User Control Manual - en - 36360756
User Control Manual - en - 36360756
ELWLCH
Translation of original instructions
Index i33
Edition 06.2021
Software specification - user manual
ELW LC H - TRANSLATIO N O F O R IGINAL INST R U CT IO N S
Table of contents
1.Introduction...................................................................................................................................................4;
2.User interface..............................................................................................................................................4
2.1.Keys description.........................................................................................................................4;
2.2.Led and Display...........................................................................................................................5
3.States................................................................................................................................................................. 6
3.1.System OFF................................................................................................................................... 6;
3.2.System ON.................................................................................................................................... 6;
3.3.System StandBy........................................................................................................................ 6
4.Alarms...............................................................................................................................................................7;
5.Setup................................................................................................................................................................. 11
1. Introduction
ELWMCH is a software designed for the control of liquid chillers.
The main functions of the control are:
• Compressor control, control of condenser fan, control of the pump in normal mode and in
antifreeze mode, control of the antifreeze heating resistance and of the Hot Gas Bypass.
• Temperature regulation on absolute or differential (in tracking mode) set point.
• Fan speed regulation on pressure (absolute and dynamic) / temperature.
• The possibility to put the unit in cooling mode.
• The pre-heating resistance control.
• Starting functions at low temperatures.
• Alarms management.
• Manual control of the components.
• Modbus serial connection.
2. User interface
2.1. Keys description
There are 4 keys on the front of the instrument. Each key provides:
• A ‘direct’ action (indicated on the key itself);
• An ‘associated’ function (indicated on the front of the instrument, at the corresponding key);
• A ‘combined’ action of two keys.
• It raises a value
UP
• Go to the next menu
• It decreases a value
DOWN
• Go to the previous menu
[UP NOT
[Enter in Programming
+ APPLICABLE
Menu BIOS]
DOWN] FOR THE USER
On hold red A user must activate but there are waiting times
Heating green
The display visualized the set size/resource for the main visualization. In case of alarm, it will
alternate to the alarm code Exx (in case of more alarms, the code with lower index, see chapter
“4. Alarms”).
• The alarm icon lights up in case of any active alarm.
• The cooling icon indicates that the compressor is active.
• The heating icon indicates that the electrical resistance is active.
• Flashing StandBy icon indicates that the control is switched off from digital contact; if the icon
is fixed, it’s switched off from the keyboard.
• The ‘on hold’ icon switches on at minimum waiting time, it’s used to understand the status of
the compressor
Degrees centigrade
Pressure (Bar)
Relative humidity (%RH) Used for percentage values
3. States
Below the possible states of the system are described.
3.2. System ON
To enter in ON state, it’s necessary to keep pressed for 3 seconds the “set” key from the OFF
state. Also the digital input for StandBy must be OFF.
In this state all the control work normally, except the antifreeze.
The alarms are active.
4. Alarms
Find below the list of possible alarms:
Text Description
HP HP alarm with automatic reset
HPM HP alarm with manual reset
LP LP alarm with automatic reset
LPM LP alarm with manual reset
FF Flow alarm with automatic reset
FFM Flow alarm with manual reset
LEPH Tank level wrong phase alarm
tHOA Compressor thermic alarm
P2TH Pump thermic alarm 2
FF1 Flow alarm circuit 1
FF2 Flow alarm circuit 2
AF Antifreeze alarm
Ht High temperature alarm
LT Low temperature alarm
HtrL High differential temperature alarm
LtrL Low differential temperature alarm
AfPB Alarm of temperature antifreeze probe broken
LTPB Alarm of supply temperature probe broken
PTPB Alarm of pressure transducer broken
EtPB Alarm of ambient temperature probe broken
RTPB Alarm of return temperature probe broken
HtSC High temperature alarm of the secondary circuit
LTSC Low temperature alarm of the secondary circuit
HrLS High differential temperature alarm of the secondary circuit
LrLS Low differential temperature alarm of the secondary circuit
HrHt High temperature alarm in heating
HrLt Low temperature alarm in heating
CTPB Alarm of condensing temperature probe broken
ERR System error alarm
Flow alarm
If the pump is ON and the digital input FF is ON, FF alarm triggers if remains for AFFD time (Flow
alarm delay time) that stops the compressor immediately and the pump after AFPD (Delay time
of pump switching off from flow alarm). If the alarm triggers 4 times in less than 3 hours, the
alarm becomes with manual reset, Otherwise it remains with automatic reset.
For the automatic reset, the control tries to restart the pump after AFID (Reset time of flow alarm
in automatic mode) from the switching off of the pump. At the start, the flow alarm is hidden for
AFDS time (Flow alarm delay time from start).
Antifreeze alarm
If the compressor is ON and the antifreeze temperature goes below AAFS value (Setpoint
Antifreeze alarm), the antifreeze alarm triggers that stops the compressor. The alarm remains
until the antifreeze temperature doesn’t go above AAFS + AAFH (Antifreeze alarm hysteresis).
The alarm has manual reset (press ESC for 3 seconds).
If the compressor is ON and the regulation temperature increases above the value AHtS, high
temperature alarm is triggered. The alarm remains until the regulation temperature goes below
AHtS – AHtH. The triggering of the alarm can be delayed from the commissioning of the system
of AHtd minutes. The alarm is automatically reset. In case of active heating mode the parameters
are dedicated (AHrH. ArHd, ArHH).
If the compressor is ON and the regulation temperature goes below the value ALtS, low
temperature alarm is triggered. The alarm remains until the regulation temperature goes above
ALtS + ALtH. The triggering of the alarm can be delayed from the commissioning of the system
of ALtd minutes. The alarm is automatically reset. In case of active heating mode the parameters
are dedicated (AHrL. ArLd, ArLH).
If AHrt > 0, when the supply temperature > ambient temperature + AHrt differential high
temperature alarm triggers. It’s inhibited for Hrtd minutes from unit starts. The alarm goes off
when the supply temperature returns < ambient temperature + AHrt – HrtH.
Se ALrt < 0, when the supply temperature < ambient temperature + ALrt differential low
temperature alarm triggers. It’s inhibited for Lrtd minutes from unit starts. The alarm goes off
when the supply temperature returns > ambient temperature + ALrt + LrtH.
If we are in System ON and the regulation temperature goes below the value ALSC, the low
temperature alarm of the secondary circuit triggers. The alarm remains until the regulation
temperature doesn’t go above ALSC + LSCH. Alarm intervention can be delayed from power ON
of the system of LSCd minutes. The alarm is automatically reset.
If HrSC > 0, when secondary circuit temperature > ambient temperature + HrSC, the alarm of high
differential temperature of the secondary circuit triggers. It’s inhibited for HrSd minutes from unit
starts. The alarm goes off when secondary circuit temperature returns < ambient temperature +
HrSC – HrSH.
Se LrSC < 0, when secondary circuit temperature < ambient temperature + LrSC, the alarm of low
differential temperature of the secondary circuit triggers. It’s inhibited for LrSd minutes from unit
starts. The alarm goes off when secondary circuit temperature returns > ambient temperature +
LrSC + LrSH.
Expansion alarm
If a function is parametrically active on the expansion and the communication between control
and expansion fails, the Expansion alarm is displayed. All the inputs of the expansion are not
considered.
5. Setup
Find below the list of parameters at user level.
SET menu
To enter in the quick menu SEt, click SEt key. Then with the arrows it’s possible to scroll through
the sub-menus and select by pressing the SEt key. The parameters that represent the state of
inputs / outputs are only read.
SET MENU
Par. Description Modbus
SP Setpoint 16384
SPrL Relative setpoint 16386
SP2 Setpoint 2 16387
AHtS High temperature alarm set 16480
ALtS Low temperature alarm set 16483
AHrt Set of high differential temperature alarm 16486
ALrt Set of low differential temperature alarm 16489
SCSP Setpoint SC 16534
SCSr Differential setpoint SC 16535
AHSC High temperature alarm set SC 16539
ALSC Low temperature alarm set SC 16542
HrSC Set of high differential temperature alarm SC 16545
LrSC Set of low differential temperature alarm SC 16548
Pbtd Timeout probe display 16562
rEL MENU
Par. Description Modbus
rEL Firmware version 8988
Al MENU
Par. Description Modbus
AFtt Antifreeze temperature (AI1) 8960
AMbt Ambient temperature (AI2) 8961
CPr Condensing pressure (AI3) 8962
SUPt Supply temperature (AI4) 8963
rEtt Return temperature (AI5) 8964
tSC Secondary circuit temperature (AIE1) 8965
AO MENU
Par. Description Modbus
COUt Output condensing fan (TRIAC e AO3) 8967
HOUt Resistance output (AO1) 8969
Cdig Output condensing fan ON-OFF (AO2) 8970
SCO Output of modulating SC valve (AO4) 8968
di MENU
Par. Description Modbus
FSdi Input flow alarm 8971
di MENU
Par. Description Modbus
HPdi Input HP alarm 8972
LPdi Input LP alarm 8973
Ctdi Input cooling thermic alarm 8974
LPHd Input level alarm / phase sequence 8975
Sbdi Remote StandBy contact 8976
PtH2 Input thermic pump 2 alarm 8977
FFC1 Input alarm FF1 8978
FFC2 Input alarm FF2 8979
HrDi Heating input mode 8989
dO MENU
Par. Description Modbus
CPdO Output compressor 8980
PUdO Output pump 8981
EEdO Output EEV enabling 8982
ALdO Output alarm 8983
Hgbd Output HGB 8984
P2dO Output pump 2 8985
F1dO Output alarm FF1 8986
F2dO Output alarm FF2 8987
PAr menu
Before entering in the menu to modify the parameters, it’s necessary to enter the password for
parameter level access. The possible levels are 3: 0, 1, 2. The password for level 2 is 19, while the
password for level 1 is 13. The level 0 is the user level and there isn’t a password to access it. To
enter the password, go in Programming menu, go to PASS menu, enter the password, then exit
and go to parameters menu PAR. To enter in Par menu, press SEt and then scroll the menus and
select the one you want.
REG MENU
Par. Description MIN MAX U.M. DEF. LIV. Modbus
SP Setpoint LOSP UPSP °C 150 0 16384
SPrL Relative Setpoint -500 500 °C 0 0 16386
SP2 Setpoint 2 LOSP UPSP °C 200 0 16387
ALARM MENU
Par. Description MIN MAX U.M. DEF. LIV Modbus
AHtS High temperature alarm set -40 100 °C 40 0 16480
AHtd Alarm of high temperature delay time at start 0 1000 min 10 0 16481
ALtS Set low temperature alarm -40 100 °C 8 0 16483
ALtd Alarm of low temperature delay time at start 0 1000 min 10 0 16484
AHrt Set alarm of high differential temperature 0 100 °C 0 0 16486
Hrtd Delay time of differential high temperature alarm at start 0 1000 min 10 0 16487
ALrt Set alarm of low differential temperature 0 100 °C 0 0 16489
Lrtd Delay time of differential low temperature alarm at start 0 1000 min 10 0 16490
AHSC Set of high temperature alarm SC -40 100 °C 40 0 16539
ALARM MENU
Par. Description MIN MAX U.M. DEF. LIV Modbus
HSCd Delay time of high temperature alarm SC at start 0 1000 min 10 0 16540
ALSC Set of low temperature alarm SC -40 100 °C 8 0 16542
LSCd Delay time of low temperature alarm SC at start 0 1000 min 10 0 16543
HrSC Set of differential high temperature alarm SC 0 100 °C 0 0 16545
Delay time of differential high temperature alarm SC at
HrSd 0 1000 min 10 0 16546
start
LrSC Set of differential low temperature alarm SC 0 100 °C 0 0 16548
Delay time of differential low temperature alarm SC at
LrSd 0 1000 min 10 0 16549
start
AHSP Setpoint of antifreeze resistance -40 100 °C 5 0 16449
AHHy Differential of antifreeze resistance 0 50 °C 2 0 16450
HtEn Enabling resistance in normal mode 0 1 0 0 16456
HtSP Resistance Setpoint -40 100 °C 5 0 16454
HtHy Resistance differential 0 50 °C 2 0 16455
HEAT MENU
Par. Description MIN MAX U.M. DEF. LIV Modbus
AHSP Antifreeze resistance setpoint AHLS AHUS °C 5 0 16449
AHHy Differential antifreeze resistance 0 50 °C 2 0 16450
HtEn Enabling Resistance in Normal 0 1 0 0 16456
HtSP Resistance setpoint -40 100 °C 5 0 16454
HtHy Resistance differential 0 50 °C 2 0 16455
rEgH MENU
Par. Description MIN MAX U.M. DEF. LIV Modbus
HrEn Heating mode enabling 0 1 0 0 16514
HrSP Setpoint in heating -40 100 °C 15 0 16515
HrHy Differential in heating 0 50 °C 2 0 16516
AHrH Set of high temperature alarm in heating -40 100 °C 35 0 16517
ArHd Delay time of high temperature alarm in heating at start 0 1000 min 10 0 16518
AHrL Set of low temperature alarm in heating -40 100 °C 8 0 16520
ArLd Delay time of low temperature alarm in heating at start 0 1000 min 10 0 16521
SC2 MENU
Par. Description MIN MAX U.M. DEF. LIV Modbus
SCSP Setpoint Secondary circuit -40 100 °C 30 0 16534
SCSr Relative setpoint of secondary circuit -50 50 °C 0 0 16535
SCeE Enabling differential regulation SC 0 1 0 0 16538
SCti PID integral time, SC valve 0 1000 sec 40 0 16555
SCtd PID derivative time, SC valve 0 1000 sec 5 0 16556
I-O MENU
Par. Description MIN MAX U.M. DEF. LIV Modbus
ALOi Reverse polarity alarm relay 0 1 0 0 16563
F1Oi Reverse polarity alarm relay FF1 0 1 0 0 16568
F2Oi Reverse polarity alarm relay FF2 0 1 0 0 16569