Circuit Breaker - For Switchayrd
Circuit Breaker - For Switchayrd
CLIENT : M/s.
PROJECT : Sheet No 1 of 9
2. Equipment Details :
LOA No :
Make :
Type :
Sl. No. : Rph : Y ph : B ph :
Mfg Year :
Feeder Name :
Rated KV :
Control Voltage : Close Coil Voltage : Trip Coil Voltage :
Rated Breaking Capacity :
Rated Making Capacity :
R ph Y ph B ph
Make
Model
Sl. No.
Mfg Year
CLIENT : M/s.
PROJECT : Sheet No 2 of 9
R ph Y ph B ph
Air Receiver No
Control Block No
Pneumatic Drive No
Magnetic Ventil No
Make Volt
Sl. No. Amperes
Type HP / KW
Year of Manufact Setting
(Thermal overload)
Make
Sl. No.
Type
Discharge
Capacity
Year of Manufact
CLIENT : M/s.
PROJECT : Sheet No 3 of 9
Circuit Reference Factory. Setting Value Site Setting Value Make Remarks
Block De block Block De block
Tripping Circuit – I
Tripping circuit—2
Closing circuit
Auto re closing ckt
Low| high pressure
Alarm circuit
Icu auto setting
Icu safety valve
Operations
CLIENT : M/s.
PROJECT : Sheet No 4 of 9
CLIENT : M/s.
PROJECT : Sheet No 5 of 9
Note : Incase case wiring for remote operation is not ready, please indicate Terminal number along
with wire ferrule number in switch cubicle where remote cables shall be terminated. Remote
operation can be checked from these terminals.
CLIENT : M/s.
PROJECT : Sheet No 6 of 9
9. IR Value with respect to Earth with breaker closed, Earth switch and Isolator open :
CLIENT : M/s.
PROJECT : Sheet No 7 of 9
CLIENT : M/s.
PROJECT : Sheet No 8 of 9
12. Check for Annunciation in control room as per the following formats and record the reading :
Sl.No. Description of test Source of Window Result Remarks
initiation Description OK / Not OK
1. Switch off the DG switch in Control cubicle DC Source I/II DC
control cubicle switch ON/OFF fail / AC fail
2. Switch off the AC switch in Control cubicle AC Source I/II DC
control cubicle switch ON/OFF fail / AC fail
3. Short the Alarm contacts of Density monitor SF6 Gas
SF6 Gas density monitor Density Low
(R ph)
4. Short the Alarm contacts of Density monitor SF6 Gas
SF6 Gas density monitor Density Low
(Y ph)
5. Short the Alarm contacts of Density monitor SF6 Gas
SF6 Gas density monitor Density Low
(B ph)
6. Remove the cable Density monitor Operation /
connected to density Closing lockout
monitor (R ph)
7. Remove the cable Density monitor Operation /
connected to density Closing lockout
monitor (Y ph)
8. Remove the cable Density monitor Operation /
connected to density Closing lockout
monitor (B ph)
9. Give tripping command to Pole descripancy Breaker pole
R ph only and check the relay at breaker descripancy
operation of pole cubicle
discrepancy relay
10. Give tripping command to Pole descripancy Breaker pole
Y ph only and check the relay at breaker descripancy
operation of pole cubicle
discrepancy relay
11. Give tripping command to Pole descripancy Breaker pole
B ph only and check the relay at breaker descripancy
operation of pole cubicle
CLIENT : M/s.
PROJECT : Sheet No 9 of 9
discrepancy relay
Note : The tripping details are to be checked as per the scheme approved by engineering.
13. Remarks :