Professional Documents
Culture Documents
00025250
00025250
Kevwordq - Short circuit, calculation of short For both induction and synchronous motors, the current
circuit currents, ANSI/IEEE C37.010-1979, dynamic is going into the motor resulting in a Thevenin voltage
simulation, breaker duty. which is smaller in magnitude. Short circuit currents
calculated near generators by the standards can be
Abstract - Selection of electrical equipment is lower than actual currents and those near motors can
influenced by the expected mangitudes of the short be larger than the actual currents.
circuit currents to which they will be exposed. The The standards were developed when computational
widely-used application guides ANSI/IEEE C37.010-1979 tools were quite limited. Today computer technology
and C37.5-1979 for ac high voltage circuit breakers as has provided machines with practically unlimited memory
well as the IEC standard used in Europe recommend address space and very fast computation speeds which
procedures for determining circuit breaker duty. These can be used in an office environment. Taking advantage
procedures utilize approximate calculations of fault of the present computer technology, a new procedure has
currents. been developed to calculate short circuit currents,
This paper presents a new method of more This procedure includes modeling the ac decrement based
accurately approximating fault currents. Calculation on the rotor circuit of each source and the dc
of short circuit currents by the new method and by the decrement based on the approximate X/R ratio at the
ANSI method are compared for an industrial system. fault location. This calculation gives an excellent
approximation to the short circuit current without
resorting to a complete three phase dynamic simulation.
Results from this method are compared with those
INTRODUCTION obtained from the standard and from a dynamic
simulation run using an electromagnetics transient
The principal function of a circuit breaker i s to program.
carry load current while being able to interrupt short
circuit currents without being damaged. The magnitude
of the short circuit current depends on what sources Calculation of AC Decrements
are on-line in the system, which transmission lines are
in service, and the fault location. Most studies are The alternating current component results from
concerned with the largest possible short circuit decaying machine internal flux linkages behind constant
currents to determine the duty required of the subtransient impedances. The derivation of how the
breakers. For an industrial plant which includes many alternating current can be approximated with acceptable
motors, the proper selection of breakers is important accuracy for several cycles after fault application is
since overrated breakers will have an economic impact shown in Appendix A. The decaying generator fluxes are
on the design of the plant, while underrated breakers modeled for machines by the, following equations:
will result in failures with loss in terms of
replacement of breakers and interrupted plant
production.
For most cases, the most severe fault is
recognized to be a three phase fault which consists of +(&-&)e -t/T"dz]
an ac component and a unidirectional dc component. The
ANSI/IEEE method requires two sets of calculations to
determine the duty within a half cycle o f fault
initiation (close and latch duty), and at the time of
the interruption (contact parting). To account for the
ac decrement, multiplying factors are used for the
Thevenin source impedance of each source in the system.
For the dc decrement calculations of fault current, the
X/R ratio is calculated by solving the R network
independently from the X network. All calculations
are based on the network operating before the fault at
flat conditions, i.e. no load current flowing through
the sources. For the close and latch duty, the short
circuit current obtained from the E/X calculation is
normally multiplied by 1.6 to obtain the total RMS of +(&-&)e -t/T"q2]
the current. For interrupting duty a multiplying
factor is obtained from tables for various breakers
using the X/R ratios. Guidance in using these tables
i s provided by articles which have been written after
the publication of the standards. [2l
It may be observed that the treatment of sources
in these standards is not realistic. Usually the
sources are carrying load. A Thevenin equivalent model e
of a source would consist of a voltage which does not &qmLe
change at fault initiation and which is located behind where
some impedance. For a generator carrying lagging power
factor load, this voltage will be larger in magnitude
than In the case of no load which the standards assume.
For generators absorbing vars, this voltage i s smaller.
88CH2565-0/88/0000-1460$01.000 1988 IEEE
~
0.0491 + 0.0409 +
j 0.0231 Q j 0.0391
Q
4-POLE 6-FQLE
CPOLE IO-POLE
c
LlGHls LIGHYS
APPENDIX A
The machine i s represented in the system by the
subtransient voltage behind the subtransient reactance.
Derivation of the Machine's Subtransient Flux as With the fault we can represent the circuit as
Function of Time Durinq A Three Phase Short Circuit
4: (t = ( L:+Le) id (t (A.7)
Assume a three phase fault applied some distance from a
synchronous machine. The external inductance is L
Then the short circuit current for the direct axis ise
. Substituting equation (1) for id(t) in equation (7).
yields
ld(t) = - EI EI e-t/Tdz
- Ld+L,
+
Ld +Le LA+Le
+ % -k e-t/Tl;z (A.1)
L;+Le LA+Le
1462
From equations (2) and ( 3 ) Substituting equations B.l and 8.2 for ibefore and
(A.9) iafter in equation 8.4 gives
and
1463
Table 1. Synchronous Machine Data on Machine Base
*X xs
- radians; values for motors 100 hp or smaller are assumed
1
I
HP Poles kV kVA A RI* R, XI X, X,*
--
io00 4 13.2 4275. 187. .0059 .0042 .I35 .075 .166 4.161 .0690
!OOO 6 4.0 1767. 256. .0106 .0112 .140 .lo9 .185 3.820 .1148
IO00 6 4.0 877.8 127. .0159 .0125 .140 .082 .I72 3.860 .0175
1000 6 2.3 877.8 220. .0159 .0125 .I40 .082 .I72 3.860 .0175
1000 2 2.3 834.6 214. .0085 .0078 .141 .087 .178 6.204 .0469
9 300 4 2.3 277.7 69.7 .0185 .0103 .082 .134 .155 2.919 .0036
100 4 .46 92.4 116. .0267 .0126 .099 .175 .I70 3.738 .oooo
17 75 4 .46 70.8 88.9 .0246 .0114 .I05 .205 .I57 3.734 .oooo
17 40 4 .46 41.4 52.0 .0279 .0156 .099 .179 .166 2.396 .oooo
I I I I I
*For calculation of various time constants and X/R ratio per NEMA
standard MGI-1.58 (1980)
1464
Table 4. Fault Currents a t One-Half Cycle
Proposed
Short
I
1 I
Proposed Short C i r c u i t
ANSI (Separate R+X) Dynamic Simulation Calculation Comparison o f RMS Currents
I
raulted
Bus
Bus
kV Fact Ka-RMS
AC+DC
Ka-RMS 1 DC
Ka
AC
Ka-RMS
DC+AC
Ka-RMS Ka
DC+AC
Ka-RCIS *loo%
I DC
1 I
1 138 6.393 .594 5.673 5.969 5.99 12.08 5.01
2 13.8 1.0% 27.234 30.07 18.28 19.76 26.85 16.72 20.28 26.3 11.99 -2.05
3
4
13.8
13.8
1.00
1.00
23.39
24.01
23.39
24.01
2.72
3.57
17.60
17.96
17.81 1.54
18.31
5.704 2.10
536
17.63
18.05
17.69 31.33 - .67
18.17 31.33 -.76
5
6
7
8
9
13.8
13.8
13.8
2.4
2.4
1.00
1.00
1.00
1.00
1.00
24.87
24.87
25.49
30.413
20.417
24.87
24.87
25.49
30.413
20.417
1.83 I
1.83
7.28
9.63
1 18.43
18.43
18.79
25.19
18.52 1.33
18.52 1.33
20.16 4.87
26.97 8.99
17.56 25
18.50
18.50
19.06
25.73
17.09
18.56
18.56
19.68
27.26
17.09
34.29
34.29
26.44
12.77
.22
.22
-2.38
1.08
16.27 -2.68
10
11
12
13
14
4.16
4.16
4.16
4.16
.48
1.026
1.07
1.07
1.00 I
I 45.42
33.04
33.886
23.89
12.795
46.58
35.37
36.25
23.89
12.795 :% I
23.65
18.G
15.747
43.92 25.57
33.26 24.03
35.26 24.99
18.95 269
15.753 .379
33.93
23.48
23.43
17.78
16.21
42.48
33.60
34.26
17.78
6.06
6.34
2.81
26.07
-3.28
1.02
-2.84
-6.17
16.22 -18.78 2.96
15 .48 21.52 21.52 2.027 18.813 18.922 1.8% 19.94 20.03 13.73 5.86
16 .48 18.288 18.288 2.199 17.884 18.019 2.027 18.76 18.87 1.49 4.72
17 .48 12.804 12.804 .658 11.342 11.361 .605 11.775 11.79 12.70 3.78
18 .48 15.649 15.649 .087 14.211 14.211 .035 14.646 14.646 10.12 3.06
19 .48 2.676 2.676
.. .651 3.019 3.089 -622 3.163 3.223 -13.37
1
1.9
20 208 9.448 9.448 .512 10.353 10.366 .457 10.488 10.498 -8.86 1.27
21 208 3.270 3.270
22 .
208 3.984 3.984
279
.003 I 3.353
4.076
3.354 242
4.0761 0
3.317
4.320
3.326
4.32
-2.50
-2.26
-.83
5.99
1465
Table 6. Fault Currents at 30 Cycles
Proposed
ANSI Dynamic Short Circuit
Separate R+X) Simulation Calculation Comparison 0' ?MS Currents
ANSI -1 PrODOSed -1
Fau 1 ted Bus Simulation Si mu 1 at ion
Bus kV Ka-RMS Ka-RMS *loo% *loo%
1466