RMS ELECTRO MECH BUILDERS INCORPORATED

Address: #8 Montevista St., El Monteverde Subd., San Juan, Taytay, Rizal, Philippines 1920
Tel. Nos.: (632) 660-9135 / (632) 213-0097 / (0917) 866-0264 | E-mail Add: rmselectro@yahoo.com

Contract Order No.: Doc. No: rms~dol/sel-001


3002268
SEL-387 PROTECTION TEST RECORDS Date Tested: 24-Sep-23
PURPOSE: Initial New Setting Routine x Page: 1 of 2

CLIENT NAME: CLARK ELECTRIC DISTRIBUTION CORP.


LOCATION: BLDG. N2830 BAYANIHAN ST., CLARK FIELD, PAMPANGA
SUBSTATION: CEDC 100MVA, 230/69kV (T5) @ CDC Dolores Substation

[RELAY INFORMATION]
Relay Identifier: DOLORES SUBSTATION
Terminal Identifier: TRANSFORMER #5 (T5)
Make/Model: SEL/387E
Serial Number: 1160950243
Protection: Main-2 (Transformer Differential Protn.)

[PROTECTION SETTINGS]
SETTING DESCRIPTION RANGE VALUE
DIFFERENTIAL PROTECTION
E87 TRANSFORMER DIFFERENTIAL ENABLE (Y,N) Y
TAP1 WDG1 CURR TAP (0.5 - 31.0 A) 1.05
TAP2 WDG2 CURR TAP (0.5 - 31.0 A) 3.49
087P OPERATE CURR LEVEL (0.10 - 1.00 TAP) 0.48
SLP1 RESTRAINT SLOPE1 (5 - 90%) 30%
SLP2 RESTRAINT SLOPE2 (5 - 90%) 70%
IRS1 RESTRAINT SLOPE1 LIMIT (1.0 - 20.0 TAP) 4.0
U87P UNRESTRAINT CURR LEVEL (1.0 - 20.0 TAP) 15
PCT2 2ND HARM BLOCK (OFF, 5 - 100%) 20%
WINDING 1 MAXIMUM PHASE TIME OVERCURRENT
51P1P PHASE TOC LEVEL (OFF, 0.50 - 16.00 A) 1.30
51P1C PHASE TOC CURVE (U1-U5 & C1-C5) C1
51P1TD PHASE TOC TDIAL (0.05 - 1.00) 0.10
WINDING 2 MAXIMUM PHASE TIME OVERCURRENT
51P2P PHASE TOC LEVEL (OFF, 0.50 - 16.00 A) 4.35
51P2C PHASE TOC CURVE (U1-U5 & C1-C5) C1
51P2TD PHASE TOC TDIAL (0.05 - 1.00) 0.10
WINDING 1 NEUTRAL TIME OVERCURRENT
51N1P NEUTRAL TOC LEVEL (OFF, 0.50 - 16.00 A) 0.50
51N1C RES TOC CUREVE (U1-U5 & C1-C5) C1
51N1TD RES TOC TDIAL (0.05 - 1.00) 0.10
WINDING 2 NEUTRAL TIME OVERCURRENT
51N2P NEUTRAL TOC LEVEL (OFF, 0.50 - 16.00 A) 1.05
51N2C RES TOC CUREVE (U1-U5 & C1-C5) C1
51N2TD RES TOC TDIAL (0.05 - 1.00) 0.10
Contract Order No.: Doc. No: rms~dol/sel-001
3002268
SEL-387 PROTECTION TEST RECORDS Date Tested: 24-Sep-23
PURPOSE: Initial New Setting Routine x Page: 2 of 2

[RELAY TEST RESULTS]

I. Testing of Setting Differential Protection:


87T (W1 Pickup / Trip Time)
Injected Current @ Phase: A-B-C A-N B-N C-N A-B B-C C-A
Measured Value in amps. 0.510 0.760 0.760 0.760 0.510 0.510 0.510
Measured Time in msec. No time No time No time No time No time No time No time
Results Failed Failed Failed Failed Failed Failed Failed
87T (W2 Pickup / Trip Time)
Injected Current @ Phase: A-B-C A-N B-N C-N A-B B-C C-A
Measured Value in amps. 1.670 2.550 2.550 2.550 1.690 1.690 1.690
Measured Time in msec. No time No time No time No time No time No time No time
Results Failed Failed Failed Failed Failed Failed Failed

87T (Trip Characteristic Test)


Test Values
Restraint Differential
W1 Side W2 Side Results
Current pu Current pu
Amps Angle Amps Angle
0.51 0 1.67 180 0.48 0.01 No tripped
0.77 0 0.91 180 0.50 0.48 No tripped
2.50 0 6.10 180 2.07 0.64 No tripped
3.00 0 7.40 180 2.50 0.75 No tripped
4.00 0 9.80 180 3.32 1.01 No tripped
5.00 0 12.20 180 4.14 1.28 No tripped
6.00 0 13.80 180 4.85 1.78 No tripped
7.00 0 15.40 180 5.55 2.28 No tripped

[REMARKS]
Test results above were indicated on LED Trip only.
The output trip relay were not operate.
The device were found to be defective and/or operates malfunction.
We recommend for corrective measures and/or replace the unit as soon as possible.

[ Approval ] [ Name ] [ Signature ] [ Date ]

Tested By: Engr. Ruel H. De Villa 24-Sep-23

Witnessed By: CEDC Representative