1 0.312 0.312 0.312 0.312 0.312 0.312 0.312 0.312

40 Y Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1 0.0037 0.0037 0.0037 0.0037 0.0037 0.0037 0.0037 0.0037

41 θm Mean Temperature of the Medium Filling the Space [°C] 67.9 74.7 74.7 67.9 74.0 81.2 81.2 74.0

42 T₄' Thermal Resistance of the Medium Inside the Duct/Pipe [K.m/W] 0.39922 0.38582 0.38583 0.39924 0.387 0.37363 0.37363 0.38703

43 Do Outside Diameter of the Duct/Pipe [mm] 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0
44 Di Inside Diameter of the Duct/Pipe [mm] 92.0 92.0 92.0 92.0 92.0 92.0 92.0 92.0

45 ρT Thermal Resistivity of the Duct/Pipe Material [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

46 T₄'' Thermal Resistance of the Duct/Pipe [K.m/W] 0.04645 0.04645 0.04645 0.04645 0.04645 0.04645 0.04645 0.04645

47 T₄''' Thermal Resistance of the Surrounding Medium [K.m/W] 2.56825 3.54878 3.92862 3.85967 4.89417 6.32139 6.86302 6.67255

Ducts Buried in the soil

48 T₄''' Thermal Resistance of the Surrounding Medium [K.m/W] 2.56825 3.54878 3.92862 3.85967 4.89417 6.32139 6.86302 6.67255

49 T₄ Total External Thermal Resistance [K.m/W] 3.01391 3.98105 4.36089 4.30536 5.32761 6.74147 7.2831 7.10603

Temperature Rise at the Surface of the Cable Due to Other


50 Δθint [°C] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Surrounding Elements

51 I Cable Core Current Ampacity [A] 362.2 362.2 362.2 362.2 362.2 362.2 362.2 362.2
Cable Short Circuit
CYMCAP Version 7.2 Revision 02
Study: YJLV22-1.8_3KV-3X300-8.25
Execution: YJLV22-1.8_3KV-3X300-8.25
Date: 2023/9/19 16:02:26

Symbol Description Unit Circuit No. 1


Cable Equipment ID YJLV22-1.8-3-3X300-8.25

Conductor Armour

ABC ABC
t Short Circuit Time [s] 0.1 0.1
K Current Carrying Component Material Constant [As¹/₂ / mm²] 148.1 78.2
S Layer Cross-Sectional Area [mm²] 300.0 50.0
θi Initial Temperature [°C] 76.6 72.6
β Reciprocal of temperature coefficient at 0°C [K] 228.1 202.2
θf Final Temperature [°C] 250.0 200.0
Iad Adiabatic Short Circuit Current [A] 94324.1 7633.6
Inad Non Adiabatic Short Circuit Current [A] 94817.3 7747.7

Symbol Description Unit Circuit No. 2


Cable Equipment ID YJLV22-1.8-3-3X300-8.25

Conductor Armour

ABC ABC
t Short Circuit Time [s] 0.1 0.1
K Current Carrying Component Material Constant [As¹/₂ / mm²] 148.1 78.2
S Layer Cross-Sectional Area [mm²] 300.0 50.0
θi Initial Temperature [°C] 83.4 79.3
β Reciprocal of temperature coefficient at 0°C [K] 228.1 202.2
θf Final Temperature [°C] 250.0 200.0
Iad Adiabatic Short Circuit Current [A] 91987.9 7388.1
Inad Non Adiabatic Short Circuit Current [A] 92468.9 7498.5

Symbol Description Unit Circuit No. 3


Cable Equipment ID YJLV22-1.8-3-3X300-8.25

Conductor Armour

ABC ABC
t Short Circuit Time [s] 0.1 0.1
K Current Carrying Component Material Constant [As¹/₂ / mm²] 148.1 78.2
S Layer Cross-Sectional Area [mm²] 300.0 50.0
θi Initial Temperature [°C] 83.4 79.3
β Reciprocal of temperature coefficient at 0°C [K] 228.1 202.2
θf Final Temperature [°C] 250.0 200.0
Iad Adiabatic Short Circuit Current [A] 91989.1 7388.3
Inad Non Adiabatic Short Circuit Current [A] 92470.1 7498.7

Symbol Description Unit Circuit No. 4


Cable Equipment ID YJLV22-1.8-3-3X300-8.25

Conductor Armour

ABC ABC
t Short Circuit Time [s] 0.1 0.1
K Current Carrying Component Material Constant [As¹/₂ / mm²] 148.1 78.2
S Layer Cross-Sectional Area [mm²] 300.0 50.0
θi Initial Temperature [°C] 76.6 72.6
β Reciprocal of temperature coefficient at 0°C [K] 228.1 202.2
θf Final Temperature [°C] 250.0 200.0
Iad Adiabatic Short Circuit Current [A] 94327.9 7634.0
Inad Non Adiabatic Short Circuit Current [A] 94821.1 7748.1

Symbol Description Unit Circuit No. 5


Cable Equipment ID YJLV22-1.8-3-3X300-8.25

Conductor Armour

ABC ABC
t Short Circuit Time [s] 0.1 0.1
K Current Carrying Component Material Constant [As¹/₂ / mm²] 148.1 78.2
S Layer Cross-Sectional Area [mm²] 300.0 50.0
θi Initial Temperature [°C] 82.8 78.7
β Reciprocal of temperature coefficient at 0°C [K] 228.1 202.2
θf Final Temperature [°C] 250.0 200.0
Iad Adiabatic Short Circuit Current [A] 92200.2 7410.5
Inad Non Adiabatic Short Circuit Current [A] 92682.3 7521.2

Symbol Description Unit Circuit No. 6


Cable Equipment ID YJLV22-1.8-3-3X300-8.25

Conductor Armour

ABC ABC
t Short Circuit Time [s] 0.1 0.1
K Current Carrying Component Material Constant [As¹/₂ / mm²] 148.1 78.2
S Layer Cross-Sectional Area [mm²] 300.0 50.0
θi Initial Temperature [°C] 90.0 85.8
β Reciprocal of temperature coefficient at 0°C [K] 228.1 202.2
θf Final Temperature [°C] 250.0 200.0
Iad Adiabatic Short Circuit Current [A] 89706.7 7147.1
Inad Non Adiabatic Short Circuit Current [A] 90175.8 7253.9

Symbol Description Unit Circuit No. 7


Cable Equipment ID YJLV22-1.8-3-3X300-8.25

Conductor Armour

ABC ABC
t Short Circuit Time [s] 0.1 0.1
K Current Carrying Component Material Constant [As¹/₂ / mm²] 148.1 78.2
S Layer Cross-Sectional Area [mm²] 300.0 50.0
θi Initial Temperature [°C] 90.0 85.8
β Reciprocal of temperature coefficient at 0°C [K] 228.1 202.2
θf Final Temperature [°C] 250.0 200.0
Iad Adiabatic Short Circuit Current [A] 89708.4 7147.2
Inad Non Adiabatic Short Circuit Current [A] 90177.5 7254.0

Symbol Description Unit Circuit No. 8


Cable Equipment ID YJLV22-1.8-3-3X300-8.25

Conductor Armour

ABC ABC
t Short Circuit Time [s] 0.1 0.1
K Current Carrying Component Material Constant [As¹/₂ / mm²] 148.1 78.2
S Layer Cross-Sectional Area [mm²] 300.0 50.0
θi Initial Temperature [°C] 82.8 78.7
β Reciprocal of temperature coefficient at 0°C [K] 228.1 202.2
θf Final Temperature [°C] 250.0 200.0
Iad Adiabatic Short Circuit Current [A] 92205.4 7411.1
Inad Non Adiabatic Short Circuit Current [A] 92687.6 7521.8
Part 7

Cyclic daily load factor


CYCLIC FACTOR CALCULATION

Cyclic Load

The cyclic load depends on the power generation of PV plant. From PVsyst softw
the approximate maximum power output at 16th, May are considered for cyclic lo

Array
Time Value of
Output Yi
(h) Yi
(kW)
0 0 0.000 Y11
1 0 0.000 Y10
2 0 0.000 Y9
3 0 0.000 Y8
4 3359 0.007 Y7
5 149614 0.315 Y6
6 378870 0.797 Y5
7 448192 0.943 Y4
8 465271 0.979 Y3
9 471608 0.992 Y2
10 475181 1.000 Y1
11 474147 0.998 Y24
12 470960 0.991 Y23
13 465830 0.980 Y22
14 454378 0.956 Y21
15 434041 0.913 Y20
16 358381 0.754 Y19
17 161799 0.340 Y18
18 11492 0.024 Y17
19 0 0.000 Y16
20 0 0.000 Y15
21 0 0.000 Y14
22 0 0.000 Y13
23 0 0.000 Y12

The loss load factor can be obtained:

= 0.46